Plan Review Details - Permit 23051628
Plan Review Stops For Permit 23051628
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-06-14 Cont ID  
Sent By cpuell Date 2023-06-14 Time 10:06 Rev Time 0.00
Received By cpuell Date 2023-06-14 Time 10:06 Sent To  
Notes
2023-06-14 10:07:56AREA OF WORK IS FOR PARCEL 74434321010130133, THE
 PARCEL NEEDS TO BE READDRESSED DUE TO THE A AND B
 DESIGNATORS AND THAT THE PARCEL TO THE WEST OF IT
 CHARES THE SAME ADDRESS. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-23 Cont ID  
Sent By shill Date 2023-06-23 Time 10:22 Rev Time 0.00
Received By shill Date 2023-06-23 Time 10:22 Sent To  
Notes
2023-06-23 10:23:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FS489, FBC 107, SURVEY IS NOT LEGIBLE. THE CHICKEE
 CANNOT HAVE NON WOOD MATERIALS. SURVEY IS TO SHOW THAT
 THE AREA WHERE THE CHICKEE IS PROPOSED IS NOT CONCRETE.
  
 (I)CHICKEES CONSTRUCTED BY THE MICCOSUKEE TRIBE OF
 INDIANS OF FLORIDA OR THE SEMINOLE TRIBE OF FLORIDA. AS
 USED IN THIS PARAGRAPH, THE TERM "CHICKEE" MEANS AN
 OPEN-SIDED WOODEN HUT THAT HAS A THATCHED ROOF OF PALM
 OR PALMETTO OR OTHER TRADITIONAL MATERIALS, AND THAT
 DOES NOT INCORPORATE ANY ELECTRICAL, PLUMBING, OR OTHER
 NONWOOD FEATURES.
  
 2. PROVIDE INFORMATION REGARDING THE INDIVIDUAL(S) WHO
 PROPOSE TO DO THE INSTALLATION.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-06-06 Cont ID  
Sent By pleduc Date 2023-06-06 Time   Rev Time 0.00
Received By pleduc Date 2023-06-06 Time 10:43 Sent To  
Notes
2023-06-06 10:45:22THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A 10 X 30 CHICKEE HUT W NO
 ELECTIC NOR PLUMBING; HOWEVER, THERE IS NO INDICATED
 PURPOSE NOR USE OF THE PROPOSED.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE AND
 ANY APPLICABLE FLOOR PLANS INCLUDING
 TABLES/CHAIRS, FURNITURE, PLANTERS, LANDCAPE, ETC.
 UNDER IT.
  
  
  
 2) THERE IS AN INDICATION ON THE SURVEY OF THE HUT 5 '
 FROM THE EAST BUILDING AND WHAT APPEARS TO BE LESS FROM
 THE EXISTING SITE BUILDING BUT NO INDICATION HOW THIS
 PROPOSED LOCATION AFFECTS THE EXISTING EXITING OF THE
 EXISTING BUILDING.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN SHEET INDICATING
 COMPLIANCE
  
  
  
 3) THERE IS AN INDICATION OF AN APPARENT COMBUSTIBLE
 VEGETATION HUT, BUT NO INDICATION OF PROPOSED FIRE
 PROTECTION/FIRE RETARDANT CERTIFICATION.
  
 4.6 GENERAL REQUIREMENTS
  
 4.6.1 AUTHORITY HAVING JURISDICTION.
  
 4.6.1.1 THE AUTHORITY HAVING JURISDICTION SHALL
 DETERMINE WHETHER THE
 PROVISIONS OF THIS CODE ARE MET.
  
 4.6.1.2 ANY REQUIREMENTS THAT ARE ESSENTIAL FOR THE
 SAFETY OF BUILDING
 OCCUPANTS AND THAT ARE NOT SPECIFICALLY PROVIDED FOR BY
 THIS CODE SHALL
 BE DETERMINED BY THE AUTHORITY HAVING JURISDICTION
  
 4.6.1.3 WHERE IT IS EVIDENT THAT A REASONABLE DEGREE OF
 SAFETY IS PROVIDED,
 ANY REQUIREMENT SHALL BE PERMITTED TO BE MODIFIED IF,
 IN THE JUDGMENT
 OF THE AUTHORITY HAVING JURISDICTION, ITS APPLICATION
 WOULD BE HAZARDOUS
 UNDER NORMAL OCCUPANCY CONDITIONS.
  
 PLEASE PROVIDE FOR THE INTENT TO APPLY/INSTALL A FIRE
 RETARDANT CERTICATION BY A QUALIFIED LICENSED CONTRATOR
 TO THIS STRUCTURE.
  
  
  
 4) FOR INFORMATIONAL PURPOSES;
  
 NO COOKING, BBQS, OPEN FLAMES NOR PROPANE HEATERS WILL
 BE ALLOWED UNDER THE HUT WITHOUT PRIOR REVIEW AND
 APPROVAL
 AND/OR PERMITTING IF APPLICABLE.
  
 WARMING OF FOOD IS ACCEPTABLE, ENSURE NO COMBUSTIBLES
 NEAR WARMING DEVICES.
  
 NO PYROTECHNICS/FLAME EFFECTS ON STAGE IN OR AROUND THE
 HUT WITHOUT PROPER FIREWORKS APPLICATION
 APPROVAL BY THE FIRE MARSHAL.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-23 Cont ID  
Sent By shill Date 2023-06-23 Time 10:27 Rev Time 0.00
Received By shill Date 2023-06-05 Time 10:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-06-16 Cont ID  
Sent By cibaven Date 2023-06-16 Time 12:33 Rev Time 0.00
Received By cibaven Date 2023-06-16 Time 12:33 Sent To  
Notes
2023-06-16 12:33:28PLEASE NOTE, SOME DIMENSIONS ON THE SURVEY SHEET THAT
 SHOW THE LOCATION OF THE PROPOSED STRUCTURE ARE NOT
 ELIGIBLE. PLEASE REVISE PLAN OR PROVIDE A HIGHER
 QUALITY PLAN. PLEASE, LABEL AREA WITH THE TYPE OF USE
 PROPOSED.
  
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER / ZONING AND PLANNING
 [email protected]
 561-822-1402
  