Plan Review Details - Permit 23050957
Plan Review Stops For Permit 23050957
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By pvalenti Date 2023-07-24 Time 14:45 Rev Time 0.00
Received By pvalenti Date 2023-07-24 Time 14:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-21 Cont ID  
Sent By pvalenti Date 2023-07-21 Time 16:04 Rev Time 0.00
Received By pvalenti Date 2023-07-21 Time 15:17 Sent To  
Notes
2023-07-21 16:04:47PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 3RD BUILDING REVIEW DENIED:
  
 NOTE: BELOW LISTED IS THE BREAKDOWN OF THE REASON FOR
 FAILURE.
 WHAT IS REQUIRED IS TO PROVIDE A FLOORING UNDERLAYMENT
 THAT WORKS FOR THE WOOD FLOOR AND WAS NOT TESTED WITH
 AN INSULATED GYPSUM BOARD SUSPENDED CEILING. THE TEST
 REPORTS STILL HAVE TO COVER SOUND AND FLAME SPREAD
 UNDER ASTM E 492, ASTM E 90 & ASTM E 84.
  
  
 2.) THE (2) TEST REPORTS THAT WERE SUBMITTED ARE NOT
 APPLICABLE TO THIS PROJECT. THE ASTM E 492 TEST REPORT
 (PROFLEX MSC 90) IS FOR PORCELAIN TILE FLOORING AND FOR
 SITUATIONS WHERE THERE IS A DROPPED CEILING. THE OTHER
 TEST REPORT IS FOR ASTM E 84 (PROFLEX SUPER-SIM 90)
 WHICH IS FOR FLAME SPREAD OF PORCELAIN TILE AND RED OAK
 FLOORING.
  
 THERE WERE NO TEST REPORTS FOR THE UNDERLAYMENT/MAPEI
 ULTRABOND 980 SUBMITTED. PLEASE NOTE THAT TEST REPORTS
 ARE REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT
 ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-10 Cont ID  
Sent By pvalenti Date 2023-07-10 Time 07:16 Rev Time 0.00
Received By pvalenti Date 2023-07-10 Time 06:54 Sent To  
Notes
2023-07-10 07:26:52PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
  
 2.) THE (2) TEST REPORTS THAT WERE SUBMITTED ARE NOT
 APPLICABLE TO THIS PROJECT. THE ASTM E 492 TEST REPORT
 (PROFLEX MSC 90) IS FOR PORCELAIN TILE FLOORING AND FOR
 SITUATIONS WHERE THERE IS A DROPPED CEILING. THE OTHER
 TEST REPORT IS FOR ASTM E 84 (PROFLEX SUPER-SIM 90)
 WHICH IS FOR FLAME SPREAD OF PORCELAIN TILE AND RED OAK
 FLOORING.
  
 THERE WERE NO TEST REPORTS FOR THE UNDERLAYMENT/MAPEI
 ULTRABOND 980 SUBMITTED. PLEASE NOTE THAT TEST REPORTS
 ARE REQUIRED - MANUFACTURER SPEC SHEETS ARE NOT
 ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC
 SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-07-05 Cont ID  
Sent By pvalenti Date 2023-07-05 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2023-07-05 Time 06:56 Sent To  
Notes
2023-07-05 07:26:32PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, PROVIDE A FLOOR PLAN (SKETCH/LAYOUT
 SHEET) SHOWING THE LOCATIONS OF PROPOSED NEW FLOORING.
  
 2.) THERE WERE NO TEST REPORTS FOR THE
 UNDERLAYMENT/MAPEI ULTRABOND 980 SUBMITTED. PLEASE NOTE
 THAT TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC
 SHEETS ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN
 SPEC SHEETS/BROCHURES AND TEST REPORTS FOR SOME
 MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER
 SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-07-17 Cont ID  
Sent By pleduc Date 2023-07-17 Time   Rev Time 0.00
Received By pleduc Date 2023-07-17 Time 12:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-10 Time 15:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 14:46 Sent To  
Notes
2023-05-23 14:55:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO FLOOR PLAN SHOWING THE LOCATIONS OF THE
 PROPOSED FLOORING
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE RECORD, PLEASE PROVIDE A FLOOR PLAN INDICATING
 THE LOCATIONS OF THE FLOORING.
  
  
 2) THERE IS FLOORING NAME/COLOR BUT NO INDICATIONS OF
 THE FLOORING MANUFACTURER NOR A PRODUCT SPEC SHEET.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 3 ) THERE ARE NO INDICATIONS OF FLOOR/SOUND
 UNDERLAYMENT NOR SPECIFICATIONS SHEETS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR CLARIFICATION PURPOSES IS THERE AN FLOOR/SOUND
 UNDERLAYMENT PROVIDED FOR THIS INSTALLATION.
  
 PLEASE REVIEW AND PROVIDE SPEC SHEETS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-07-24 Cont ID  
Sent By pvalenti Date 2023-07-24 Time 14:45 Rev Time 0.00
Received By pvalenti Date 2023-07-24 Time 08:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-21 Cont ID  
Sent By pvalenti Date 2023-07-21 Time 16:14 Rev Time 0.00
Received By pvalenti Date 2023-07-14 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-10 Cont ID  
Sent By lmarchan Date 2023-07-10 Time 15:42 Rev Time 0.00
Received By lmarchan Date 2023-07-06 Time 13:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-07-05 Cont ID  
Sent By pvalenti Date 2023-07-05 Time 07:26 Rev Time 0.00
Received By pvalenti Date 2023-05-22 Time 13:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-07-05 Cont ID  
Sent By pvalenti Date 2023-07-05 Time 07:26 Rev Time 0.00
Received By pvalenti Date 2023-07-05 Time 06:56 Sent To  
Notes
***NONE***