Plan Review Details - Permit 23051661
Plan Review Stops For Permit 23051661
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-06-01 Cont ID  
Sent By cpuell Date 2023-06-01 Time 16:54 Rev Time 0.00
Received By cpuell Date 2023-06-01 Time 16:54 Sent To  
Notes
2023-06-01 16:55:03UPDATED PERMIT TO REFLECT CORRECT ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-28 Cont ID  
Sent By jbrooks Date 2023-07-28 Time 12:58 Rev Time 0.00
Received By jbrooks Date 2023-07-28 Time 08:09 Sent To  
Notes
2023-07-28 13:00:36JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL5444-R20 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: COVER SHEET
 (WWW.FLORIDABUILDING.ORG, THIS WILL INCLUDE THE (CODE
 VERSION, PRODUCT APPROVAL NUMBER, STATUS, GENERAL
 INFORMATION ABOUT THE PRODUCT). MISSING EVALUATION
 REPORT PAGES 11-15.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5444-R20 COVERS MULTIPLE PRODUCTS &
 INSTALLATION METHODS. SELECT PRODUCT & INSTALLATION
 METHOD TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
 3. FBC B 107.2.1. PLEASE VERIFY & CORRECT; NEWLY
 SUBMITTED ROOF DIAGRAM/SKETCH SHOWS BUILDING ADDRESS AS
 3171 VILLAGE BLVD, PERMIT APPLICATION IS FOR 3121
 VILLAGE BLVD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-05 Cont ID  
Sent By jbrooks Date 2023-06-05 Time 09:14 Rev Time 0.00
Received By jbrooks Date 2023-06-05 Time 07:47 Sent To  
Notes
2023-06-05 09:14:44JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 21-1130.01 COVERS
 MULTIPLE PRODUCTS & INSTALLATION PROCEDURES: SYSTEMS
 TYPE E(1) THROUGH F(1). SELECT PRODUCT & INSTALLATION
 PROCEDURE TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS.
 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ASPHALT SHINGLE
 ROOFING SYSTEM TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING. SUBMITTED MIAMI-DADE NOA NO. 21-0518.04
 LIMITATION #2 SHALL NOT BE INSTALLED ON ROOF HEIGHTS IN
 EXCESS OF 33FT. SUBMITTED ROOF DIAGRAM LISTS MEAN ROOF
 HEIGHT 30 FT. A THREE-STORY COMMERCIAL BUILDING WITH A
 6:12 ROOF SLOPE MEAN ROOF HEIGHT @ A MINIMUM WILL BE 40
 FT.
 3. FBC B 107.2.1. PLEASE VERIFY & CORRECT; SUBMITTED
 ROOF DIAGRAM/SKETCH SHOWS BUILDING ADDRESS AS 3101
 VILLAGE BLVD, PERMIT APPLICATION IS FOR 3131 VILLAGE
 BLVD.
 4.FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE IS
 LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO WALL
 CONNECTIONS WILL BE IMPROVED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-28 Cont ID  
Sent By jbrooks Date 2023-07-28 Time 13:00 Rev Time 0.00
Received By jbrooks Date 2023-07-26 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-05 Cont ID  
Sent By jbrooks Date 2023-06-05 Time 09:14 Rev Time 0.00
Received By jbrooks Date 2023-06-01 Time 10:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-07-28 Cont ID  
Sent By jbrooks Date 2023-07-28 Time 12:56 Rev Time 0.00
Received By jbrooks Date 2023-07-28 Time 12:56 Sent To  
Notes
2023-07-28 12:56:37JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED HURRICANE MITIGATION
 RETROFIT MANUAL INSPECTION LETTER IS A COPY OF A WET
 SIGNATURE. PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved