Plan Review Details - Permit 23060501
Plan Review Stops For Permit 23060501
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 12:28 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 12:28 Sent To  
Notes
2023-06-14 12:29:22PARCEL NEEDS TO BE READDRESSED SO THAT THE ENTRANCES ON
 THE GROUND FLOOR FALLS IN LINE WITH THE CITY'S ROAD
 CENTER LINES. ADDRESSES THAT NEED TO BE ESTABLISHED
 WOULD BE FOR THE BUILDING ITSELF AND ALL THE APARTMENT
 UNITS ON ALL THE FLOORS. PLEASE CONTACT [email protected]
 OR CALL 561-805-6659 TO WORK ON THE READDRESSING
 ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2023-07-21 16:09:06SUBJECT TO PUBLIC ART - ART ASSESSMENT SENT 7.21.23
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By lbond Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-13 Cont ID  
Sent By mpeterso Date 2023-07-13 Time 12:47 Rev Time 0.00
Received By mpeterso Date 2023-06-28 Time 14:09 Sent To  
Notes
2023-07-13 12:52:55I WOULD LIKE TO START THIS REVIEW BY COMPLIMENTING THE
 ENGINEERS AND STAFF WHO CONTRIBUTED TO A LARGE AND
 COMPLICATED PROJECT. THESE ELECTRICAL PLANS APPEAR TO
 HAVE BEEN CAREFULLY PUT TOGETHER, WITH GREAT THOUGHT
 AND ATTENTION TO DETAIL AND THE ELECTRICAL CODES. I
 HAVE ONLY SOME MINOR COMMENTS ON CODE COMPLIANCE AND
 ADDITIONAL INFORMATION REQUIRED FOR THIS SUBMITTAL. I
 HAVE OUTLINED THESE BELOW.
  
 1) FAULT CURRENT CALCULATIONS AND SELECTIVE
 COORDINATION STUDIES BY THE NATURE OF THEIR PURPOSE
 SHOULD BE PROVIDED BEFORE SELECTING AND INSTALLING
 EQUIPMENT FOR ELECTRICAL PROJECTS. PLEASE PROVIDE THE
 APPROPRIATE AVAILABLE FAULT CURRENT SUPPLIED BY THE
 UTILITY AND THE RESULTING FAULT CURRENT CALCULATIONS AS
 REQUIRED PER NEC 110.10 AND A NOTE STATING FIELD
 MARKING TO BE DONE IN ACCORDANCE WITH NEC110.24. IN
 ADDITION, PLEASE PROVIDE STAMPED SELECTIVE COORDINATION
 STUDY IN ACCORDANCE WITH NEC 700.32 FOR THE EMERGENCY
 STANDBY SYSTEM.
  
 2) SHEET E1.1.3A DETAILS A NOTE 7 ON STATES THERE WILL
 BE AN EPO PUSHBUTTON WIRED TO ALL MAIN BREAKERS TO
 PROVIDE BUILDING WIDE SHUTDOWN OF POWER. THE RISER
 DIAGRAMS AND PANEL SCHEDULES SUBMITTED ONLY DETAIL
 SHUNT TRIP BREAKER ON PANEL OSDP. IF SHUNT TRIP
 BREAKERS ARE TO BE INSTALLED AS STATED IN NOTE, PLEASE
 DETAIL THEM ON ALL RISER DIAGRAMS AND PANEL SCHEDULES
 AS APPLICABLE. NEC 215.5
  
 3) SHEET E1.6.2B DETAILS A 50-AMP RECEPTACLE FOR A
 MULTI COOKER. PLEASE DETAIL THIS RECEPTACLE AS BEING
 GFIC PROTECTED IN ACCORDANCE WITH NEC 210.8
  
 4) SHEET E3.2.2 DETAILS WHAT APPEARS TO BE A FLOOR TO
 CEILING WINDOW IN THE LOFT ROOM WITH A LENGTH OF
 APPROXIMATELY 24 FEET. PLEASE DETAIL THE REQUIRED FLOOR
 OR WALL RECEPTACLES IN ACCORDANCE WITH NEC 210.52
  
 5) ALL SHEETS DETAILING PATIO KITCHENS APPEAR TO HAVE
 ONLY ONE SMALL APPLIANCE RECEPTACLE CIRCUIT SUPPLYING
 THE COUNTERTOP RECEPTACLES. THE REQUIREMENT IN
 ACCORDANCE WITH NEC 210.52(B)(3) IS TO HAVE TWO SMALL
 APPLIANCE CIRCUITS TO FEED THESE COUNTERTOP
 RECEPTACLES. PLEASE CORRECT AS APPLICABLE.
  
 6) ALL RESIDENTIAL UNIT???S DETAIL REFRIGERATION AND
 FREEZER RECEPTACLE BRANCH CIRCUITS SUPPLIED FROM AN
 OPTIONAL STANDBY PANEL NOT LOCATED IN THE RESIDENTIAL
 PREMISE. PLEASE PROVIDE CLARITY ON HOW THIS IS
 COMPLIANT IN ACCORDANCE WITH NEC 240.24(B). DO
 OCCUPANTS HAVE READY ACCESS TO ELECTRIC ROOMS AND READY
 ACCESS TO FLOORS OTHER THAN WHERE THEY RESIDE?
  
 NEC 240.24 (B) OCCUPANCY. EACH OCCUPANT SHALL HAVE
 READY ACCESS TO ALL OVERCURRENT DEVICES PROTECTING THE
 CONDUCTORS SUPPLYING THAT OCCUPANCY, UNLESS OTHERWISE
 PERMITTED IN 240.24(B)(1) AND (B)???(2).
  
