Plan Review Details - Permit 23060579
Plan Review Stops For Permit 23060579
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By cpuell Date 2023-06-29 Time 16:22 Rev Time 0.00
Received By cpuell Date 2023-06-29 Time 16:22 Sent To  
Notes
2023-06-29 16:22:38TWO ADDRESS ISSUES WITH THIS PROJECT. FIRSTLY THERE ARE
 CURRENTLY TWO ADDRESSES ASSOCIATED WITH THIS SITE 625
 25TH ST WHICH HAD MOST RECENTLY RUN AN AUTO MECHANIC
 SHOP AND 2603 PINEWOOD AVE WHICH HAS BEEN RUNNING AS A
 WAREHOUSE. THE SITE PLAN SHOWS A RECTANGULAR BUILDING,
 BUT THE RENOVATED AREA OF WORKS SHOWS MORE OF AN L
 SHAPE. IS THE INTENT THAT NO WORK IS TO HAPPEN ON 625
 25TH ST? THE SECOND ISSUE IS THAT THE DUE TO THE
 RECONFIGURATION OF THE SPACE, A NEW ADDRESS WILL NEED
 TO BE ASSIGNED DUE TO THE NEW ENTRANCE TO THE BUSINESS
 NOW BEING ON 25TH ST. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESS ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 10:34 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 10:33 Sent To  
Notes
2023-07-18 10:33:57COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 11:26 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 08:11 Sent To  
Notes
2023-07-18 11:22:59WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23060579
 ADD: 2603 PINEWOOD
 CONT: BUILTMORE CONTRACTING INC.
 TEL: 561-331-1476
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JULY 18TH/23
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN:
 1A) BOTH THE LIFE SAFETY PLAN AND FLOOR PLAN SHOW AN
 ENLARGED UNISEX RESTROOM, BUT THE EXISTING WALL LINES
 OF THE OLD RESTROOM STILL SHOW WITH AN INSWING DOOR.
 THE PLUMBING FLOOR PLAN SHOWS THE WALL CONFIGURATION
 CORRECTLY. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
 1B) STORAGE ROOM 909 SQ. FT. SHOWS AN EMERGENCY BATTERY
 LIGHT WALL PACK WITH EXIT SIGN BUT THERE IS NO EXIT
 BENEATH THE BATTERY BACKPACK. DISCREPANCY IN PLANS.
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 1C) NEITHER OF THE LARGE STORAGE AREAS SHOW THE EXIT
 DIRECTIONAL NOR THE 2 SMALL STORAGE ROOMS SHOW EXIT
 LIGHTS FROM THE ROOMS. 2020 FBC-BUILDING CODE SECTION
 1013.1.
 1D) THE TASTING ROOM SHOWS 6 CHAIRS WITH TABLE LOT THEN
 A 4 FOOT SECTION OF TABLE TOP, THE PLANS ARE NOT CLEAR
 AS TO THE HEIGHT OF EITHER SECTION OF THE TABLE, IF THE
 ONE WITHOUT A CHAIR IS TO REPRESENT AN ACCESSIBLE
 SECTION OF THE TABLE, PLANS ARE NOT CLEAR. THE LIFE
 SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
 1E) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 1F) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 2) THE LIFE SAFETY PLAN NOR FLOOR PLAN SHOW WALL
 ELEVATIONS OF THE NEW ACCESSIBLE RESTROOM AND ACCESSIB
 2A) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE
 WATER CLOSET. SECTION 604.3
 2B) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE
 LAVATORIES. SECTION 606.2.
 2C) TURNING SPACE DIAMETERS. SECTION 304.3
 2D) CENTERLINE OF THE WATER CLOSETS FROM THE NEAREST
 SIDE WALL. SECTION 604.2.
 2E) HEIGHT OF THE WATERCLOSET SEATS FROM FINISH FLOOR.
 SECTION 604.4.
 2F) HEIGHT OF THE LAVATORIES AND OR SINKS OR COUNTER
 SURFACES FROM THE FINISH FLOOR. SECTION 606.3.
 KNEE & TOE SPACE REQUIRED BY SECTION 306.2 TOE
 CLEARANCE, 306.3 KNEE CLEARANCES, 2020 FBC-
 ACCESSIBILITY CODE. INSULATE PIPES PER SECTION
 2G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE BOTTOM EDGE OF THE REFLECTIVE SURFACE, MIRRORS
 ABOVE SINKS. SECTION 606.3.
 2H) LOCATIONS, LENGTHS AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS SEE SECTION 604.5, 609.4 &.
 FIGURE 604.
 2I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS.
 SECTION 604.6.
 2J) CENTERLINES OF THE TOILET DISPENSER MEASURED FROM
 THE FRONTS OF THE WATER CLOSET. SECTION & FIGURE 604.7
 2K) 2020 FBC-ACCESSIBILITY CODE. 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH 602.7.
 2L) PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS 307.2.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES AND NOT
 MORE THAN 80 INCHES ABOVE THE FLOOR SHALL
 NOT PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
 2M) 602.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306
 SHALL BE PROVIDED.
 2N) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 ACCESS.
 CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38 TO 43 INCHES ABOVE FINISH FLOOR.
  
