Plan Review Details - Permit 23050314
Plan Review Stops For Permit 23050314
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 12:51 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 12:30 Sent To  
Notes
2023-06-21 12:50:44 
 COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-06-21 Cont ID  
Sent By jwitmer Date 2023-06-21 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2023-06-21 Time 12:31 Sent To  
Notes
2023-06-21 13:31:40WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23050314
 ADD: 807 BELVEDERE RD
 CONT: CLOSE PERMITS FAST INC
 TEL: 561-644-0302
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 21ST/2023
 ACTION: DENIED
  
 1) NOTE THERE ARE (7) EXPIRED PERMITS AT THIS LOCATION.
 PLEASE SEE ABOUT GETTING THE EXPIRED ON THIS PROPERTY
 CLEANED UP, DOES THE SCOPE OF WORK UNDER THIS PERMIT
 ENCOMPASS THE EXPIRED PERMIT WORK?
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2A) THERE IS ALSO A 4X FEE ON GAS PIPING INTERIOR &
 EXTERIOR. NO GAS PERMIT OR GAS WORK SHOWN ON THE PLANS
 JUST THE EXPIRED GAS PERMIT 20090291 IS THERE GOING TO
 BE A GAS PERMIT APPLIED FOR, THERE MAYBE A HOLD PUT ON
 THIS PROPERTY FOR THE UNPERMITTED WORK!!!!!!
 CONFORMANCE. 2020 EXISTING BUILDING CODE, LEVEL-1
 ALTERATION 701.2, LEVEL-2 ALTERATION 801.3, & LEVEL-3
 ALTERATIONS 901.2COMPLIANCE. AN EXISTING BUILDING OR
 PORTION THEREOF SHALL NOT BE ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE THAN ITS EXISTING CONDITION.
  
 2B) THE ORIGINAL BLDG. PERMIT 21030476 EXPIRED HAD A
 VALUE OF $30,000.00 DOLLARS. WHY IS THERE SUCH A
 DIFFERENCE IN THE PRICE FROM THE EXPIRED PERMIT TWICE
 THE VALUE TO THE SCOPE OF WORK SHOWN ON THIS PERMIT.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 3) THE SUBMITTED FLOOR PLAN IS DRAWN BY THE BUILDING
 CONTRACTOR SHOWING WORK UNDER BUILDING, PLUMBING,
 ELECTRICAL AND MECHANICAL, CERTIFICATION BY CONTRACTOR.
 107.3.4.3. THE CONTRACTOR (QUALIFIER) THAT CREATED /
 DREW THE SET OF PLANS AND OR SCHEDULES WILL NEED TO
 IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. PLEASE
 PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE NUMBER FOR
 THE TRADE YOU ARE LICENSED IN AND PLANS AND OR
 SCHEDULES DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE
 LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR
 THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE
 CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF
 PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF
 THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND
 LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND
 PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET. THE PLANS INDICATE NO MECHANICAL WORK BUT
 SHOW IN THE HALLWAY A DROPPED CEILING.
  
 4) THE PLANS STATE A DROP IN CEILING BUT THERE IS NO
 CEILING PLAN SHOWING THE LAYOUT OF CEILING NOR
 COMPLIANCE WITH 2020 FBC-BUILDING CODE 808.1.1,
 808.1.1.1, OR 1208.2.
  
 5) THE FLOOR PLAN SHOWS A SYMBOL A DOT AND A LARGER
 CIRCLE BUT NOT FOUND IN THE LEGEND. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL
 BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 6) THE PLAN DOES NOT ADDRESS THE UNPERMITTED WORK, NOR
 DOES THE FLOOR PLAN PROVIDE ANY ACCESSIBLE ELEMENTS.
 FOR INSTANCE, THE FRONT ENTRY IS NOT ACCESSIBLE, NOR
 THE RESTROOM. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN.
  
 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By jleahy Date 2023-06-07 Time 12:02 Rev Time 0.00
Received By jleahy Date 2023-06-07 Time 11:49 Sent To  
Notes
2023-06-07 12:03:00PLAN NEEDS TO SIGNED PER WPB 107.2.1

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-05-24 Cont ID  
Sent By pleduc Date 2023-05-24 Time   Rev Time 0.00
Received By pleduc Date 2023-05-24 Time 10:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2023-05-31 Cont ID  
Sent By ccole Date 2023-05-31 Time 14:24 Rev Time 0.00
Received By ccole Date 2023-05-31 Time 14:24 Sent To  
Notes
2023-05-31 14:25:021ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23050314
 5/31/2023
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-01: GAS PERMIT #20090291 LISTED ON THE PLAN
 WAS REJECTED IN PLAN REVIEW, WAS NOT ISSUED, EXPIRED,
 AND WAS ULTIMATELY ABANDONED. IN ACCORDANCE WITH SEC.
 107.3.5.1.5 WPB COMPLETE GAS PLANS AND SPECIFICATIONS
 ARE REQUIRED FOR THE NEW RESTAURANT INCLUDING THE
 FOLLOWING ITEMS-
 A) GAS PIPING LAYOUT PLAN AND RISER DRAWING.
 B) GAS APPLIANCE SCHEDULE AND PRODUCT SPECIFICATION
 SUBMITTALS (SUBMITTALS MAY BE DEFERRED AND ONSITE FOR
 INSPECTION).
 C) COMBUSTION AIR PLAN AND CALCULATIONS FOR GAS-FIRED
 APPLIANCES.
 D) GAS VENTING PLANS FOR ALL APPLIANCES REQUIRING
 EXHAUST VENTILATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2023-06-21 Time   Rev Time 0.00
Received By amcgrego Date 2023-05-23 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-05-31 Cont ID  
Sent By ccole Date 2023-05-31 Time 14:04 Rev Time 0.00
Received By ccole Date 2023-05-31 Time 11:05 Sent To  
Notes
2023-05-31 14:07:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23050314
 5/31/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET G-01: BASED ON WPB BUILDING DEPT. RECORDS
 WHICH SHOW MULTIPLE EXPIRED PERMITS FOR PLUMBING UNDER
 THE PREVIOUS OWNERSHIP, ALL PLUMBING WORK SHOWN ON THE
 PLANS SHALL BE REVIEWED AS NEW INSTALLATIONS- SEC.
 107.2.1 WPB. THE CHANGE OF USE FROM HAIR SALON TO
 RESTAURANT REQUIRES THE FOLLOWING PLANS AND DETAILS IN
 ACCORDANCE WITH SECS. 1010.1, 1010.2, & 1010.3 FBC
 EXISTING BUILDING AND THE FBC PLUMBING AND
 ACCESSIBILITY CODES.
  