  PLEASE BE AWARE THAT MANY LOW VOLTAGE AND OTHER TYPES
 OF WIRING ARE NOT INCLUDED WITH THIS PERMIT AND REQUIRE
 SEPARATE PERMITS. EXAMPLES OF WIRING SYSTEMS AND OTHER
 ITEMS REQUIRING SEPARATE PERMITS INCLUDE BUT ARE NOT
 LIMITED TO, LOW VOLTAGE WIRING SYSTEMS SUCH AS DAS/BDA,
 FIRE ALARM, SECURITY, AUDIO, VIDEO, VOICE, DATA,
 ACCESS, AND POOLS, SIGNS, GENERATORS, LANDSCAPE
 LIGHTING AND LIGHTNING PROTECTION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-06-23 Cont ID  
Sent By cseifer Date 2023-06-23 Time 14:26 Rev Time 0.00
Received By cseifer Date 2023-06-23 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By pleduc Date 2023-07-14 Time   Rev Time 0.00
Received By pleduc Date 2023-07-11 Time 14:51 Sent To  
Notes
2023-07-14 09:55:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) LIFE SAFETY & ELECTRICAL SHEETS - THERE APPEARS TO
 BE DISCREPANCIES OF EXIT SIGNS MARKING THE TRAVEL PATHS
 LEADING TO AN EXIT.
  
 PER NFPA 101 CH 7 MEANS OF EGRESS
  
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCORDANCE
 WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS 11 THROUGH
 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT
 ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR 100 FT (30 M),
 WHICHEVER IS LESS, FROM THE NEAREST SIGN
  
 ENSURE EXIT TRAVEL PATHS IS MARKED WITH EXIT SIGNS PER
 NFPA 101 CH 7 ON BOTH THE LIFE SAFETY & ELECTIRCAL
 PLANS.
  
 2) FIRE ALARM DOCUMENTATION - THERE DOES NOT APPEAR TO
 BE FIRE ALARM DOCUMENTATION IN COMPLAINCE WITH F.A.C.
 61G
  
 PER F.A.C.
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER???S INTENDED USE AND
 PROPOSED PROTECTION OF THE BUILDING OR FACILITY AND TO
 PROVIDE SUFFICIENT DIRECTION TO THE INSTALLATION
 CONTRACTOR OR OTHER INTERESTED PARTIES REGARDING THE
 LAYOUT OF THE SYSTEM(S), SHALL BE INCLUDED IN THE FIRE
 PROTECTION SYSTEM ENGINEERING DOCUMENTS.
  
  
 61G15-32.008 DESIGN OF FIRE ALARMS AND DETECTION
 SYSTEMS.
 (1) FIRE ALARMS AND DETECTION SYSTEMS INCLUDE FIRE
 PROTECTION SUPERVISION, EMERGENCY ALARM CIRCUITS,
 ACTIVATION OF LIFE SAFETY SYSTEM CONTROLS AND REMOTE
 SIGNALING OF EMERGENCY CONDITIONS.
 (2) THE DESIGN SPECIFICATIONS SHALL BE BASED ON THE
 FLORIDA BUILDING CODE (2007), THE FLORIDA FIRE
 PREVENTION CODE, OR AS REQUIRED BY THE LOCAL AUTHORITY
 HAVING JURISDICTION.
 (3) FOR FIRE ALARM PLANS ON SMALL SYSTEMS BELOW THE
 THRESHOLD REQUIREMENTS FOR MANDATORY USE OF
 PROFESSIONAL ENGINEERING SERVICES, THE ENGINEER OF
 RECORD SHALL SPECIFY THE MINIMUM SYSTEM REQUIREMENTS.
 (4) TO ENSURE MINIMUM DESIGN QUALITY OF FIRE ALARM AND
 DETECTION SYSTEMS ENGINEERING DOCUMENTS, SAID DOCUMENTS
 SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION
 WHEN APPLICABLE:
 (A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND,
 SYSTEM RISER DIAGRAM SHOWING ALL INITIATION AND
 NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS.
 INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS
 DETERMINED BY THE SYSTEM???S SURVIVABILITY
 REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE
 PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS
 IT IS CLEAR FROM FEATURES SHOWN.
 (B) LOCATE INITIATION AND NOTIFICATION DEVICES AND
 CONNECTIONS TO RELATED SYSTEMS ON THE FLOOR PLANS AND
 SECTIONS WHEN NEEDED FOR CLARITY. RELATED SYSTEMS
 INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS,
 DAMPERS, AND DOORS.
 (C) STROBE INTENSITY AND SPEAKER OUTPUT RATINGS FOR ALL
 NOTIFICATION DEVICES.
 (D) IDENTIFY THE CLASS AND STYLE OF CIRCUITS AS LISTED
 IN THE NFPA 72.
 (E) IDENTIFY THE FUNCTIONS REQUIRED BY THE ALARM AND
 CONTROL SYSTEMS INCLUDING THE TRANSMISSION OF EMERGENCY
 SIGNALS BEING MONITORED OR ANNUNCIATED.
 (F) INDICATE WHETHER THE FIRE ALARM IS CONVENTIONAL OR
 ADDRESSABLE, AND INDICATE ALL ZONING.
 (G) LOCATE SURGE PROTECTIVE DEVICES AND REQUIRED
 PROTECTIVE FEATURES.
 (H) LOCATE SYSTEM DEVICES THAT ARE SUBJECT TO
 ENVIRONMENTAL FACTORS, AND INDICATE REQUIREMENTS FOR
 THE PROTECTION OF EQUIPMENT FROM TEMPERATURE, HUMIDITY
 OR CORROSIVE ATMOSPHERES, INCLUDING COASTAL SALT AIR.
 (I) THE PLANS SHALL INCLUDE A SITE PLAN OF THE
 IMMEDIATE AREA AROUND THE PROTECTED BUILDING, STRUCTURE
 OR EQUIPMENT WHEN ALARM DEVICES ARE REQUIRED OUTSIDE
 THE STRUCTURE.
 (J) IN BUILDINGS WERE SMOKE DETECTION WILL BE
 OBSTRUCTED BY WALLS, BEAMS OR CEILING FEATURES, THE
 ENGINEER OF RECORD SHALL PROVIDE APPLICABLE DESIGN AND
 DETAILS TO DIRECT THE INSTALLER TO MITIGATE THE
 OBSTRUCTIONS. IN BUILDINGS WITH SMOKE DETECTION UNDER A
 PITCHED ROOF, THE PLANS SHALL INDICATE THE ROOF PITCH
 AND A BUILDING SECTION SHALL BE PROVIDED AS PART OF THE
 ENGINEERING DESIGN DOCUMENTS.
 (K) FIRE DETECTION SYSTEMS UTILIZING SMOKE DETECTION IN
 SITUATIONS WHERE SMOKE STRATIFICATION IS ANTICIPATED,
 THE DESIGN SHALL PROVIDE THE NECESSARY CRITERIA TO
 MITIGATE THE DETECTION PROBLEMS.
 (L) SYSTEMS DESIGNED USING PERFORMANCE BASED CRITERIA
 SHALL BE IDENTIFIED AND REFERENCED TO DESIGN GUIDES OR
 STANDARDS APPROVED BY THE LOCAL AUTHORITY HAVING
 JURISDICTION CONSISTENT WITH STANDARDS ADOPTED BY THE
 FLORIDA FIRE PREVENTION CODE AND THE FLORIDA BUILDING
 CODE (2007).
 (M) THE SYSTEM DESIGN MUST INDICATE IF THE SYSTEM IS TO
 PROVIDE A GENERAL EVACUATION SIGNAL OR A ZONED
 EVACUATION FOR ALL HIGH-RISE BUILDINGS OR
 MULTI-TENANTED PROPERTIES AS DEFINED IN THE FLORIDA
 BUILDING CODE (2007).
 (N) WIRING REQUIREMENTS FOR UNDERGROUND, WET LOCATIONS,
 CAMPUS STYLE WIRING, PROTECTION AGAINST DAMAGE AND
 BURIAL DEPTH SHALL BE SPECIFIED OR INDICATED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (O) REQUIREMENTS FOR OPERATIONS AND MAINTENANCE
 PROCEDURES, MANUALS, SYSTEM DOCUMENTATION, AND
 INSTRUCTION OF OWNER???S OPERATING PERSONNEL, AS NEEDED
 TO OPERATE THE SYSTEMS AS INTENDED OVER TIME.
 (5) IN THE EVENT THAT THE ENGINEER OF RECORD ELECTS TO
 SPECIFY SPECIFIC EQUIPMENT AND TO SHOW THE REQUIRED
 WIRING, BATTERY AND VOLTAGE DROP (CIRCUIT ANALYSIS)
 CALCULATIONS SHALL BE COMPLETED. THE CALCULATIONS SHALL
 BE COMPLETED USING THE EQUIPMENT MANUFACTURE???S DATA
 AND APPLICABLE NFPA 72 PROCEDURES.
 (6) SYSTEM TEST REQUIREMENTS SHALL BE NOTED ON THE
 ENGINEERING DESIGN DOCUMENTS.
 (7) WHEN THE ENGINEER DETERMINES THAT SPECIAL
 REQUIREMENTS ARE REQUIRED BY THE OWNER, INSURANCE
 UNDERWRITER OR LOCAL FIRE CODE AMENDMENTS THESE
 REQUIREMENTS SHALL BE DOCUMENTED OR REFERENCED ON THE
 ENGINEERING DESIGN DOCUMENTS.
  