  
  
  
  
 3) NEITHER THE LIFE SAFETY PLAN NOR THE FLOOR PLANS
 PROVIDE WALL FINISH SCHEDULE FOR RESTROOMS AND SERVICE
 SINKS. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 2020 FBC-BUILDING 1210.2.2 WALLS & PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 4) THE SITE PLAN SHOWS AN EXTENDED STRIPPED WALKWAY TO
 BUILDING. THE SITE PLAN APPEARS TO BE POSSIBLY HAVE A
 CANOPY NOT SHOWN ON THE LIFE SAFETY PLAN NOR ANY FLOOR
 PLAN. WHICH DOORWAY IS GOING TO BE THE MAIN ENTRY/ EXIT
 DOORWAY NEEDING TO SHOW COMPLIANCE WITH 2020
 FBC-ACCESS. CODE CHANGES IN LEVEL 303.2 AND 303.3.
 WHERE CHANGES IN LEVEL ARE PERMITTED IN THE FLOOR OR
 GROUND SURFACES, THEY SHALL COMPLY WITH SECTION 303.
 SEE 303.1 & 303.2.
  
 5) THIS PERMIT IS FOR AN INTERIOR REMODEL, NOT EXISTING
 PARKING, OR ACCESSIBLE PARKING NOR EXTEND STRIPPING TO
 BUILDING. CLARIFICATION ONLY, NO ACTION IS REQUIRED ON
 THE DESIGNER???S PART.
  
 6) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-07-10 Cont ID  
Sent By jleahy Date 2023-07-10 Time 16:44 Rev Time 0.00
Received By jleahy Date 2023-07-10 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 10:29 Sent To  
Notes
2023-07-06 13:44:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS ARE NO INDICATIONS OF EXIT SIGNS &
 EMERGENCY LIGHTING ON THE ELECTRICAL PLAN SHEET.
  
 EXITS SIGNS & EMERGECNY LIGHTING SHALL INSTALLED AS
 REQUIRED PER NFPA 101 CH 7, MEANS OF EGRESS AND
 INDICATED ON THE LIFE SAFETY SHEET AND
 ELECTRICAL/LIGHTING SHEET AS APPLICABLE TO THE EXIT
 TRAVEL PATHS AND EXIT DOORS
  
 PLEASE REVIEW AND CORRECT/PROVIDE PER THE REQUIRMENTS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By ccole Date 2023-07-10 Time 11:01 Rev Time 0.00
Received By ccole Date 2023-07-07 Time 17:02 Sent To  
Notes
2023-07-10 11:02:451ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23060579
 7/10/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 5A GAS RISER CORRECTIONS:
  
 A) THE GAS LOAD CALCULATIONS SHOW TWO 90,000 BTU
 ROASTERS AT TOTAL LOAD OF 180,000 BTUH. THE RISER SHOWS
 ONE ROASTER AT 144,000 BTUH.
  
 B) THE 3/4-INCH MAIN SUPPLY PIPE IS UNDERSIZED FOR A
 TOTAL LOAD OF 180,000 BTUH AT 37 FT. TOTAL DEVELOPED
 LENGTH- TABLE 402.4(2) FBC FG.
  
