Plan Review Stops For Permit 23050963 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-06-15 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-15 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-15 |
Time |
10:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-22 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-22 |
Time |
14:12 |
Sent To |
|
|
Notes |
2023-05-22 14:21:35 | ROOFING | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PRODUCT APPROVAL FL5259-R38 FOR THE UNDERLAYMENT - | | SYSTEM NUMBER UDL-2 (-90.0) IS CIRCLED WHICH DOES NOT | | MEET THE REQUIRED PRESSURE PER THE FRSA/TRI FLORIDA | | HIGH WIND CONCRETE AND CLAY ROOF TILE INSTALLATION | | MANUAL TABLE 1A | | | | 2) PLEASE SHOW THE MEAN ROOF HEIGHT - FBC 107.2.1.1 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-22 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-19 |
Time |
16:53 |
Sent To |
|
|
Notes |
|
|
|