 EVEN IF THE EOR DEFERS TO A LOCAL QUALIFIED CONTRACTOR,
 THAT CONTRACTOR MUST SUBMIT THE REQUIRED 61G
 INFORMATION WITH THIS MASTER.
  
 PLEASE PROVIDE THE REQUIRED DOCUMENTATION.
  
  
 3) THERE IS NO INDICATION OF SMOKE CONTROL AND THE
 SEQUENCE OF OPERATION
  
 PER NFPA 101
  
 30.4 SPECIAL PROVISIONS
 30.4.1 HIGH-RISE BUILDINGS.
 30.4.1.1 HIGH-RISE BUILDINGS SHALL COMPLY WITH SECTION
 11.8. THE PROVISIONS
 OF 30.3.5.3 AND 30.3.4.5 SHALL BE PERMITTED.
  
 11.8.2.3 ALL NEW VERTICAL EXIT ENCLOSURES SERVING THE
 HIGH-RISE PORTION
 OF THE BUILDING SHALL BE SMOKEPROOF ENCLOSURES IN
 ACCORDANCE WITH 7.2.3
  
 PLEASE PROVIDE THE SMOKE CONTROL AND SEQUENCE OF
 OPERATION PLAN
  
 4) THERE IS AN INDICATION OF AN ELECTRIC FIRE PUMP,
 HOWEVER, THERE IS NO INDICATION OF THE FIRE PUMP
 EMERGENCY BACK UP POWER NOR ITS FUEL SUPPLY
  
  
 PER NFPA 101 CH 11
  
 11.8.5 EMERGENCY AND STANDBY POWER.
 11.8.5.1 EMERGENCY POWER REQUIREMENTS FOR ELECTRIC FIRE
 PUMPS SHALL
 BE IN ACCORDANCE WITH NFPA 20.
 11.8.5.2 EMERGENCY POWER REQUIREMENTS FOR DETECTION,
 ALARM, AND COMMUNICATIONS
 SYSTEMS SHALL BE IN ACCORDANCE WITH NFPA 72.
 11.8.5.3 REQUIREMENTS FOR STANDBY POWER SHALL BE AS
 SPECIFIED IN
 11.8.5.3.1 THROUGH 11.8.5.3.
 11.8.5.3.1 TYPE 60, CLASS 1, LEVEL 1, STANDBY POWER IN
 ACCORDANCE WITH
 NFPA 110 SHALL BE PROVIDED.
 11.8.5.3.2 THE STANDBY POWER SYSTEM SHALL HAVE A
 CAPACITY AND RATING
 SUFFICIENT TO SUPPLY ALL REQUIRED EQUIPMENT.
 11.8.5.3.3 SELECTIVE LOAD PICKUP AND LOAD SHEDDING
 SHALL BE PERMITTED
 IN ACCORDANCE WITH NFPA 70.
 11.8.5.3.4 THE STANDBY POWER SYSTEM SHALL BE CONNECTED
 TO THE
 FOLLOWING:
 (1) JOCKEY PUMP, EXCEPT AS OTHERWISE PROVIDED IN 40.4.2
 FOR SPECIALPURPOSE
 INDUSTRIAL OCCUPANCIES
 (2) AIR COMPRESSOR SERVING DRY-PIPE AND PRE-ACTION
 SYSTEMS, EXCEPT
 AS OTHERWISE PROVIDED IN 40.4.2 FOR SPECIAL-PURPOSE
 INDUSTRIAL
 OCCUPANCIES
 (3) EMERGENCY COMMAND CENTER EQUIPMENT AND LIGHTING
 (4) NOT LESS THAN ONE ELEVATOR SERVING ALL FLOORS, WITH
 STANDBY POWER
 TRANSFERABLE TO ANY ELEVATOR
 (5) MECHANICAL EQUIPMENT FOR SMOKEPROOF ENCLOSURES
 (6) MECHANICAL EQUIPMENT REQUIRED TO CONFORM WITH THE
 REQUIREMENTS
 OF SECTION 9.3
 (7) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 PER NFPA
  
 NFPA 101 CHAPTER 7 SECTION 7.9
  
 7.9.1 FUEL TANKS SHALL BE SIZED TO ACCOMMODATE THE
 SPECIFIC
  
 EPS CLASS.
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
  
  
 PLEASE PROVIDE DETAILS AND CONFIRMATION OF THE
 REQUIREMENTS.
  
  
  
  
 4) THE ADDRESSING ON THE PLANS AND ON THE APPLICATION
 DO NOT MATCH. APPLICATION LISTS 4708 N FLAGLER AS THE
 PROJECT ADDRESS AND THE PLANS INDICATE THE ADDRESS
 BEING 4714 N FLAGLER.
  
 PLEASE REVIEW AND FOR THE OFFICIAL RECORD, CORRECT AS
 APPLICABLE
  
  
  
 5) THERE IS AN INDICATION OF A EMERGENCY COMMAND
 CENTER.
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
  
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
 (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE.
 (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY
 COMMAND CENTER.
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION
 OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 NFPA 101
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 PLEASE ENSURE COMPLIANCE WITH THE REQUIREMENTS.
  
  
  
 6) THERE ARE NO INDICATIONS OF COMPLIANCE WITH THE
 REQUIRMENTS OF EMERGENCY RADIO COMMUNICATIONS
  
 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT SYSTEMS.
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
 24.9.1 GENERAL.
 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM
 CAPABLE
 OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON
 FREQUENCIES
 ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE
 INSTALLED
 WITHOUT PRIOR COORDINATION AND APPROVAL OF THE
 AUTHORITY
 HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL
 SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT
 DEGRADE
 THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM.
 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED
 FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH
 FIRE DEPARTMENT.
  
 TESTING SHALL BE BY AN ACCEPTABLE NATIONAL STANDARD
 DOCUMENTING PERCENTAGES NOTED ABOVE AND BY ACTUAL RADIO
 TESTING BY FIRE PERSONNEL.
  
 IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL
 AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM
 2-HOUR RUN TIME BATTERY BACK-UP.
  
 CONTACT SHALL BE MADE TO KEN DECKER, PALM BEACH COUNTY
 PUBLIC SAFETY RADIO SYSTEMS MANAGER,
 [email protected], 561-233-0837; AS OUR RADIOS OPERATE
 ON THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND
 INSTALLATION INSTRUCTIONS.
  
 NO PERMIT SHALL BE SUBMITTED OR BDA SYSTEM INSTALLED
 UNTIL ALL DOCUMENTATION IS REVIEWED BY PBC & THE OFFICE
 OF THE FIRE MARSHAL AND SUBSEQUENTLY APPROVED FOR
 INSTALL OR PARTIAL INSTALL.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By ccole Date 2023-07-14 Time 17:38 Rev Time 0.00
Received By ccole Date 2023-07-14 Time 17:38 Sent To  
Notes
2023-07-14 17:39:141ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23060501
 7/14/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3.13.0 GAS RISER: BASED ON THE GAS PIPE
 SIZING TABLE SPECIFIED ON THE PLAN- (402.4(3) FBC FG)-
 THE 1-1/4-INCH SCHEDULE 40 PIPING IS UNDERSIZED TO
 SUPPLY THE TOTAL 1,200,000 BTU LOAD AT A TOTAL
 DEVELOPED LENGTH OF 410 FT. BASED ON THE TABLE THE
 MINIMUM PIPE SIZE FOR THE LOAD IS 2-INCH. PLEASE NOTE
 AN 1-1/4 PIPE IS ADEQUATE FOR A 2 PSI SYSTEM SIZED
 ACCORDING TO TABLE 402.4(5) FBC FG.
  
 2) P3.13.0 GAS RISER: PROVIDE AND ENLARGED GAS TRAIN
 DETAIL FOR THE WATER HEATERS SHOWING THE INPUT
 PRESSURES OF THE WATER HEATERS, LOCATIONS OF SHUT OFF
 VALVES, REGULATORS, PIPE UNIONS, AND TEST TEES- SEC.
 409.1 & 410.2 FBC FG.
  
 A) PROVIDE THE MAKE AND MODEL OF THE SELECTED REGULATOR
 ON THE DRAWING AND PROVIDE VENTING DETAILS INCLUDING
 VENT PIPING RUNS AND TERMINATION LOCATIONS- SEC. 410.2
 & 410.3 FBC FG
  
 3) P3.13.0, A2.01, & M2.01: PLEASE SHOW THE CLEARANCE
 DISTANCES FROM THE WATER HEATER EXHAUST OUTLET TO THE
 COMBUSTION AIR INTAKE AND OTHER GRAVITY OR MECHANICAL
 AIR INTAKES INTO THE BUILDING- SEC. & TABLE 503.8 FBC
 FG, AND SEC. 401.4 FBC M.
  
