Plan Review Details - Permit 23051607
Plan Review Stops For Permit 23051607
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-17 Cont ID  
Sent By rperdomo Date 2023-07-17 Time 14:13 Rev Time 0.00
Received By rperdomo Date 2023-07-17 Time 14:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-07-11 Cont ID  
Sent By rperdomo Date 2023-07-11 Time 09:28 Rev Time 0.00
Received By rperdomo Date 2023-07-11 Time 08:47 Sent To  
Notes
2023-07-11 09:29:55FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE ELECTRICAL SCOPE OF WORK. FBC 107.2.1,
 107.3.5, AND FS 471.003(2), 471.025
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN P. PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-07-06 Cont ID  
Sent By pleduc Date 2023-07-06 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-06-28 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-07-03 Cont ID  
Sent By ccole Date 2023-07-03 Time 16:09 Rev Time 0.00
Received By ccole Date 2023-07-03 Time 15:56 Sent To  
Notes
2023-07-03 16:12:421ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23051607
 7/3/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SITE PLAN: PROVIDE POTABLE WATER SERVICE LINE
 DETAILS FOR THE CONSTRUCTION TRAILER- SEC. 108.2 WPB &
 - SECS. 301.4, 602.1, 602.2, & 605.3 FBC P. SHOW THE
 TYPE AND SIZE OF SERVICE LINE, SERVICE LINE RUN, POINT
 OF CONNECTION TO THE CITY MAIN, AND THE LOCATIONS OF
 THE WATER METER AND BACKFLOW PREVENTER. INDICATE THE
 TYPE AND SIZE OF BACKFLOW PREVENTER TO BE INSTALLED-
 SEC. 608.3 FBC P AND SEC. E WPB UTILITIES CROSS
 CONNECTION MANUAL. PLEASE NOTE A SEPARATE PLUMBINGL
 PLAN MAY SUBMITTED AS AN ALTERNATIVE TO REVISING THE
 SITE PLAN- SEC. 107.2.1 WPB.
 A) CONCERNING THE BACKFLOW PREVENTER PLEASE NOTE A
 PERMIT APPLICATION SHALL BE SUBMITTED FOR THE
 INSTALLATION PRIOR TO APPROVAL OF THE PLUMBING PLAN
 REVIEW. YOU CAN SUBMIT AN APPLICATION TBD (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 2) SITE PLAN: PROVIDE A SANITARY DRAINAGE PLAN FOR THE
 TRAILER- SEC 701.2 & 701.3 FBC P. PROVIDE EITHER A
 DIRECT PIPE CONNECTION TO THE CITY SEWER LINE OR AN
 ONSITE SYSTEM SUCH AS A HOLDING TANK WITH PUMP-OUT
 CAPABILITY.
 A) SEWER CONNECTION- SHOW THE TYPE AND SIZE OF BUILDING
 DRAIN PIPE, THE DRAIN PIPE RUN, POINT OF CONNECTION TO
 THE SEWER LINE, AND CLEANOUT LOCATIONS.
 B) PUMP TANK- SHOW THE LOCATION OF THE TANK ON THE
 PLAN, PROVIDE A PIPING DIAGRAM, AND SUBMIT
 MANUFACTURER???S SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-07-14 Cont ID  
Sent By cibaven Date 2023-07-14 Time 16:55 Rev Time 0.00
Received By cibaven Date 2023-07-14 Time 16:54 Sent To  
Notes
2023-07-14 16:55:40PLEASE REVISE YOUR SITE PLAN, THE TRAILER NEEDS TO BE
 SETBACK 25 FEET FROM THE FRONT FACING 8TH STREET AND
 SETBACK FROM THE REAR SHOULD BE A MINIMUM OF 20FEET.
 SIDE SETBACKS SHOWN ON SITE PLAN MEET THE PROVIDENCIA
 PARK DISTRICT'S REQUIREMENTS. (SETBACKS ARE MEASURE
 FROM THE LOT LINE TO THE NEAREST VERTICAL SURFACE).
  
 CLAUDIA D. IBAVEN
 CITY URBAN DESIGNER / ZONING AND PLANNING
 [email protected]
 561-822-1402
  