 A) PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE WITH
 TABLE 403.1 FBC P. PROVIDE A SCHEDULE THAT SHOWS THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES. THE PLANS
 APPEAR TO SHOW A RESTAURANT WHICH IS FOUND UNDER
 ASSEMBLY CLASSIFICATION IN THE TABLE. THERE IS ONLY ONE
 TOILET ROOM SHOWN HOWEVER SEPARATE FACILITIES FOR MALE
 AND FEMALE USE ARE REQUIRED UNLESS MEETING ONE OF THE
 FOUR EXCEPTIONS UNDER SEC. 403.2 FBC P. ALSO REQUIRED
 ARE A SERVICE OR MOP SINK AND DRINKING FOUNTAIN.
 DRINKING FOUNTAINS ARE NOT REQUIRED IF DRINKING WATER
 IS PROVIDED TO PATRONS IN A CONTAINER FREE OF CHARGE-
 SEE SEC. 410.4 FBC P. IF CHOOSING THIS OPTION PLACE A
 NOTE UNDER THE FIXTURE CALCULATIONS.
  
 B) FBC ACCESSIBILITY COMPLIANCE- REFER TO SEC. 202.3,
 213.2, & 213.3 FBC ACC AND PROVIDE THE FOLLOWING
 DRAWINGS AND DETAILS FOR THE NEW TOILET ROOM FIXTURES-
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SEC. 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SEC. 604.5 & 609.4, FIGURES
 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS ???
 SEC. 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2.
  
 C) SANITARY DRAINAGE AND WATER RISER LAYOUT PLANS
 INCLUDING RISER DRAWINGS FOR ALL NEW PLUMBING PIPING
 INSTALLATIONS ASSOCIATE WITH THE NEW FIXTURE
 INSTALLATIONS- SEC. 107.3.5.1.3 WPB.
  
 D) GREASE INTERCEPTOR PLANS- SEC. 1003.1 FBC P
 INCLUDING THE FOLLOWING ITEMS-
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 B) EQUIPMENT SCHEDULE INDICATING THE MAKE AND MODEL AND
 CAPACITY OF THE UNIT.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, VENTS AND CLEANOUTS.
 E) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. (PLEASE NOTE
 THE SPECS MAY BE DEFERRED SUBMITTAL).
  
 PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 GREASE INTERCEPTOR. AT A MINIMUM, THE PERMIT
 APPLICATION SHALL BE SUBMITTED PRIOR TO MAIN PLUMBING
 PLAN APPROVAL. IF A CONTRACTORS IS NOT CURRENTLY
 SELECTED FOR THE INSTALLATION, A PERMIT APPLICATION CAN
 BE SUBMITTED TBD (TO BE DETERMINED). THE COMPLETED
 APPLICATION SHALL BE EMAILED TO [email protected]
 . YOU WILL THEN RECEIVE INSTRUCTIONS TO PAY FEES AND
 UPLOAD PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A
 FUTURE DATE, BUT THE APPLICATION IS REQUIRED AT THIS
 TIME. WE RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS
 AT THE SAME TIME. AFTER YOU HAVE THE PERMIT(S)
 GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE THE
 REVIEW STATUS TO PASS.
  
 E) HOT WATER REQUIREMENTS- SEC. 607.1 FBC P INCLUDING-
 A) LOCATION OF THE WATER HEATER.
 B) EQUIPMENT SCHEDULE FOR THE WATER HEATER.
 C) WATER HEATER PIPING DETAIL SHOWING THE LOCATION OF
 ALL ASSOCIATED DEVICES INCLUDING THE THERMAL EXPANSION
 CONTROL DEVICE, RECIRCULATION PUMP (IF INSTALLED), AND
 REQUIRED TEMPERATURE LIMITING DEVICE PER SEC. 607.1.2.
  
 F) KITCHEN PLUMBING EQUIPMENT SCHEDULE AND LAYOUT PLAN.
 PLEASE PROVIDE A NUMBERED OR LETTERED EQUIPMENT
 SCHEDULE AND CORRESPONDING PLAN SHOWING MAKES AND
 MODELS AND LOCATIONS OF THE 3-COMPARTMENT SINK, HAND
 SINK, FLOOR SINKS AND FLOOR DRAINS, DISHWASHERS,
 GLASSWASHERS, BEVERAGE DISPENSERS ETC.- SEC. 107.2.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-06-07 Cont ID  
Sent By jleahy Date 2023-06-07 Time 12:02 Rev Time 0.00
Received By jleahy Date 2023-06-07 Time 12:02 Sent To  
Notes
2023-06-07 12:02:09FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT SIGNED BY PERSON RESPONSIBLE FOR THE DESIGN
 WPB 107.2.1