 4) P3.13.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE WATER HEATERS AND INSTALLATION GUIDELINES FOR THE
 COMBUSTION AIR AND VENT DUCTS- SEC. 624.1 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-06-14 Time 12:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-07-22 Cont ID  
Sent By hmoser Date 2023-07-22 Time 11:35 Rev Time 0.00
Received By hmoser Date 2023-07-20 Time 13:01 Sent To  
Notes
2023-07-22 11:35:07PLAN DENIED
 1) PAGE SP.0.1 UNDERGROUND FUEL TANKS AND FUEL PIPING
 REQUIRE SEPRATE APPLICATION, PLAN AND PERMIT. SECTION
 1301
 FUEL PIPING AND STORAGE. 2020 FBC (M)
 2) PROVIDE THE DUCT SIZE IN RATED SHAFT FOR SMOKE
 EXHAUST
 OUT SIDE AIR AND ELEAATOR1, 2, 3, AND 4 SECTION 107 FBC
 3) PAGE M3.10.2 PROVIDE DUCT SIZE FOR DININGROOM ON
 PLAN
 SECTION 107
 4) PROVIDE CLOTHES DRYER SPECIFICSTIONS FOR THE
 APARTMENTS
 SECTION 504 CLOTHES DRYER EXHAUST. 2020 FBC (M)
 5) SHOW ON THE PLAN WHERE THE AIR CONDITIONING
 CONDENSERS
 ARE LOCATED FROM 1ST FLOOR TO 6TH FLOOR. SECTION 107
 FBC
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By ccole Date 2023-07-14 Time 17:40 Rev Time 0.00
Received By ccole Date 2023-07-11 Time 08:21 Sent To  
Notes
2023-07-14 17:41:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060501
 7/14/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. GENERAL/ADMINISTRATIVE COMMENTS.
  
 1) THE ENERGYGAUGE REPORT DOES NOT PROVIDE COMPLIANCE
 DATA FOR THE WATER HEATING AND PIPING SYSTEMS- SEC.
 C404.1 FBC EC.
  
 2) SEPARATE PERMITS REQUIRED INCLUDE THE POTABLE WATER
 BACKFLOW PREVENTER, GROUND FLOOR SOLIDS INTERCEPTORS
 AND OIL SEPARATOR, AND 6TH FLOOR GREASE INTERCEPTOR-
 SEC. 105.1 & 107.2.1 WPB. PLEASE NOTE THE SUBMITTED
 PLUMBING PLANS FOR THE BUILDING WILL NOT BE APPROVED
 UNTIL PERMIT APPLICATIONS FOR THE ITEMS LISTED ABOVE
 HAVE BEEN SUBMITTED. YOU CAN SUBMIT APPLICATIONS TBD
 (TO BE DETERMINED) IF YOU DO NOT HAVE CONTRACTORS
 SELECTED BY EMAILING COMPLETED PERMIT APPLICATIONS TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATIONS ARE
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE ALL
 OF THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE PUBLIC AND
 PRIVATE POOLS AND SPAS HOWEVER THE PLUMBING FLOOR PLANS
 AND RISERS SHOW POOL WASTEWATER DRAINING INTO THE
 SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126
 (B)(5) WPB CODE OF ORDINANCES. PLEASE NOTE THE
 FOLLOWING INFORMATION.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 - THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 - DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 4) SEPARATE PERMITS ARE REQUIRED FOR THE IRRIGATION
 SYSTEM AND SYSTEM BACKFLOW PREVENTER. CURRENTLY NO
 PLANS HAVE BEEN SUBMITTED FOR REVIEW. PLANS SHALL BE
 SUBMITTED UNDER THE SEPARATE PERMITS- SEC. 107.2.1 WPB.
  
 2. ARCHITECTURAL COMMENTS.
  
 5) 4) SHEETS ALS.0.0, ALS.0.2 & ALS.0.3: PLEASE REFER
 TO SEC. 233 FBC ACCESSIBILITY. BASED ON SECS 233.3.1 &
 233.3.1.1 AT LEAST 5% OF THE TOTAL NUMBER OF
 RESIDENTIAL DWELLING UNITS SHALL BE PROVIDED WITH
 MOBILITY FEATURES COMPLYING WITH SECS. 809.2- 809.4 AND
 SHALL BE ON AN ACCESSIBLE ROUTE; AND AT LEAST 2% SHALL
 BE PROVIDED WITH COMMUNICATION FEATURES COMPLYING WITH
 809.4. THESE REQUIREMENTS ARE SEPARATE FROM COMPLIANCE
 WITH THE FAIR HOUSING DESIGN ACT REQUIREMENTS. REFER TO
 SEC. 233.3.5 DISPERSION AND PROVIDE A LIST OR SCHEDULE
 ON THE PLAN SHOWING THE LOCATIONS OF THE UNITS, AND
 REVISE THE ARCHITECTURAL AND PLUMBING PLANS WHERE
 REQUIRED.
  
 A) ALS.02 & ALS.0.3: THE PLANS INDICATE THE R2 CONDO
 UNITS ARE DESIGNED IN ACCORDANCE WITH THE FAIR HOUSING
 DESIGN ACT MANUAL (1998). TO HELP EXPEDITE THE REVIEW
 AND INSPECTION OF THE CONDO BATHROOMS PLEASE REFER TO
 PAGES 7.34 & 7.35 OF THE FHDA AND INDICATE WHICH DESIGN
 SPECIFICATION HAS BEEN CHOSEN- SPECIFICATION A OR B.
 PLEASE PROVIDE THE SPECIFICATION TYPE ON ALS.02,
 ALS.04, AND ON THE ENLARGED A, B, C & D UNIT PLANS-
 SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1.
  
 B) ALS.0.0, ALS.0.2 & ALS.0.3: AS NOTED THERE ARE
 DESIGN DIFFERENCES BETWEEN AN FBC ACCESSIBLE (ADA
 COMPLIANT) DWELLING UNITS AND A FHDA COMPLIANT UNITS.
 PLEASE REFER TO SEC. 809.4 FBC ACCESSIBILITY AND
 PROVIDE SEPARATE ENLARGED ACCESSIBLE UNIT DRAWINGS WITH
 THE FOLLOWING COMPLIANCE DETAILS PER SEC. 603- 610 FBC
 ACCESSIBILITY. PLEASE NOTE MANY OF THESE SECTIONS HAVE
 EXCEPTIONS WHICH ALLOW FOR JUST GRAB BAR BACKING TO BE
 INSTALLED INSTEAD OF COMPLETE GRAB BARS.
  
 1. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
  
 2. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
  
 3. TURNING SPACE DIAMETERS- SEC. 304.3.
  
 4. CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
  
 5. HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 6. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
  
 7. HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3.
  
 8. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2.
  
