Plan Review Details - Permit 23060106
Plan Review Stops For Permit 23060106
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-07-03 Cont ID  
Sent By jbrooks Date 2023-07-03 Time 09:33 Rev Time 0.00
Received By jbrooks Date 2023-07-03 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-22 Cont ID  
Sent By jbrooks Date 2023-06-22 Time 12:40 Rev Time 0.00
Received By jbrooks Date 2023-06-22 Time 12:11 Sent To  
Notes
2023-06-22 12:40:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R31 SYSTEM NO. W-193 DOES NOT MEET THE
 MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17
 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT
 MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR
 EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. PLEASE NOTE: FL1654-R31 WAS REVISED ON JUNE 20,
 2023 TO FL1654-R32.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By jbrooks Date 2023-06-07 Time 13:38 Rev Time 0.00
Received By jbrooks Date 2023-06-07 Time 08:18 Sent To  
Notes
2023-06-07 13:39:17JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL1654-R30 HAS BEEN
 REVISED TO FL1654-R31. PLEASE PROVIDE THE FOLLOWING:
 COVER PAGE, EVALUATION REPORT PAGES 1-5 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. SUBMITTED
 FLORIDA DBPR PRODUCT APPROVAL FL1654-R30 SYSTEM NO.
 W-209 DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -131.42 FOR EXPOSURE CATEGORY D AREAS.
 PROVIDE SYSTEM THAT MEETS OR EXCEEDS ALL DESIGN
 PRESSURE REQUIREMENTS FOR EXPOSURE CATEGORY D/PROVIDE
 SIGNED AND SEALED ENGINEERED NAILING CALCULATIONS WITH
 AN APPROVED SYSTEM.
 2. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF
 DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD
 OF PROVIDING POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-03 Cont ID  
Sent By jbrooks Date 2023-07-03 Time 09:33 Rev Time 0.00
Received By jbrooks Date 2023-06-26 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-22 Cont ID  
Sent By jbrooks Date 2023-06-22 Time 12:40 Rev Time 0.00
Received By jbrooks Date 2023-06-12 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-07 Cont ID  
Sent By jbrooks Date 2023-06-07 Time 13:39 Rev Time 0.00
Received By jbrooks Date 2023-06-05 Time 10:48 Sent To  
Notes
***NONE***