Plan Review Details - Permit 23050418
Plan Review Stops For Permit 23050418
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By rmcphers Date 2023-06-07 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2023-06-07 Time 14:41 Sent To  
Notes
2023-06-07 15:03:00ADD OFFICE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE ROOM USE ON THE DRAWINGS - FBC 107
  
 2) PLEASE SHOW THE ROOM DIMENSIONS - FBC 107
  
 3) PLEASE SHOW THE WALL HOURLY FIRE RATING FOR THE
 OCCUPANCY CLASSIFICATION SEPARATION PER FBC TABLE 508.4
  
 4) PLEASE SHOW THE DOOR SIZES - FBC 107
  
 5) DRAWINGS DO NOT SHOW AS DIGITALLY SIGNED BY THE
 ARCHITECT IN ADOBE READER - SIGNED AND SEALED DRAWINGS
 IN PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY
 SIGNED TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
 6) THIS IS NOT REQUIRED FOR PLAN REVIEW BUT JUST TO
 INFORM YOU - A TEMPORARY/PARTIAL CERTIFICATE OF
 OCCUPANCY WILL NEED TO BE APPLIED FOR BEFORE OCCUPANCY
 SEE FBC WPB 111.3 TEMPORARY/PARTIAL OCCUPANCY. A
 TEMPORARY/PARTIAL CERTIFICATE OF OCCUPANCY OR
 CERTIFICATE OF COMPLETION MAY BE ISSUED FOR A PORTION
 OR PORTIONS OF A BUILDING THAT MAY SAFELY BE OCCUPIED
 PRIOR TO FINAL COMPLETION OF THE BUILDING. THE BUILDING
 OFFICIAL MAY REQUIRE, ONCE ALL LIFE SAFETY ISSUES HAVE
 BEEN COMPLIED WITH, AN APPLICANT TO PROVIDE ADEQUATE
 CASH SURETY FOR UNFINISHED WORK OR REVISION OF PLANS
 UNTIL A PERMANENT CERTIFICATE OF OCCUPANCY OR
 CERTIFICATE OF COMPLETION IS GRANTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By pleduc Date 2023-05-22 Time   Rev Time 0.00
Received By pleduc Date 2023-05-22 Time 10:36 Sent To  
Notes
2023-05-22 10:51:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE OCCUPANCY OF AN AREA
 OF THE PARKING GARAGE.
  
 AS PREVIOUSLY STATED FROM THIS OFFICE AND THE FIRE
 INSPECTOR, LIFE SAFETY IS REQUIRED TO BE IN PLACE,
 INCLUDING FIRE ALARM, FIRE SPRINKLER, EMERGENCY
 LIGHTING, EXIT TRAVEL TO 2 EXITS MIN., EXIT LIGHTING,
 EXITS, ETC.
  
 THERE IS NO INDICATION OF THE ABOVE NOTED LIFE SAFETY
 FEATURES.
  
 THERE IS NO LOCATION FLOOR PLAN SHOWING THE LOCATION
 THE CLEAR PROTECTED EXIT PATHS TO A PUBLIC WAY.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS
  
  
 2) THERE ARE NO INDICATIONS OF ELECTRICAL WIRING.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND PROVIDE ELECTICAL WORK IN COMPLIOANCE
 WITH NFPA 70.
  
  
  
 3) THERE IS NO INDICATIONS OF A/C.
  
 WILL THERE BE A/C PROVIDED?
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-07 Cont ID  
Sent By rmcphers Date 2023-06-07 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2023-05-12 Time 08:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By jgomez Date 2023-05-22 Time 10:03 Rev Time 0.00
Received By jgomez Date 2023-05-22 Time 10:03 Sent To  
Notes
2023-05-22 10:04:49SIGNATURE REVIEW:
  
 1- ARCHITECTURAL DRAWING SUBMITTED A1.1.5M HAVE A COPY
 OF A DIGITAL SIGNATURE. DIGITAL SIGNATURES ARE NOT
 ALLOWED TO BE PRINTED. ALL DOCUMENTS PREPARED BY A
 LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL VERIFIABLE
 DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD AS
 REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 ARCHITECTS
 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.