 9. CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
  
 10. KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 11. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 BATHTUBS- SEC. 607.2.
  
 12. BATHTUB PERMANENT OR REMOVAL SEAT DETAILS- SEC.
 607.3.
  
 13. BATHTUB GRAB BAR DETAILS- SEC. 607.4.
  
 14. BATHTUB CONTROLS DETAILS- SECS. 607.5- 607.6.
  
 15. CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 SHOWER- SECS. 608.2.1 & 608.2.2.
  
 16. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3.1 AND
 608.3.2.
  
 17. LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS
 IN THE SHOWERS- SECS. 608.5.1 & 608.5.2.
  
 18. LOCATIONS OF ACCESSIBLE SHOWER SEATS AND MOUNTING
 DETAILS-
  
 6) ALS.02, ALS.0.3: PROVIDE GRAB BAR BACKING DETAILS
 FOR THE CONDO SHOWERS IN COMPLIANCE WITH PAGES 6.12 &
 6.13 FDHA MANUAL.
  
 7) SHEETS A-9.10.1, A-9.11.1, A-9.12.1 & A-9.13.1,
 A-9.14.1, A-9-15.1, A-9.16.1,A-17.1, A-18.1: PLEASE
 PROVIDE FHDA COMPLIANCE DETAILS ON THE FLOOR PLANS OR
 PROVIDE NOTES REFERENCING SHEETS ALS.02 & ALS.03 FOR
 DETAIL LOCATIONS.
  
 8) ALS.1.1 PLUMBING FIXTURE COUNT TABLE: REQUIRED AND
 PROVIDED COUNTS CANNOT BE UNISEX BECAUSE SEPARATE
 FACILITIES ARE REQUIRED FOR MALE AND FEMALE USE UNLESS
 ONLY ONE WATER CLOSET FOR EACH IS REQUIRED- SECS. 403.2
 & 403.2.1 FBC P. PLEASE LABEL THE BATHROOMS ON ALL 1ST
 FLOOR PLANS AS EITHER MALE OR FEMALE.
  
 9) P1.6.2A: SHOW THE WEST POOL OUTDOOR SHOWER LOCATION-
 SEC. 454.1.6.2 FBC B.
  
 10) A9.1.1A: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS AT THE ACCESSIBLE EMPLOYEE LOUNGE SINK
 AND WHEEL CHAIR ACCESSIBLE DRINKING FOUNTAIN- SECS.
 602.2 & 606.2 FBC ACC. A) PLEASE PROVIDE AN ELEVATION
 DETAIL FOR THE DRINKING FOUNTAINS SHOWING THE KNEE AND
 TOE CLEARANCES AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC
 ACC.
  
 11) A9.1.6: SHOW THE HEIGHTS OF THE WATER CLOSET SEATS
 MEASURED FROM THE FINISHED FLOORS- SEC. 604.4 FBC ACC.
  
 12) A9.1.6: SHOW THE KNEE AND TOE CLEARANCES FOR THE
 LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3 FBC ACC.
  
 13) A9.7.5: PROVIDE AN ELEVATION DETAIL FOR THE
 DRINKING FOUNTAINS SHOWING THE KNEE AND TOE CLEARANCES
 AND SPOUT HEIGHTS- SECS 602.2- 602.7 FBC ACC.
  
 14) A9.7.6, A9.7.7, & A9.7.8: MISSING FBC ACC DETAILS:
  
 A) HEIGHTS OF THE ACCESSIBLE WATER CLOSET SEATS
 MEASURED FROM THE FINISHED FLOORS- SEC. 604.4.
  
 B) KNEE AND TOE CLEARANCES FOR THE ACCESSIBLE
 LAVATORIES- SECS. 606.2, FIG. 306.2 & 306.3.
  
 C) ACCESSIBLE URINAL RIM HEIGHT FROM THE FINISHED
 FLOOR- SEC. 605.2.
  
 15) A9.7.1B, A9.7.10: THE MEN'S AND WOMEN'S SHOWERS
 SHALL BE ACCESSIBLE AS REQUIRED BY SEC. 213.3.6 FBC
 ACC. PROVIDE THE FOLLOWING DETAILS FBC ACC.
  
 A) GRAB BAR LOCATIONS, LENGTHS AND MOUNTING HEIGHTS-
 SEC. 608.3.3. PLEASE NOTE THE SEATS WILL HAVE TO BE
 RELOCATED TO ALLOW INSTALLATION OF THE SIDE WALL GRAB
 BARS.
  
 B) THE CONTROLS, FAUCETS, AND SHOWER SPRAY SHALL BE
 RELOCATED TO THE SIDE WALL ADJACENT TO THE RELOCATED
 SEAT AT A POINT 27 INCHES MAXIMUM FROM THE SIDE WALL
 BEHIND THE SEAT OR SHALL BE LOCATED ON THE BACK WALL
 OPPOSITE THE SEAT 15 INCHES MAXIMUM, LEFT OR RIGHT, OF
 THE CENTERLINE OF THE SEAT.
  
 C) SHOW THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN
 48 INCHES ABOVE THE SHOWER FLOOR.
  
 3. PLUMBING COMMENTS
  
 16) P1.0.0, P1.1.1A, P1.1.1B, P1.1.1C- FLOOD HAZARD:
 FLOOD MAPS INDICATE PORTIONS OF THE BUILDING MAY BE
 CONSTRUCTED IN AN AE FLOOD HAZARD ZONE. PLEASE NOTE THE
 FOLLOWING.
  
 A) REFER TO SEC. 309.2 FBC P FLOOD HAZARD AND SEC. 7.3
 ASCE 24-14: THE PLUMBING SYSTEMS, EQUIPMENT, FIXTURES
 AND OTHER COMPONENTS SYSTEM SHALL BE INSTALLED ABOVE
 THE DESIGN FLOOD ELEVATION HEIGHT, OR MEET THE
 EXCEPTION UNDER 309.2.
  
 B) UNDERGROUND PIPING AND PLUMBING SYSTEMS SHALL BE
 BURIED TO A DEPTH SUFFICIENT TO PREVENT MOVEMENT,
 SEPARATION, OR LOSS DUE TO FLOODING AND EROSION UNDER
 DESIGN FLOOD CONDITIONS- 7.3.1 ASCE 24-14.
  