 2) 5A: THE METER IS CALLED OUT AS EXISTING. PLEASE
 MODIFY THE RISER DRAWING TO SHOW ALL EXISTING PIPING
 AND APPLIANCES THAT ARE CONNECTED TO THE SYSTEM- SECS.
 401.3 & 401.4 FBC P.
  
 3) 5A: COMBUSTION AIR CORRECTIONS:
  
 A) REMOVE MECHANICAL SUPPLY CALCULATION. IT IS NOT
 CONSISTENT WITH THE TWO OUTDOOR AIR OPENINGS METHOD
 SHOWN ON THE PLANS.
  
 B) REFER TO SEC. 304.6.1 AND REVISE THE CALCULATION FOR
 EACH OPENING TO INDICATE 1 SQ. INCH OF FREE AIR PER
 4000 BTUH REQUIRED, OR 45 SQ. INCHES PER OPENING,
  
 C) SHOW THE UPPER OPENING WILL COMMENCE WITHIN 12
 INCHES OF THE TOP OF THE ENCLOSURE- SEC. 304.6.1.
  
 4) COFFEE ROASTER VENTING: A COMPLETE REVIEW OF THE
 VENTING SYSTEM CANNOT BE ACCOMPLISHED WITHOUT SUBMITTAL
 OF MANUFACTURER'S SPECIFICATIONS FOR THE ROASTERS AND
 FOR THE VENT DUCTS- SECS. 305.1, 503.4 & 503.7 FBC FG.
 BASED ON THE NOTES ON THE PLAN THE DUCTS SHALL BE UL
 LISTED AND LABELED AND SUITABLE FOR 1000 DEGREES F
 CONTINUOUS, AND 1400 DEGREES F INTERMITTENT. REFER TO
 SEC. 202 AND ADD NOTES ON THE PLAN TO INDICATE THE
 CATEGORY OF THE COFFEE ROASTERS- 1, II, II, OR IV, AND
 THE TYPE OF VENTING SYSTEMS- FORCED DRAFT, INDUCED
 DRAFT, MECHANICAL DRAFT OR NATURAL DRAFT. PLEASE NOTE
 ALL SUBMITTALS SHALL BEAR THE APPROVAL STAMP OF THE
 ENGINEER OF RECORD- SEC. 107.3.4 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-19 Cont ID  
Sent By hmoser Date 2023-07-19 Time 13:18 Rev Time 0.00
Received By hmoser Date 2023-06-28 Time 15:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-07-18 Cont ID  
Sent By jwitmer Date 2023-07-18 Time 10:35 Rev Time 0.00
Received By jwitmer Date 2023-07-18 Time 10:34 Sent To  
Notes
2023-07-18 10:34:54IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 23031230
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM???S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-07-19 Cont ID  
Sent By hmoser Date 2023-07-19 Time 13:18 Rev Time 0.00
Received By hmoser Date 2023-07-19 Time 11:12 Sent To  
Notes
2023-07-19 13:18:12PLAN DENIED
 PROVIDE MORE INFORMATION ON THE ROSTERS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-10 Cont ID  
Sent By ccole Date 2023-07-10 Time 07:41 Rev Time 0.00
Received By ccole Date 2023-07-06 Time 11:08 Sent To  
Notes
2023-07-10 07:47:101ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060579
 7/7/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET C-1: DRINKING FOUNTAINS ARE REQUIRED FIXTURES
 FOR FACTORY/INDUSTRIAL, BUSINESS, AND ASSEMBLY
 OCCUPANCIES- TABLE 403.1 FBC P. A MINIMUM OF TWO SHALL
 BE INSTALLED- ONE HI AND ONE LO- SEC. 410.3. PLEASE
 REVISE THE DRAWINGS TO SHOW THE LOCATION, ACCESSIBILITY
 DETAILS, AND PLUMBING PIPING REQUIREMENTS.
  
 2) 7P: PROVIDE A VENT FOR THE MOP SINK FIXTURE TRAP-
 SECS. 909.1, 910.1 FBC P.
  
