Plan Review Details - Permit 23050894
Plan Review Stops For Permit 23050894
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-06-12 Cont ID  
Sent By ccole Date 2023-06-12 Time 11:58 Rev Time 0.00
Received By ccole Date 2023-06-12 Time 11:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 06:04 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 06:04 Sent To  
Notes
2023-05-30 06:06:562ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT ADDRESSED - NEED A SITE PLAN SHOWING THE TANK'S
 LOCATION ON THE PROPERTY ---
 2017 WPB AMEND 107.3.5.3 (13) - A SITE PLAN IS REQUIRED
 FOR THE LOCATION OF THE TANK, GAS LINE AND GENERATOR.
  
 2. NOT ADDRESSED - AN ENGINEER'S STAMP ON A DIGITAL
 SUBMITTAL IS NOT ACCEPTED. IT MUST BE AN ELECTRONIC
 SEAL ON THE FILE ITSELF -
 2017 WPB AMEND 105.3.1.2 - THE REQUIRED TIE DOWN SPECS
 SUBMITTED HAVE AN ENGINEERS STAMP/SEAL. THE DATE OF THE
 SEAL IS FROM 2017 AND WOULD NEED TO BE CURRENT IF THE
 ENGINEER'S SEAL IS USED. THE SAME GOES FOR THE TANK
 SPECS. IF AN ENGINEER IS REQUIRED AND YOU CHOOSE TO USE
 THEIR SIGNATURE, IT MUST MEET THE REQUIREMENTS SET IN
 THE STATUTE. ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ENGINEER MUST COMPLY WITH 61G15-23.001 AND BE EITHER
 DIGITALLY SIGNED AND SEALED -OR- ELECTRONICALLY SIGNED
 AND SEALED, IN ACCORDANCE WITH 61G15-23.004 AND
 61G15-23.005 F.A.C. RESPECTIVELY.
  
 3. NOT ADDRESSED - AS SITE PLAN SHOWING ITS LOCATION
 AND SEPARATION FROM STRUCTURE OPENINGS IS REQUIRED --
 2020 FRC R303.5.1 - RESIDENTIAL GAS GENERATORS MUST BE
 10 FEET FROM OPENINGS.
  
 4. NOT ADDRESSED - A SITE PLAN SHOWING ITS LOCATION IS
 REQUIRED -
 2020 FRC G2412.2 (401.2)/2018 NFPA 6.4.1.1 - AN
 UNDERGROUND TANK SHALL BE 10 FEET FROM AN IMPORTANT
 BUILDING OR LINE OF ADJOINING PROPERTY THAT CAN BE
 BUILT UPON PER TABLE 6.4.1.1, TABLE 6.5.1.2, 6.4.1.2
 THROUGH 6.4.1.3, 6.4.3, 6.4.4.1 THROUGH 6.4.4.4, AND
 6.5.3.6 THROUGH 6.5.3.11.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-05-18 Cont ID  
Sent By rwbrown Date 2023-05-18 Time 08:44 Rev Time 0.00
Received By rwbrown Date 2023-05-18 Time 08:44 Sent To  
Notes
2023-05-18 08:53:331ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (13) - A SITE PLAN IS
 REQUIRED FOR THE LOCATION OF THE TANK, GAS LINE AND
 GENERATOR.
  
 2. 2017 WPB AMEND 105.3.1.2 - THE REQUIRED TIE DOWN
 SPECS SUBMITTED HAVE AN ENGINEERS STAMP/SEAL. THE DATE
 OF THE SEAL IS FROM 2017 AND WOULD NEED TO BE CURRENT
 IF THE ENGINEER'S SEAL IS USED. THE SAME GOES FOR THE
 TANK SPECS. IF AN ENGINEER IS REQUIRED AND YOU CHOOSE
 TO USE THEIR SIGNATURE, IT MUST MEET THE REQUIREMENTS
 SET IN THE STATUTE. ALL ELECTRONIC SUBMISSIONS PREPARED
 BY AN ENGINEER MUST COMPLY WITH 61G15-23.001 AND BE
 EITHER DIGITALLY SIGNED AND SEALED -OR- ELECTRONICALLY
 SIGNED AND SEALED, IN ACCORDANCE WITH 61G15-23.004 AND
 61G15-23.005 F.A.C. RESPECTIVELY.
  
 3. 2020 FRC R303.5.1 - RESIDENTIAL GAS GENERATORS MUST
 BE 10 FEET FROM OPENINGS.
  
 4. 2020 FRC G2412.2 (401.2)/2018 NFPA 6.4.1.1 - AN
 UNDERGROUND TANK SHALL BE 10 FEET FROM AN IMPORTANT
 BUILDING OR LINE OF ADJOINING PROPERTY THAT CAN BE
 BUILT UPON PER TABLE 6.4.1.1, TABLE 6.5.1.2, 6.4.1.2
 THROUGH 6.4.1.3, 6.4.3, 6.4.4.1 THROUGH 6.4.4.4, AND
 6.5.3.6 THROUGH 6.5.3.11.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-06-12 Time   Rev Time 0.00
Received By lmarchan Date 2023-06-09 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 06:04 Rev Time 0.00
Received By rwbrown Date 2023-05-26 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-18 Cont ID  
Sent By rwbrown Date 2023-05-18 Time 08:56 Rev Time 0.00
Received By rwbrown Date 2023-05-17 Time 10:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2023-06-12 Cont ID  
Sent By ccole Date 2023-06-12 Time 11:58 Rev Time 0.00
Received By ccole Date 2023-06-12 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 06:04 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 06:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-05-18 Cont ID  
Sent By rwbrown Date 2023-05-18 Time 08:44 Rev Time 0.00
Received By rwbrown Date 2023-05-18 Time 08:44 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-06-12 Cont ID  
Sent By ccole Date 2023-06-12 Time 11:58 Rev Time 0.00
Received By ccole Date 2023-06-12 Time 11:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 06:03 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 06:03 Sent To  
Notes
2023-05-30 06:04:06NOT ADDRESSED--
 ALL ELECTRONIC SUBMISSIONS PREPARED BY AN ENGINEER MUST
 COMPLY WITH 61G15-23.001 AND BE EITHER DIGITALLY SIGNED
 AND SEALED -OR- ELECTRONICALLY SIGNED AND SEALED, IN
 ACCORDANCE WITH 61G15-23.004 AND 61G15-23.005 F.A.C.
 RESPECTIVELY.
  
  
 SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-18 Cont ID  
Sent By rwbrown Date 2023-05-18 Time 08:53 Rev Time 0.00
Received By rwbrown Date 2023-05-18 Time 08:53 Sent To  
Notes
2023-05-18 08:56:27 
 ALL ELECTRONIC SUBMISSIONS PREPARED BY AN ENGINEER MUST
 COMPLY WITH 61G15-23.001 AND BE EITHER DIGITALLY SIGNED
 AND SEALED -OR- ELECTRONICALLY SIGNED AND SEALED, IN
 ACCORDANCE WITH 61G15-23.004 AND 61G15-23.005 F.A.C.
 RESPECTIVELY.
  
  
 SIGNATURE REVIEW FAILED - THE FILES SUBMITTED ARE NOT
 ELECTRONICALLY SEALED
  
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]