Plan Review Details - Permit 23060307
Plan Review Stops For Permit 23060307
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By rmcdouga Date 2023-07-14 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2023-07-14 Time 14:18 Sent To  
Notes
2023-07-14 14:19:41PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ???ASBESTOS???
 IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By rmcdouga Date 2023-07-14 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2023-07-14 Time 14:18 Sent To  
Notes
2023-07-14 15:48:29PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT PRODUCT FOR EXTERIOR STOREFRONTS AND DOORS.
 FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL MULLIONS
 AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF
 REQUESTED AND LISTED ON THE PLANS, HOWEVER, THE
 DOCUMENTS MUST BE SUBMITTED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THEY CAN BE INSTALLED. ONLY
 ONE SET IS REQUIRED TO BE UPLOADED FOR ELECTRONICALLY
 SUBMITTED DOCUMENTS.
  
 2) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE
 REVIEW COMMENTS HAVE BEEN ADDRESSED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-07 Cont ID  
Sent By jleahy Date 2023-07-07 Time 13:15 Rev Time 0.00
Received By jleahy Date 2023-07-07 Time 07:56 Sent To  
Notes
2023-07-07 15:20:29FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 OUTLETS IN THE KITCHEN AND WITHIN 6" OF THE SINKS TO BE
 GFCI PROTECTED
  
 POS 5,11
 PANEL A-4,39,2,33,31,29,27,23,25
 PANEL B-37,6,4,17,28,16,26
 PANEL C-17
 PANEL D-2,37,31,25,36,19,13,7,1
 PANEL E-19,8,2,10,31,32,46
 PANEL F-26, 24,22,27,29,14
 PANEL G-6,10,12,14,8,41,2,37,5,13,3,9,23,6,35,14,41
  
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL SHALL BE PROVIDED AS REQUIRED IN 210.8(A)
 THROUGH (E). THE GROUND-FAULT CIRCUIT INTERRUPTER SHALL
 BE INSTALLED IN A READILY ACCESSIBLE LOCATION.
 (B) OTHER THAN DWELLING UNITS.
 ALL SINGLE-PHASE RECEPTACLES RATED 150 VOLTS TO GROUND
 OR LESS, 50 AMPERES OR LESS AND THREE-PHASE RECEPTACLES
 RATED 150 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS
 INSTALLED IN THE FOLLOWING LOCATIONS SHALL HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR
 PERSONNEL.
  
 (2)
 KITCHENS
  
 (5)
 SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M
 (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF THE SINK
 EXCEPTION NO. 1 TO (5): IN INDUSTRIAL LABORATORIES,
 RECEPTACLES USED TO SUPPLY EQUIPMENT WHERE REMOVAL OF
 POWER WOULD INTRODUCE A GREATER HAZARD SHALL BE
 PERMITTED TO BE INSTALLED WITHOUT GFCI PROTECTION.
  
 EXCEPTION NO. 2 TO (5): FOR RECEPTACLES LOCATED IN
 PATIENT BED LOCATIONS OF GENERAL CARE (CATEGORY 2) OR
 CRITICAL CARE (CATEGORY 1) SPACES OF HEALTH CARE
 FACILITIES OTHER THAN THOSE COVERED UNDER 210.8(B)(1),
 GFCI PROTECTION SHALL NOT BE REQUIRED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-14 Cont ID  
Sent By pleduc Date 2023-06-14 Time   Rev Time 0.00
Received By pleduc Date 2023-06-13 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-17 Cont ID  
Sent By cmontell Date 2023-07-17 Time 13:34 Rev Time 0.00
Received By cmontell Date 2023-07-17 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-07-17 Cont ID  
Sent By cmontell Date 2023-07-17 Time 13:33 Rev Time 0.00
Received By cmontell Date 2023-07-17 Time 13:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-30 Cont ID  
Sent By ccole Date 2023-06-30 Time 17:26 Rev Time 0.00
Received By ccole Date 2023-06-30 Time 06:58 Sent To  
Notes
2023-06-30 17:28:051ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23060307
 6/30/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2.1 & P5.2: THE PLANS DO NOT APPEAR TO SHOW
 A MEANS OF POTABLE WATER SUPPLY TO THE FILTERED WATER
 SYSTEM- SEC. 608.4 FBC P.
  
 2) SHEETS P1.1 & P5.1: THE PLANS SHOW NON-GREASE-LADEN
 WASTE FROM HAND SINKS (P-5) AND TRENCH RECEIVING
 DISCHARGES FROM ICE MACHINES (P-29A, P-29B, P-29C)
 DRAINING INTO THE GREASE WASTE LINE WHICH IS PROHIBITED
 PER SEC. 1003.3.1 FBC P. THE DRAINAGE FROM THE FIXTURES
 SHALL BE RE-ROUTED TO THE SANITARY. PLEASE CLARIFY IF
 THE TRENCH DRAINS ARE ALSO CONVEYING OTHER WASTE WATER
 THAT IS GREASE-LADEN.
  
 3) D-201: THERE IS NO CORRELATING TEXT FOR NOTE #17
 WHICH IS SHOWN IN THE EXISTING RESTROOMS- SEC. 107.2.1
 WPB.
  
 4) G-002, A-201: IT APPEARS NEW BATHROOM FIXTURES AND
 COMPARTMENTS ARE BEING INSTALLED. PLEASE PROVIDE
 ENLARGED FLOOR PLAN DRAWINGS AND DETAILS SHOWING
 ACCESSIBLE WATER CLOSET DIMENSIONS AND THE CLEAR FLOOR
 SPACE DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSETS AND
 LAVATORIES- SECS. 604.3 & 606.2 FBC ACC.
  
 5) G-002: THE WATER CLOSET CENTERLINE MEASUREMENT IS
 NOT SHOWN IN THE DETAIL- SEC. 604.2 FBC ACC.
  
 6) G-002: SHOW THE HEIGHTS OF THE GRAB BARS MEASURED
 FROM THE FINISHED FLOORS TO THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-07-14 Cont ID  
Sent By rmcdouga Date 2023-07-14 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2023-07-14 Time 14:18 Sent To  
Notes
2023-06-30 07:24:11PLUMBING DIG/SIGS PASSED.

Review Stop Z ZONING
Rev No 1 Status P Date 2023-06-22 Cont ID  
Sent By asangele Date 2023-06-22 Time 14:16 Rev Time 0.00
Received By asangele Date 2023-06-22 Time 14:16 Sent To  
Notes
***NONE***