2023-07-15 12:07:39 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 23060804 |
| 7/17/23 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FDHA- FAIR HOUSING DESIGN ACT MANUAL- 1998 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| |
| 1. GENERAL/ADMINISTRATIVE COMMENTS. |
| |
| 1) POTABLE WATER SERVICE BACKFLOW PREVENTER & GREASE |
| INTERCEPTORS: SEPARATE PERMITS ARE REQUIRED FOR THE |
| POTABLE WATER BACKFLOW PREVENTER AND THE GREASE |
| INTERCEPTORS- SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE |
| SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT BE |
| APPROVED UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED |
| ABOVE HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS |
| TBD (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS |
| SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO |
| [email protected]. YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL |
| OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| 2) SWIMMING POOL: A SEPARATE PERMIT IS REQUIRED FOR THE |
| POOL HOWEVER THE DETAIL ON SHEET P7-01 SHOWING POOL |
| WASTEWATER DRAINING INTO THE SANITARY SYSTEM IS NOT IN |
| COMPLIANCE WITH SEC. 90-126 (B)(5) WPB CODE OF |
| ORDINANCES. PLEASE NOTE THE FOLLOWING INFORMATION. |
| SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| DEPARTMENT. |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| -THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 3) IRRIGATION: SEPARATE PERMITS ARE REQUIRED FOR THE |
| IRRIGATION SYSTEM AND SYSTEM BACKFLOW PREVENTER. A |
| PRELIMINARY REVIEW OF SHEETS L5 & L5-A SYSTEM WAS |
| PERFORMED UNDER THIS MASTER PLAN AND THE PLANS APPEAR |
| INCOMPLETE PER THE FOLLOWING NOTES: |
| |
| A) WATER SOURCES, PUMPS, SHUTOFF VALVES, AND BACKFLOW |
| PREVENTERS NOT SHOWN. |
| |
| B) PIPING RUNS, PIPE SIZES AND LOCATIONS OF SLEEVES NOT |
| PROVIDED |
| |
| |
| 2. ARCHITECTURAL COMMENTS. |
| |
| 4) LS1-00: PLEASE REFER TO SEC. 233 FBC ACCESSIBILITY. |
| BASED ON SECS 233.3.1 & 233.3.1.1 AT LEAST 5% OF THE |
| TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL BE |
| PROVIDED WITH MOBILITY FEATURES COMPLYING WITH SECS. |
| 809.2- 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE; AND |
| AT LEAST 2% SHALL BE PROVIDED WITH COMMUNICATION |
| FEATURES COMPLYING WITH 809.4. THESE REQUIREMENTS ARE |
| SEPARATE FROM COMPLIANCE WITH THE FAIR HOUSING DESIGN |
| ACT REQUIREMENTS. REFER TO SEC. 233.3.5 DISPERSION AND |
| PROVIDE A LIST OR SCHEDULE ON THE PLAN SHOWING THE |
| LOCATIONS OF THE UNITS, AND REVISE THE ARCHITECTURAL |
| AND PLUMBING PLANS WHERE REQUIRED. |
| |
| 5) LS1-00, A6-35: THE APPLICABLE CODE DATA FOR THE |
| BUILDING INDICATES THE R2 APARTMENT UNITS ARE DESIGNED |
| IN ACCORDANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL |
| (1998). REFER TO PAGES 7.34 & 7.35 OF THE MANUAL AND |
| INDICATE ON BOTH PLANS WHICH DESIGN SPECIFICATION FOR |
| THE APARTMENT BATHROOMS AND FIXTURES INSTALLATIONS HAS |
| BEEN CHOSEN- SPECIFICATION A OR B. |
| |
| A) A7-04: PLEASE ADD COMPLIANCE DETAILS FOR THE |
| SHOWERS- PAGES 7.56- 7.59 FHDA MANUAL. |
| |
| 6) LS1-00: AS NOTED IN COMMENT #4 THERE ARE DESIGN |
| DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA COMPLIANT) |
