Plan Review Details - Permit 23051604
Plan Review Stops For Permit 23051604
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By jwitmer Date 2023-06-27 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2023-06-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By jwitmer Date 2023-06-01 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2023-06-01 Time 07:30 Sent To  
Notes
2023-06-01 07:57:44WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W.P.B. REVISION: 23051604
 W. P. B. PERMIT: 22080822
 ADD: 3800 WASHINGTON RD # 1207
 CONT: SAMUEL BLAKE DEV.
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. 06/01/2023
 ACTION: DENIED
  
 1) REVISION SUBMITTED BUT THERE IS NO INCREASE IN VALUE
 FOR THE NEW SCOPE OF WORK.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 2) THE MECHANICAL CONTRACTOR SUBMITTED PLANS THE
 CONTRACTOR DREW. PLEASE NOTE THERE IS A ARCHITECT OF
 RECORD SANDRA PUERTA THAT DREW ALSO THE MEP DRAWINGS.
 CONTRACTOR NEEDS TO SUBMIT FIELD CHANGES TO THE
 DESIGNER OF RECORD TO BE REVIEWED AND INCORPORATED INTO
 THE DESIGNER OF RECORD PLANS. THIS IS A $100,000-DOLLAR
 PROJECT BEFORE REVISION MUST BE DRAWN BY THE DESIGNER
 OF RECORD. FL S 481.229.
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-07-01 Cont ID  
Sent By jleahy Date 2023-07-01 Time 11:10 Rev Time 0.00
Received By jleahy Date 2023-07-01 Time 11:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-12 Cont ID  
Sent By jleahy Date 2023-06-12 Time 11:51 Rev Time 0.00
Received By jleahy Date 2023-06-12 Time 11:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-22 Cont ID  
Sent By pleduc Date 2023-06-22 Time   Rev Time 0.00
Received By pleduc Date 2023-06-22 Time 14:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-06-01 Cont ID  
Sent By pleduc Date 2023-06-01 Time   Rev Time 0.00
Received By pleduc Date 2023-06-01 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-01 Cont ID  
Sent By jleahy Date 2023-07-01 Time 11:10 Rev Time 0.00
Received By jleahy Date 2023-06-20 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-12 Cont ID  
Sent By jleahy Date 2023-06-12 Time 11:51 Rev Time 0.00
Received By jleahy Date 2023-05-31 Time 13:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-06-22 Cont ID  
Sent By rwbrown Date 2023-06-22 Time 12:47 Rev Time 0.00
Received By rwbrown Date 2023-06-22 Time 12:46 Sent To  
Notes
2023-06-22 13:07:531ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 912.1 - EACH WET-VENTED FIXTURE DRAIN SHALL
 CONNECT INDEPENDENTLY TO THE HORIZONTAL WET VENT. THE
 WATER CLOSET, TUB AND SHOWER ARE ILLEGALLY CONNECTED.
 THEY EACH NEED TO CONNECT INDEPENDENTLY TO THE VENTED
 BRANCH.
  
 2. 2017 WPB AMENDS 107.2.1 - PLEASE CLARIFY THE VENT.
 TYPICALLY, THE VENT WOULD TIE INTO A VENT STACK. IF
 THIS IS ON THE TOP FLOOR AND A NEW VENT THROUGH THE
 ROOF IS INTENDED, THEN NEW PENETRATIONS WOULD BE
 SUBJECT TO FIRE STOPPING RULES. IF THIS IS ON THE TOP
 FLOOR THE THE DRAIN DETAIL THAT INDICATE "UP TO THE
 13TH FLOOR" WOULD NOT BE THERE. IT WOULD BE A "STACK
 VENT".
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By rwbrown Date 2023-06-01 Time 13:34 Rev Time 0.00
Received By rwbrown Date 2023-06-01 Time 13:34 Sent To  
Notes
2023-06-01 13:36:351ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 901.2.1 - THE TUB AND SHOWER ARE CONNECTED
 TO THE STACK WITHOUT A VENT. IF IT WERE A FIXTURE
 STACK, THE TWO FIXTURE DRAINS WOULD HAVE TO CONNECT
 INDEPENDENTLY TO THE STACK.
  
 2. 2020 FPC 315.1 - NEW PENETRATIONS NEED UL LISTED
 DETAILS FOR FIRE STOPPING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2023-05-31 Cont ID  
Sent By lmarchan Date 2023-05-31 Time 13:09 Rev Time 0.00
Received By lmarchan Date 2023-05-31 Time 13:09 Sent To  
Notes
2023-05-31 13:09:47APPROVED ON MASTER

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By jwitmer Date 2023-06-27 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2023-06-27 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-01 Cont ID  
Sent By jwitmer Date 2023-06-01 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2023-06-01 Time 07:55 Sent To  
Notes
***NONE***