 C) OPENINGS IN THE PLUMBING SYSTEMS BELOW THE DESIGN
 FLOOD ELEVATION HEIGHT SHALL BE PROTECTED WITH
 AUTOMATIC BACKWATER VALVES. SHOW COMPLIANCE WHERE
 REQUIRED WITH NOTES AND DETAILS ON THE PLANS- SEC.
 714.1 FBC P.
  
 17) P1.0.0: PROVIDE CIVIL PLANS SHOWING WATER, FIRE AND
 GAS SERVICE PIPING CONTINUATIONS AND CONNECTIONS TO
 MAINS, AND SANITARY AND STORM DRAIN CONTINUATIONS AND
 CONNECTIONS- SEC. 107.2.1 WPB.
  
 18) P1.1.1A, P1.1.1B, P1.1.1C: TO HELP EXPEDITE THE
 REVIEW PLEASE SHOW THE DFU TOTALS AT THE SANITARY
 RISERS, BRANCHES, AND MAIN BUILDING DRAINS- TABLES
 710.1(1) & 710.1(2) FBC P.
  
 A) SHOW THE GPM TOTALS AT STORM RISERS, BRANCHES, AND
 MAIN DRAINS- TABLES 1106.2, 1106.3 FBC P.
  
 B) TO HELP EXPEDITE THE REVIEW PLEASE LABEL SANITARY
 PIPING (S) AND STORM PIPING (ST)- SEC. 107.2.1 WPB.
  
 19) P1.1.1B, P1.1.1C, P4.1.1: PROVIDE EQUIPMENT
 SCHEDULES AND SIZING CALCULATIONS FOR THE SOLIDS
 INTERCEPTORS, THE OIL SEPARATOR, AND THE LINT TRAP-
 SECS. 1003.1, 1003,4,2, & 1003.6 FBC P.
  
 A) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR EACH WITH
 ENGINEER'S APPROVAL STAMP- SEC. 107.3.4 WPB.
  
 20) P1.1.C & P4.1.1: IT APPEARS THE SOLIDS INTERCEPTOR
 IN THE TRASH ROOM IS NOT VENTED- SEC. 1003.9 FBC P.
  
 21) P1.1.2A, P4.2.1: PLEASE PROVIDE WATER DISTRIBUTION
 DESIGN CRITERIA- SEC. 604.3 FBC P.
  
 22) P4.2.1: COMPLETE WATER RISER DRAWINGS FROM THE
 GROUND FLOOR THROUGH THE FLOOR INTERVALS TO THE ROOF
 HAVE NOT BEEN PROVIDED. PLEASE PROVIDE THE RISERS- SEC.
 107.3.5.1.3 WPB. TO HELP EXPEDITE THE REVIEW PLEASE
 NUMBER THE INDIVIDUAL RISERS AND PROVIDE MATCHING
 NUMBERS AT THE RISER LOCATIONS SHOWN ON THE GROUND
 FLOOR ISOMETRIC DRAWINGS.
  
 A) THE WATER RISER DRAWINGS SHALL SHOW PIPE SIZES FROM
 FLOOR-TO-FLOOR INTERVALS, PIPE SIZES AT UNIT ENTRANCES,
 AND LOCATIONS OF SHUTOFF VALVES AND PRV'S WHERE
 REQUIRED- SECS 604.4, 604.7 & 606.1 FBC P.
  
 23) P4.1.1: COMPLETE CONVENTIONAL SANITARY
 DRAINAGE/VENT RISER DRAWINGS FROM THE GROUND FLOOR
 THROUGH THE FLOOR INTERVALS TO THE ROOF HAVE NOT BEEN
 PROVIDED. PLEASE PROVIDE THE RISERS- SEC. 107.3.5.1.3
 WPB. TO HELP EXPEDITE THE REVIEW PLEASE NUMBER THE
 INDIVIDUAL RISERS AND PROVIDE MATCHING NUMBERS AT THE
 RISER LOCATIONS SHOWN ON THE GROUND FLOOR ISOMETRIC
 DRAWINGS.
  
 B) THE CONVENTIONAL SANITARY RISERS SHALL SHOW SOIL,
 WASTE, AND VENT STACK SIZES FROM FLOOR-TO-FLOOR,
 LOCATIONS AND SIZES OF OFFSETS AND RELIEF VENTS WHERE
 REQUIRED, VENT TO ROOF LOCATIONS, CLEANOUT LOCATIONS,
 AND DFU CALCULATIONS- SECS. 710.1, 904.1, 904.2, 904.4,
 904.5, 906.1, 907.1, & 908.1 FBC P.
  
 24) P4.1.1 & P.503: CONCERNING THE TUFF-RITE SOVENT
 SYSTEM PLEASE REFER TO SEC. 316 FBC P. THE SYSTEM IS
 DEFINED AS AN ALTERNATIVE ENGINEERED DESIGN WHICH
 REQUIRES THE ENGINEER OF RECORD TO SUBMIT TECHNICAL
 DATA TO SUBSTANTIATE THE PROPOSED ALTERNATIVE DESIGN
 AND TO PROVE THE PERFORMANCE MEETS THE INTENT OF THE
 CODE- SEC. 316.1.3. PLEASE PROVIDE THE FOLLOWING ITEMS
  
 A) ENGINEER'S LETTER TO THE BUILDING OFFICIAL WITH
 SUFFICIENT EVIDENCE TO REQUEST APPROVAL OF THE
 ALTERNATIVE SYSTEM.
  
 B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS WITH ENGINEER'S APPROVAL STAMP.
  
 C) SEPARATE SITE-SPECIFIC FLOOR PLANS AND COMPLETE
 RISER DRAWINGS. THE CURRENT PLANS SUBMITTED CAN BE
 SEPARATED, MODIFIED, LABELED PROPERLY AND PROVIDED WITH
 ADDITIONAL SITE-SPECIFIC INFORMATION SUCH AS PIPE
 SLOPES AND HORIZONTAL PIPE LENGTHS ETC.- SEC. 316.1.4.
 PLEASE NOTE WHERE REQUIRED THE RISERS SHALL BE
 CONTINUOUS FROM GROUND FLOOR TO ROOF.
  