| DWELLING UNIT AND A FHDA COMPLIANT UNITS HOWEVER SHEETS |
| A6-35 & A7-04 WHICH ARE INTENDED TO DEMONSTRATE FAIR |
| HOUSING COMPLIANCE ARE TITLED ENLARGED UNIT |
| ACCESSIBILITY PLANS & APARTMENT UNIT ACCESSIBILITY |
| STANDARDS WHICH CAN BE MISLEADING. PLEASE REFER TO SEC. |
| 809.4 FBC ACCESSIBILITY AND PROVIDE SEPARATE ENLARGED |
| ACCESSIBLE UNIT DRAWINGS WITH THE FOLLOWING COMPLIANCE |
| DETAILS PER SEC. 603- 610 FBC ACCESSIBILITY. PLEASE |
| NOTE SOME OF THE REQUIRED DETAILS ARE CURRENTLY SHOWN |
| ON A7-05. |
| |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SEC. 604.3. |
| |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- SEC. 606.2. |
| |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| |
| D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| WALLS- SEC. 604.2. |
| |
| E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- SEC. 604.4. |
| |
| F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| SURFACES FROM THE FINISHED FLOORS- SEC. 606.3. |
| |
| G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SEC. 603.3. |
| |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES |
| 604.5.1 & 604.5.2. |
| |
| I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| 604.7. |
| |
| J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| 606.2. |
| |
| K) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| BATHTUBS- SEC. 607.2. |
| |
| L) BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC. |
| 607.3. |
| |
| M) BATHTUB GRAB BAR DETAILS- SEC. 607.4. |
| |
| N) BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6. |
| |
| O) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| SHOWER- SECS. 608.2.1 & 608.2.2. |
| |
| P) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND |
| 608.3.2. |
| |
| Q) LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS IN |
| THE SHOWERS- SECS. 608.5.1 & 608.5.2. |
| |
| R) LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING |
| DETAILS- SECS. 610.3- 610.4. |
| |
| 7) A6.05: SHOW THE DIMENSIONS OF THE WATER CLOSET AND |
| LAVATORY CLEAR FLOOR SPACES- SECS. 604.3 & 606.2 FBC |
| ACC. |
| |
| 8) A6.05: THE RESTROOM DOORS SHALL NOT SWING INTO THE |
| CLEAR FLOOR SPACES FOR THE LAVATORIES- SEC. 603.2.3 FBC |
| ACC. |
| |
| 9) A1-01A: ENLARGED ACCESSIBLE PUBLIC RESTROOM FLOOR |
| PLAN DRAWINGS NOT PROVIDED- SEC. 603- 604 FBC ACC. |
| |
| 10) LS1-00: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED |
| OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH |
| TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A |
| SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER |
| OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS |
| ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL |
| BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND |
| PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC |
| RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE |
| FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS- |
| HI & LO. NO FOUNTAIN WAS SPECIFIED IN THE FIXTURE |
| SCHEDULES- SHEET P0-02. |
| |
| A) A1-01B: THE DRINKING FOUNTAIN AT THE PUBLIC RESTROOM |
| CORRIDOR IS PROTRUDING INTO THE CIRCULATION PATH AND |
| SHALL BE EITHER BE RECESSED IN A NICHE OR BARRIERS ON |
| EACH SIDE SHALL BE PROVIDED- SEC. 307.2 FBC ACC. |
| |