 3) 7P: WPB BUILDING DEPT. PERMITTING RECORDS DO NOT
 SHOW ANY PERMITS ON FILE FOR THE EXISTING BATHROOMS,
 AND 3-COMPARTMENT SINK. PLEASE PROVIDE COMPLETE
 PLUMBING PLANS INCLUDING THE FOLLOWING ITEMS AS
 REQUIRED BY SECS. 107.2.1 & 107.3.5.1.3 WPB.
  
 A) WATER PIPING LAYOUT PLAN: SHOW WATER SERVICE
 ENTRANCE, LOCATION OF METER AND BACKFLOW PREVENTER, AND
 HOT AND COLD WATER DISTRIBUTION PIPING RUNS THROUGH THE
 TENANT SPACE.
  
 B) SANITARY PIPING LAYOUT PLAN: SHOW UNDERSLAB SANITARY
 AND GREASE WASTE PIPING RUNS THROUGH THE TENANT SPACE.
  
 C) PLUMBING RISER DRAWINGS INCLUDING SANITARY, GREASE
 WASTE, AND WATER DISTRIBUTION.
  
 D) PLUMBING FIXTURE AND APPLIANCE SCHEDULE.
  
 E) WATER HEATER AND TANK EQUIPMENT SCHEDULES AND PIPING
 DIAGRAM. PLEASE INCLUDE THE PAN DRAIN PIPING
 TERMINATION LOCATION IN THE DIAGRAM.
  
 E) GREASE WASTE INTERCEPTOR: A GREASE INTERCEPTOR IS
 REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES WITH
 GREASE LADEN WASTE. PLEASE SHOW THE LOCATION OF THE
 INTERCEPTOR AND PROVIDE AN EQUIPMENT SCHEDULE, SIZING
 CALCULATIONS, PIPING DIAGRAM. PLEASE NOTE A SEPARATE
 PERMIT IS REQUIRED FOR INSTALLATION- SEE NOTE BELOW.
  
 F) PLUMBING DEVICES: THE WATER PIPING PLANS SHALL SHOW
 THE LOCATIONS OF REQUIRED MIXING VALVES, INLINE
 BACKFLOW PREVENTERS TO APPLIANCES AND EQUIPMENT, AND
 WATER HAMMER ARRESTORS. PLEASE NOTE THE FOLLOWING CODE
 SECTIONS.
  
 SEC. 419.5 REQUIRES TEMPERED WATER DELIVERY FROM THE
 PUBLIC LAVATORY IF THE LAVATORY HAS HOT WATER SUPPLY.
  
 SEC. 607.1.1 REQUIRES A MEANS OF LIMITING THE HOT WATER
 TEMPERATURE DELIVERY AT THE FIXTURES OTHER THAN THE
 THERMOSTAT ON THE WATER HEATER.
  
 SEC. C404.5.1 FBC ENERGY LIMITS THE LENGTH OF A
 1/2-INCH HOT WATER SUPPLY PIPE TO A PUBLIC LAVATORY TO
 2 FT.
  
 4) CIVIL PLANS ARE REQUIRED FOR WORK INVOLVING NEW OR
 ALTERED UNDERGROUND SERVICE PIPING INCLUDING WATER,
 SANITARY, STORM DRAINAGE, FIRE LINES, GAS AND ELECTRIC.
 THE PLANS SHALL SHOW POINTS OF CONNECTIONS TO EXISTING
 MAIN SERVICE PIPES.
  
 5) DUE TO A CHANGE IN PROCESS, GREASE INTERCEPTOR
 PERMIT APPLICATION IS REQUIRED TO BE SUBMITTED PRIOR TO
 PLUMBING PLAN REVIEW APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-10 Cont ID  
Sent By jleahy Date 2023-07-10 Time 16:46 Rev Time 0.00
Received By jleahy Date 2023-07-10 Time 16:46 Sent To  
Notes
2023-07-07 15:50:42PLUMBING & MECHANICAL SIGNATURES PASSED.

Review Stop Z ZONING
Rev No 1 Status P Date 2023-07-11 Cont ID  
Sent By vbroglia Date 2023-07-11 Time 12:07 Rev Time 0.00
Received By vbroglia Date 2023-07-11 Time 12:07 Sent To  
Notes
***NONE***