 25) P.4.1.1: SHOW REQUIRED TRAPS FOR THE DW 1 DRAINS-
 SEC. 1002.1 FBC P.
  
 26) P1.1.2A, P1.1.2B, P4.2.1: COLD OR TEMPERED WATER
 SHALL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P.
  
 27) P1.1.2A, P1.1.2B, P4.2.1: THE 1/2-INCH HOT WATER
 FIXTURE SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING
 THE MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT
 WATER SOURCES- TABLE C404.5.1 FBC ENERGY.
  
 28) P4.2.1: SHOW FULL-OPEN SHUT OFF VALVES AT BASE OF
 THE WATER RISERS- SEC. 606.1 (4) FBC P.
  
 29) P1.2.1A, P1.3.1A, P1.4A: THE DRAWINGS APPEAR TO
 SHOW AREA DRAINS (AD) ON THE WEST SIDE DRAINING INTO
 THE SANITARY WHICH IS PROHIBITED PER SEC. 90-126 (B)
 WPB CODE OF ORDINANCES.
  
 30) P1.5.2C NOTE 6: A BACKFLOW PREVENTER IS REQUIRED
 FOR THE MAKEUP WATER LINE TO THE POOL EQUIPMENT- SEC.
 608.3 FBC P.
  
 31) P1.6.1A: THE PLAN APPEARS TO SHOW A SANITARY DRAIN
 LINE PENETRATING THE INTERIOR EXIST STAIRWAY 2 WHICH IS
 PROHIBITED PER SEC. 1023.5 FBC B.
  
 32) P1.6.1B KITCHEN GREASE INTERCEPTOR: PLEASE PROVIDE
 THE FOLLOWING ITEMS PER SEC. 1003.3.5 FBC P.
  
 A) EQUIPMENT SCHEDULE- MAKE AND MODEL, GALLON SIZE.
  
 B) SIZING CALCULATIONS.
  
 C) ENLARGED PIPING DIAGRAM SHOWING DRAIN PIPE SIZES AND
 RUNS FROM FIXTURES, OUTLET AND VENT PIPING SIZES AND
 RUNS.
  
 D) PLEASE NOTE DISCHARGES FROM HAND SINKS, ICE MAKER
 AND ICE BINS SHALL NOT DRAIN INTO THE INTERCEPTOR- SEC.
 1003.3.1 FBC P.
  
 E) P4.1.2: SHOW THE INTERCEPTOR LOCATION ON THE RISER-
 SEC. 107.2.1 WPB.
  
 33) P1.6.1B, P1.6.2B: PLEASE PROVIDE A PLUMBING
 APPLIANCE AND FIXTURE EQUIPMENT SCHEDULE AND
 CORRELATING PLAN FOR THE KITCHEN- SEC. 107.2.1 WPB.
  
 34) P1.6.2A, P1.6.2B: PROVIDE BACKFLOW PREVENTERS FOR
 WATER SUPPLY LINES TO POOL EQUIPMENT AND STEAM
 GENERATORS- SEC. 608.3 FBC P.
  
 35) P1.6.2A, P1.6.2B: COLD OR TEMPERED WATER SHALL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5.
  
 36) P1.6.2A, P1.6.2B: THE 1/2-INCH HOT WATER FIXTURE
 SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THE
 MAXIMUM ALLOWABLE 2 FT. DISTANCES FROM THE HOT WATER
 SOURCES- TABLE C404.5.1 FBC ENERGY.
  
 37) P2.0.1, A2.0.1, A8.4.1: THE OVERFLOW SCUPPERS SIZES
 ARE NOT SHOWN AND THE SCUPPER LOCATIONS ON THE PLANS
 DON'T MATCH- SEC. 1108.3 FBC P.
  
 38) P4.01 & P4.02: THE STORM RISERS DO NOT SHOW THE GPM
 FLOWS FROM THE AD'S, PD'S, AND CND'S, AND ALSO THE
 ACCUMULATIVE TOTALS BRANCH CONNECTIONS AND MAIN
 OUTFLOWS- SEC. 1106.2 FBC P.
  
 39) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1,
 P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3,
 P3.12.4: SHOW WATER SHUTOFF LOCATIONS AT UNIT
 ENTRANCES- SEC. 606.1 (6) FBC P.
  
 40) P3.1.2, P3.2.2, P3.4.2, P3.5.2, P3.6.1, P3.7.1,
 P3.8.2, P3.9.2, P3.10.3, P3.11.3, P3.11.4, P3.12.3,
 P3.12.4: IT APPEARS THE DEVELOPED LENGTH OF THE HOT
 WATER TO SOME OF THE UNIT PLUMBING FIXTURES MAY EXCEED
 50 FT. FROM THE HOT WATER SOURCES- SEC. 607.2 FBC P.
 PLEASE REVIEW AND CORRECT OIF NECESSARY.
  
 41) P3.13.0: A MEANS OF DILUTING OR NEUTRALIZING THE
 CONDENSATE WASTE FROM THE GAS-FIRED WATER HEATERS IS
 REQUIRED- SEC. 803.1 FBC P.
  
 42) P0.0.1 & P5.0.1: PROVIDE PIPING SPECIFICATIONS FOR
 WATER, SANITARY, GREASE, OIL, VENT, GAS AND COMPLETE
 FIRESTOPPING DETAILS FOR WALL AND FLOOR PENETRATIONS-
 SECS. 315.1 605.4, 702.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-16 Cont ID  
Sent By lbond Date 2023-06-16 Time 11:08 Rev Time 0.00
Received By lbond Date 2023-06-16 Time 11:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-08-16 Cont ID  
Sent By jswaby Date 2023-08-16 Time 15:16 Rev Time 0.00
Received By jlswaby Date 2023-08-16 Time 15:16 Sent To  
Notes
2023-07-08 11:28:27APPROVAL FOR FOUNDATION ONLY.
  
  
  
 JERMAINE SWABY
 SENIOR PLANNER
 561-822-1431
 [email protected]
  