| B) A1-01B: PLEASE SHOW THE CLEAR FLOOR DIAGRAM AND |
| DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE FOUNTAIN |
| POSITIONED FOR A FORWARD APPROACH- SEC. 606.2 FBC ACC. |
| |
| C) A7-05: SHOW THE SPOUT HEIGHT FOR THE HI (STANDING |
| PERSONS) DRINKING FOUNTAIN- SEC. 602.7 FBC ACC. |
| |
| 11) LS-01, A1-05B & A6-06: THE POOL WILL BE UNDER |
| SEPARATE PERMIT HOWEVER A PRELIMINARY REVIEW OF THE |
| POOL BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER |
| TO SEC. & TABLE 403.6 AND PROVIDE PLUMBING FIXTURE |
| CALCULATIONS. THE PLANS SHOW ONE POOL RESTROOM BY THE |
| POOL AND ONE RESTROOM AT THE CLUB ROOM. PLEASE NOTE |
| THAT SEC. 451.6.1 STATES THAT POOLS WITH A BATHING LOAD |
| OF 20 PERSONS OR LESS MAY UTILIZE A UNISEX RESTROOM. |
| PLEASE PROVIDE BATHING LOAD CALCULATIONS IN ACCORDANCE |
| WITH SEC. 454.1.1.1 FBC B. |
| |
| B) PLEASE REFER TO SEC. 403.6 AND PROVIDE A URINAL AND |
| DIAPER CHANGING TABLE FOR THE POOL BATHROOM. A FLOOR |
| DRAINS AND HOSE BIB ARE ALSO REQUIRED FOR THE BATHROOMS |
| ACCORDING TO SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC |
| BUILDING. PLEASE NOTE THE HOSE BIB CAN BE PROVIDED IN |
| OR WITHIN 25 FT. OF THE RESTROOM. PLEASE REVISE THE |
| PLANS TO SHOW COMPLIANCE. |
| |
| C) PLEASE SHOW THE POOL SHOWER LOCATION- SEC. 454.1.6.2 |
| FBC B. |
| |
| 12) LS-01, A1-05B & A6-06: CONCERNING THE CLUBROOM AND |
| ROOFTOP LOUNGE REFER TO COMMENT #10. |
| |
| 13) A1-05B: THE POOL RESTROOM DOOR SHALL NOT SWING INTO |
| THE CLEAR FLOOR SPACE FOR THE LAVATORY- SEC. 603.2.3 |
| FBC ACC. |
| |
| 14) A1-01B & A7.05: SHOW THE CLEAR FLOOR SPACE FOR THE |
| WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN AND THE SPOUT |
| HEIGHT OF THE HI (STANDING PERSONS) FOUNTAIN- SEC. |
| 602.2 & 602.7 FBC ACC. |
| |
| 3. PLUMBING COMMENTS. |
| |
| 15) P2-00A: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH |
| BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES |
| BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3, |
| 708.1.8 EXCEPTION 2 FBC P. |
| |
| 16) P2-00A & P2-00B: IT APPEARS CLEANOUTS AT 100 FT. |
| INTERVAL SPACINGS ARE MISSING FOR THE 6-INCH SANITARY |
| SEWER LINE ON THE NORTH SIDE OF THE BUILDING- SEC. |
| 708.1.2 FBC P. |
| |
| 17) P2-00A & P-200B: PROVIDE A GROUND FLOOR SANITARY |
| DRAINAGE AND VENT ISOMETRIC FOR THE GROUND FLOOR WITH |
| WASTE AND SOIL STACK RISER LOCATIONS NUMBERED TO MATCH |
| WITH THE NUMBERED RISERS SHOWN ON SHEETS P6-02 & P6-03- |
| SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 710.1 FBC P. |
| |
| 18) P2-00A: SHOW UNDERGROUND STORM DRAIN PIPING RUNS |
| INCLUDING PIPE SIZES AND GPM FLOWS AS SHOWN ON P-200B- |
| SEC. 1106.2 FBC P. |
| |
| 19) P2-00A & P-200B: SHOW THE WATER HEATER DRAIN PAN |
| LINE RUNS AND TERMINATION LOCATIONS- SEC. 504.7.2 FBC |
| P. |
| |
| 20) P2-00A, P2-00B, P2-09A, P2-09B: PROVIDE A STORM |
| DRAIN RISER DRAWING SHOWING VERTICAL AND HORIZONTAL |
| PIPE RUNS AND SIZES FROM ROOFTOP TO DISPOSAL LOCATIONS- |
| SEC. 1106.2 & 1106.3 FBC P. PLEASE INCLUDE GPM FLOWS, |
| CLEANOUT LOCATIONS AND AC CONDENSATE PIPING POINTS OF |
| CONNECTIONS TO THE SYSTEM- SECS. 314.2.1, 1101.8 FBC P. |
| |
| 21) P2-00A, P2-00B & C2-3: THE PLUMBING UNDERGROUND |
| PLANS DO NOT MATCH WITH THE WATER AND WASTEWATER CIVIL |
