Plan Review Stops For Permit 23050763 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2023-05-17 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-17 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-17 |
Time |
11:58 |
Sent To |
|
|
Notes |
2023-05-17 11:59:16 | PARCEL READDRESSED 975, 985 & 995 N RAILROAD AVE |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-12 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-12 |
Time |
15:15 |
Sent To |
|
|
Notes |
2023-07-12 15:15:36 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
12:39 |
Sent To |
|
|
Notes |
2023-06-08 12:40:03 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-12 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-12 |
Time |
14:46 |
Sent To |
|
|
Notes |
2023-07-12 14:56:05 | RENOVATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) ALL OF THE REVISED STRUCTURAL DRAWINGS DO NOT SHOW | | AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED | | DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
10:07 |
Sent To |
|
|
Notes |
2023-06-08 11:57:16 | RENOVATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE A SITE PLAN SHOWING THE BUILDING | | DISTANCE FROM THE PROPERTY LINES - FBC WPB 107.2.5 SITE | | PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED WITH THE | | APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY A SITE | | PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF NEW | | CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, | | DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES | | AND THE PROPOSED FINISHED GRADES, DEPICTING THE | | PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD | | AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT | | SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND | | INCLUDED ON A BOUNDARY LINE SURVEY. (PLEASE PROVIDE CUT | | SECTIONS FOR ANY PROPOSED WATER RETAINING SWALES) | | | | 2) EXTERIOR DOORS CANNOT ENCROACH INTO THE PUBLIC WAY - | | FBC 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET | | IN HEIGHT. | | ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE | | AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE | | PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1 | | THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR | | PROJECT INTO THE PUBLIC RIGHT-OF-WAY. | | | | 3) PLEASE SHOW THE RAMP SLOPE - FBC A 405.2 | | | | 4) PLEASE SHOW THE FIRE WALL EXTENSIONS (IF USING ONE | | OF THE EXCEPTIONS SHOW THE DIMENSIONS AND FIRE RATED | | OPENINGS) - FBC 706.5 HORIZONTAL CONTINUITY. | | FIRE WALLS SHALL BE CONTINUOUS FROM EXTERIOR WALL TO | | EXTERIOR WALL AND SHALL EXTEND NOT LESS THAN 18 INCHES | | (457 MM) BEYOND THE EXTERIOR SURFACE OF EXTERIOR WALLS. | | | | 5) THE LIFE SAFETY PLAN SHOWS NO FIRE WALLS - DRAWING | | A.101 SHOWS SOME FIRE WALLS - PLEASE CLARIFY AND SHOW | | THE HOURLY FIRE RATINGS - FBC 701 | | | | 6) DRAWING A.101 - WASTE ROOM - FIRE WALLS ARE SHOWN | | WITHOUT AN HOURLY RATING - IS THE DOOR TO BE FIRE RATED | | ? FBC 701 | | | | 7) PLEASE PROVIDE A SIGNED AND SEALED ANALYSIS REPORT | | FROM A DESIGN PROFESSIONAL ON THE EXISTING BUILDING | | MEETING THE HIGHER WIND LOADS OF A RISK CATEGORY III AS | | STATED ON THE DRAWINGS - FBC EXISTING BUILDING 1007.2 | | SNOW AND WIND LOADS. BUILDINGS AND STRUCTURES SUBJECT | | TO A CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE | | NATURE OF OCCUPANCY RESULTS IN HIGHER WIND OR SNOW RISK | | CATEGORIES BASED ON THE FLORIDA BUILDING CODE, BUILDING | | TABLE 1604.5, (HIGH-VELOCITY HURRICANE ZONES SHALL | | COMPLY WITH SECTION 1620) SHALL BE ANALYZED AND SHALL | | COMPLY WITH THE APPLICABLE WIND OR SNOW LOAD PROVISIONS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-07-19 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-07-19 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-07-19 |
Time |
16:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-05-31 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-05-31 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
cseifer |
Date |
2023-07-18 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
cseifer |
Date |
2023-07-18 |
Time |
09:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
parking |
Date |
2023-06-01 |
Time |
19:27 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-06-01 |
Time |
19:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-07-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-07-12 |
Time |
15:39 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-22 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-19 |
Time |
15:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-05-22 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-05-22 |
Time |
16:54 |
Sent To |
|
|
Notes |
2023-05-22 16:55:34 | GAS SHALL BE UNDER A SEPARATE PERMIT. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
amcgrego |
Date |
2023-07-11 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-06-12 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-06-12 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2023-06-12 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
Sent By |
jbaker |
Date |
2023-07-17 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
jbaker |
Date |
2023-07-17 |
Time |
12:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2023-06-12 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-06-12 |
Time |
13:16 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2023-06-12 |
Time |
13:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-07-18 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-07-18 |
Time |
14:42 |
Sent To |
|
|
Notes |
2023-07-18 15:27:20 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 23050763 | | 7/18/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PLUMBING WILL BE APPROVED WHEN SHEETS P-101 & | | P-700 ARE RESUBMITTED WITH DIGITAL SIGNATURES AND | | SEALS- FL. STATUTE 471.025 AND SEC. 61G15- 23.005 FAC. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-05-22 |
Time |
17:07 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-05-22 |
Time |
15:54 |
Sent To |
|
|
Notes |
2023-05-22 17:08:01 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 23050763 | | 5/22/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE WATER | | BACKFLOW PREVENTER AND THE GREASE INTERCEPTOR. AT A | | MINIMUM, THE PERMIT APPLICATIONS FOR EACH SHALL BE | | SUBMITTED PRIOR TO MAIN PLUMBING PLAN APPROVAL. IF | | CONTRACTORS ARE NOT CURRENTLY SELECTED FOR EACH | | INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED TBD | | (TO BE DETERMINED). EACH COMPLETED APPLICATION SHALL BE | | EMAILED TO [email protected] . YOU WILL THEN | | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU | | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE | | APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND | | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. | | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA | | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. | | | | 2) SHEETS A301, P101, & P700: THE 8-INCH GUTTER IS | | UNDERSIZED FOR 552 GPM ROOF DRAINAGE FLOW ACCORDING TO | | TABLE 1106.6 FBC P. | | | | A) REFER TO TABLE 1106.3 AND PROVIDE THE DOWNSPOUT | | SIZES. | | | | 3) P100: KEYNOTES 2, 3, 5, 8, & 10 REFER TO CIVIL | | DRAWINGS WHICH WERE NOT UPLOADED FOR REVIEW. PLEASE | | PROVIDE THE DRAWINGS- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
N |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-12 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-12 |
Time |
15:16 |
Sent To |
|
|
Notes |
2023-07-12 15:17:17 | ROOFING SYSTEM TO BE DEFERRED |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-07-12 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-12 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-12 |
Time |
15:48 |
Sent To |
|
|
Notes |
2023-07-12 15:49:36 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) ALL OF THE STRUCTURAL DRAWINGS AND DRAWINGS P-101, | | P-700 DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
12:48 |
Sent To |
|
|
Notes |
2023-05-23 08:22:26 | PLUMBING SIGNATURES APPROVED. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2023-05-30 |
|
|
Cont ID |
|
Sent By |
ckimmerl |
Date |
2023-05-30 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
ckimmerl |
Date |
2023-05-30 |
Time |
10:06 |
Sent To |
|
|
Notes |
|
|