Plan Review Details - Permit 23060360
Plan Review Stops For Permit 23060360
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-06-20 Cont ID  
Sent By cpuell Date 2023-06-20 Time 09:24 Rev Time 0.00
Received By cpuell Date 2023-06-20 Time 09:24 Sent To  
Notes
2023-06-20 09:24:32ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By rmcphers Date 2023-06-29 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2023-06-29 Time 15:29 Sent To  
Notes
2023-06-29 15:30:23PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-29 Cont ID  
Sent By rmcphers Date 2023-06-29 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2023-06-29 Time 15:30 Sent To  
Notes
2023-06-29 15:30:49REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE AN EXISTING FLOOR PLAN. FBC WPB 107.2
  
 2) PLEASE WRITE THE SCOPE OF WORK ON THE DRAWINGS - FBC
 WPB 107.2
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jleahy Date 2023-06-28 Time 07:30 Rev Time 0.00
Received By jleahy Date 2023-06-26 Time 13:27 Sent To  
Notes
2023-06-28 07:35:08FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN E-1 CALLS FOR NEW MAIN SWITCH GEAR AND SUBFEEDERS
 IS THIS CORRECT? IS THERE A PERMIT FOR THAT ?
  
 PLAN ON E-1 DOES NOT MATCH PLANS ON PAGES ID-101.1 AND
 ID-102.1 DIFFERENT LAYOUT OF KITCHEN.
  
 PLEASE IDENTIFY WHAT IS BEING DONE IN THE UNIT ON THE
 PLAN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By pleduc Date 2023-06-21 Time   Rev Time 0.00
Received By pleduc Date 2023-06-21 Time 13:31 Sent To  
Notes
2023-06-21 13:31:58THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE SUBMITTED PLANS; HOWEVER, THERE ARE NO
 DETAILS ON THESE PALNS TO REVIEW FOR LIFE SAFETY CODE
 COMPLIANCE.
  
 THERE IS NO SCOPE OF WORK NOR ANY DETAILED PLAN SHEETS
 ON WHAT IS EXISTING OR WHAT IS NEW.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE REVIEW AND PROVIDE THE REQUIRED PLAN SHEETS AND
 DETAILS TO CONDUCT A THOROUGH LIFE SAFETY REVIEW OF THE
 PROPOSED WORK.
  
  
 1A.) PLAN SHEETS ID-101, ID-102, ID-103, ID-104. & 105
 ARE MISSING.
  
 PLEASE REVIEW AND SUBMIT OR CORRECT THE COVER SHEET
 LIST.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-05 Cont ID  
Sent By cmontell Date 2023-07-05 Time 13:28 Rev Time 0.00
Received By cmontell Date 2023-07-05 Time 13:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-07-05 Cont ID  
Sent By cmontell Date 2023-07-05 Time 13:28 Rev Time 0.00
Received By cmontell Date 2023-07-05 Time 13:27 Sent To  
Notes
2023-07-05 13:28:05MECHANICAL PLAN NEEDS SUPPLY DUCT SIZES FBC 107
  
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-22 Cont ID  
Sent By rwbrown Date 2023-06-22 Time 14:00 Rev Time 0.00
Received By rwbrown Date 2023-06-22 Time 14:00 Sent To  
Notes
2023-06-22 14:01:011ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 406.2 - THE SANITARY ISOMETRIC SHOWS AN 1
 1/2" STANDPIPE TO THE WASHING MACHINE. A 2" IS
 REQUIRED.
  
 2. WPB ORD. SEC. 90 - 126 - PLEASE SHOW A DETAIL THAT
 INCLUDE THE DISCHARGE LOCATION OF THE AC CONDENSATE
 DRAIN TO VERIFY IT DOES NOT GO INTO THE SANITARY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-28 Cont ID  
Sent By jleahy Date 2023-06-28 Time 07:49 Rev Time 0.00
Received By jleahy Date 2023-06-28 Time 07:49 Sent To  
Notes
2023-06-28 07:51:56FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN E-1 SIGNATURE IS NOT DIGITALLY VERIFIABLE WPB
 107.2.1