| PLAN. THE PLUMBING PLANS DO NOT SHOW SANITARY DRAIN |
| CONNECTIONS INTO TEMPORARY LIFT STATIONS, AND THE CIVIL |
| PLANS DO NOT SHOW THE GREASE INTERCEPTORS, OR THE |
| SANITARY SER LINE ON THE NORTH SIDE OF THE BUILDING TO |
| NAME A FEW OF THE MANY INCONSISTENCIES- SEC. 107.2.1 |
| WPB. PLEASE CORRECT THE PLANS. AT THIS TIME THE CIVIL |
| PLANS WILL BE EXCLUDED FROM FURTHER PLUMBING REVIEW. |
| |
| 22) P0-02 & P2-00B & GREASE INTERCEPTORS GI-1. |
| |
| A) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE |
| INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE |
| SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P. |
| |
| B) P0-02: THE INTERCEPTOR EQUIPMENT SCHEDULE REFERS TO |
| SHEET P-702 WHICH WAS NOT INCLUDED WITH THE UPLOADED |
| PLAN SET- SEC. 107.2.1 WPB. |
| |
| C) P2-00B: THE PLAN DOES NOT IDENTIFY WHICH PLUMBING |
| FIXTURES AND APPLIANCES ARE DISCHARGING INTO THE GREASE |
| WASTE LINE. PLEASE PROVIDE A KITCHEN PLUMBING FIXTURE |
| EQUIPMENT PLAN AND SCHEDULE- SEC. 107.2.1 WPB. PLEASE |
| NOTE THE PLAN APPEARS TO SHOW DRAINAGE FROM A |
| 3-COMPARTMENT SINK AND A MOP SINK DISCHARGING INTO THE |
| SANITARY LINE INSTEAD OF THE GREASE WASTE LINE- SEC. |
| 1003.3.1 FBC P. |
| D) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE |
| VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE |
| 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS- |
| SEC. 918.8 FBC P. |
| |
| 23) P2-00B GREASE INTERCEPTOR GI-2: THE USE OF THE |
| GREASE INTERCEPTOR FOR TRASH ROOM DRAINAGE DOES NOT |
| APPEAR TO BE IN COMPLIANCE WITH SEC. 1003.3.1 FBC P. |
| PLEASE CLARIFY THE USE OF THE INTERCEPTOR. |
| |
| A) PROVIDE SIZING CALCULATIONS IN ACCORDANCE WITH SEC. |
| 1003.3.5 FBC P. |
| |
| B) P2-00B & P7-01: THE CLEANOUTS FOR THE GREASE |
| INTERCEPTORS REQUIRE HEAVY DUTY TRAFFIC LIDS. PLEASE |
| SPECIFY MAKES AND MODELS- SEC. 305.7 FBC P. |
| |
| C) P2-00B: REFER TO SEC. 1003.9 FBC P AND PROVIDE |
| VENTING FOR THE INTERCEPTOR. PLEASE NOTE THE AAV (NOTE |
| 2) CANNOT BE USED AS THE VENT FOR THE INTERCEPTORS- |
| SEC. 918.8 FBC P. |
| |
| 24) P2-00B & P5-01: THE DISCHARGES FROM THE ELEVATOR |
| SUMP PUMPS SHALL BE INDIRECTLY CONNECTED TO A WASTE |
| RECEPTOR WHICH IS EITHER A FLOOR DRAIN, FLOOR SINK, HUB |
| DRAIN OR STANDPIPE. DISPOSAL AT THE MOP SINK IS NOT IN |
| COMPLIANCE - SEC. 3002.4 FBC B, & SECS. 202 & 802.3 FBC |
| P. |
| |
| 25) P2-01A & P2-01B: PROVIDE A FIRST-FLOOR WATER |
| ISOMETRIC DRAWING WITH WATER RISER LOCATIONS NUMBERED |
| TO MATCH WITH THE NUMBERED RISERS SHOWN ON SHEET P6-01- |
| SECS. 107.2.1, 107.3.5.1.3 WPB & SEC. 604.1 FBC P. |
| |
| 26) P2-01B: SHOW THE WATER SERVICE ENTRANCE LOCATION |
| AND MAIN SHUTOFF VALVE FOR THE BUILDING- SEC. 603.1- |
| 603.2.1 & 606.1 FBC P. |
| |
| 27) P2-01B: SHOW THE WATER FEED LINE TO THE RETAIL |
| RESTROOMS AT DETAIL 4/P5.01- SEC. 107.2.1 WPB. |
| |
| 28) P2-01B: PLEASE PROVIDE WATER DISTRIBUTION DESIGN |
| CRITERIA- SEC. 604.3 FBC P. |
| |
| 29) P4-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER |
| RISER DRAWINGS NOT PROVIDED FOR THE TYPICAL APARTMENT |
| UNITS- SEC. 107.3.5.1.3 WPB. |
| |
| 30) P4-01: TWO-WAY CLEANOUTS FOR THE 3 & 4-INCH |
| BUILDING DRAINS ARE REQUIRED AT A POINT 30 INCHES |
