Plan Review Details - Permit 23050318
Plan Review Stops For Permit 23050318
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-06-12 Cont ID  
Sent By cpuell Date 2023-06-12 Time 17:11 Rev Time 0.00
Received By cpuell Date 2023-06-12 Time 17:11 Sent To  
Notes
2023-06-12 17:12:36WORK IS BEING DONE ON THE NORTH BUILDING ONLY. HALF
 ADDRESS CHANGED FROM 618 1/2 EL VEDADO TO 620 EL
 VEDADO.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By cpuell Date 2023-05-30 Time 16:15 Rev Time 0.00
Received By cpuell Date 2023-05-30 Time 16:15 Sent To  
Notes
2023-05-30 16:19:30WHICH BUILDING IS THE WORK TO BE DONE, NORTH OR SOUTH?
 THE SOUTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS
 THE HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-01 Cont ID  
Sent By jbrooks Date 2023-06-01 Time 10:04 Rev Time 0.00
Received By jbrooks Date 2023-06-01 Time 07:57 Sent To  
Notes
2023-06-01 10:05:13JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 17-1003.04 SYSTEM TYPE E (13) MAXIMUM DESIGN PRESSURE
 -90 PSF. DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -108.17 FOR EXPOSURE CATEGORY C AREAS.
 GENERAL LIMITATION #9 IS SPECIFICALLY REFERRED TO IN
 THIS NOA. THE MAXIMUM DESIGNED PRESSURE LIMITATION
 LISTED SHALL BE APPLICABLE TO ALL ROOF PRESSURE ZONES
 (I.E. FIELD, PERIMETERS, AND CORNERS). NEITHER RATIONAL
 ANALYSIS, NOR EXTRAPOLATION SHALL BE PERMITTED FOR
 ENHANCED FASTENING AT ENHANCED PRESSURE ZONES (I.E.
 PERIMETERS, EXTENDED CORNERS AND CORNERS). THIS SYSTEM
 CAN???T BE USED. PROVIDE SYSTEM THAT MEETS OR EXCEEDS
 THESE REQUIREMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-01 Cont ID  
Sent By jbrooks Date 2023-06-01 Time 10:05 Rev Time 0.00
Received By jbrooks Date 2023-05-25 Time 09:50 Sent To  
Notes
***NONE***