| BEYOND THE EXTERIOR WALL OF EACH UNIT- SEC. 708.1.3, |
| 708.1.8 EXCEPTION 2 FBC P. |
| |
| 31) P2-08B, P5-01: ENLARGED SANITARY DRAINAGE/VENT |
| PLANS FOR THE POOL AND CLUBROOM/ROOFTOP LOUNGE |
| RESTROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB. |
| |
| 32) P5-01: ENLARGED SANITARY DRAINAGE/VENT AND WATER |
| ISOMETRIC DRAWINGS NOT PROVIDED FOR THE 1ST FLOOR |
| PUBLIC, RETAIL, POOL AND CLUBROOM/LOUNGE BATHROOMS- |
| SEC. 107.3.5.1.3 WPB. |
| |
| 33) P5-01: COLD OR TEMPERED WATER SHALL BE DELIVERED |
| FROM THE LAVATORIES- SEC. 419.5. |
| |
| 34) P5.01: THE 1/2-INCH HOT WATER FIXTURE SUPPLY PIPES |
| TO THE RETAIL RESTROOM LAVATORIES ARE EXCEEDING THE |
| MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER |
| SOURCES- TABLE C404.5.1 FBC ENERGY. |
| |
| 35) P4-01 & P5-01: A MEANS OF LIMITING THE TEMPERATURE |
| OF THE HOT WATER DELIVERY TO THE FIXTURES IS REQUIRED |
| OTHER THAN THE WATER HEATER THERMOSTAT- SEC. 607.1.1 |
| FBC P. PLEASE PROVIDE MASTER THERMOSTATIC MIXING |
| VALVES. |
| |
| 36) P6-02 & P6-03: THE VENT STACKS SHALL CONNECT TO THE |
| BASES OF THE DRAINAGE STACKS AT A POINT BELOW THE |
| LOWEST HORIZONTAL BRANCH. CONNECTIONS AT THE LAVATORY |
| DRAINS DO NOT MEET COMPLIANCE- SECS. 904.2 & 904.4 FBC |
| P. |
| |
| 37) P2-09A, P2-09B: AS PREVIOUSLY NOTED IN COMMENT #10 |
| A STORM RISER ISOMETRIC DRAWING IS REQUIRED- SEC. |
| 107.3.5.1.3 WPB. |
| |
| A) P2-09A, P2-09B: SECONDARY/EMERGENCY ROOF DRAINAGE |
| WILL BE HANDLED BY OVERFLOW SCUPPERS AS STATED IN NOTE |
| B. THE LOCATIONS OF THE SCUPPERS SHALL BE SHOWN ON THE |
| PLANS, AND A CONSTRUCTION DETAIL SHOWING THE SCUPPER |
| OPENING DIMENSIONS, AND HEIGHT ABOVE ROOF ETC. SHALL BE |
| PROVIDED- SECS. 1108.1- 1108.3 FBC P. |
| |
| 38) P0-01: PLUMBING FIXTURE CALCULATIONS FOR THE MIXED |
| OCCUPANCY BUILDING ARE REQUIRED IN COMPLIANCE WITH |
| TABLE 403.1 & SEC. 403.1.1 FBC P. PLEASE PROVIDE A |
| SCHEDULE THAT ITEMIZES THE REQUIRED AND PROVIDED NUMBER |
| OF FIXTURES. PLEASE NOTE THAT WHERE DRINKING FOUNTAINS |
| ARE REQUIRED A MINIMUM OF TWO- ONE HI AND ONE LO- SHALL |
| BE PROVIDED- SEC. 410.3 FBC P. THE ARCHITECTURAL AND |
| PLUMBING PLANS SHOW ONE DRINKING FOUNTAIN AT THE PUBLIC |
| RESTROOMS WHICH DOES NOT MEET COMPLIANCE UNLESS THE |
| FOUNTAIN MEETS EXCEPTION 1 AND HAS TWO SEPARATE SPOUTS- |
| HI & LO. NO FOUNTAIN WAS SPECIFIED ON SHEET P0-02. |
| |
| 39) P0-01, P2-08B: THE POOL WILL BE UNDER SEPARATE |
| PERMIT HOWEVER A PRELIMINARY REVIEW OF THE POOL |
| BATHROOMS AND PLUMBING IS REQUIRED. PLEASE REFER TO |
| SEC. 403.6 AND PROVIDE A URINAL AND DIAPER CHANGING |
| TABLE FOR EACH POOL BATHROOM. FLOOR DRAINS AND HOSE |
| BIBS ARE ALSO REQUIRED FOR THE BATHROOMS ACCORDING TO |
| SECS. 454.1.6.1.3 & 454.1.6.1.4 FBC BUILDING. PLEASE |
| NOTE THE HOSE BIB CAN BE PROVIDED IN OR WITHIN 25 FT. |
| OF EACH RESTROOM. PLEASE REVISE THE PLANS TO SHOW |
| COMPLIANCE. |
| |
| 40) P2-08B, P6-01, P6-02, P-6-03: PROVIDE PLUMBING |
| PLANS AND RISERS FOR THE POOL AND CLUBHOUSE RESTROOMS |
| AND THE BAR SINK- SEC. 107.2.1 & SEC. 107.3.5.1.3 WPB. |
| |
| 41) P0-01: PLEASE PROVIDE TESTED AND APPROVED |
| FIRESTOPPING ASSEMBLIES FOR PLUMBING PIPES PENETRATING |
| FIRE-RATED WALLS AND FLOORS- SEC. 315.1 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |