Plan Review Stops For Permit 23050068 |
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-07 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-07 |
Time |
10:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2023-05-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-17 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-17 |
Time |
14:09 |
Sent To |
|
|
Notes |
2023-05-17 15:45:31 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | CAN BE FOUND ON THEIR WEBSITE: | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-21 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-21 |
Time |
15:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-07 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-07 |
Time |
10:10 |
Sent To |
|
|
Notes |
2023-06-07 10:18:45 | REMODEL | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-1.03 DOES NOT SHOW AS DIGITALLY SIGNED IN | | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED | | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-17 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-17 |
Time |
14:09 |
Sent To |
|
|
Notes |
2023-05-17 15:51:49 | | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE ACCESSIBLE CLEAR FLOOR SPACE AND | | COUNTER WIDTH ON THE DRAWING FOR THE CHECK OUT COUNTER | | - FBC A 904.4 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-06-14 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-06-14 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-06-13 |
Time |
16:20 |
Sent To |
|
|
Notes |
2023-06-14 14:47:17 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: APPROVED, SEE COMMENTS BELOW | | | | 1. SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE WIRING AND | | ACCESS CONTROL. | | | | END OF COMMENTS | | | | RUBEN P. PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | 561-805-6738 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-05-18 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-05-18 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-05-18 |
Time |
14:31 |
Sent To |
|
|
Notes |
2023-05-18 16:28:37 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE INFORMATION OF THE FEEDERS AND PROTECTIONS | | FOR PANEL 3HA AND PANEL 3LA | | NEC 215.2, 220, 240 | | | | 2. LOW VOLTAGE WIRING REQUIRES A SEPARATE PERMIT | | APPLICATION. | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER/ INSPECTOR | | 561-805-6738 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-06-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-06-21 |
Time |
12:45 |
Sent To |
|
|
Notes |
2023-06-21 12:45:25 | FIRE PROVISO: | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND | | EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS | | FOR CODE COMPLIANT COVERAGE | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-06-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-06-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-06-06 |
Time |
09:47 |
Sent To |
|
|
Notes |
2023-06-06 09:49:49 | FIRE PROVISO: | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND | | EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS | | FOR CODE COMPLIANT COVERAGE | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-08 |
Time |
12:37 |
Sent To |
|
|
Notes |
2023-05-08 13:09:47 | FIRE PROVISO: | | | | ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND | | EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS | | FOR CODE COMPLIANT COVERAGE | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | DRAWINGS. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-06-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-21 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-16 |
Time |
08:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-15 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-15 |
Time |
06:53 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-06-05 |
Time |
17:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-05-19 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-05-19 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-05-03 |
Time |
12:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2023-05-16 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2023-05-16 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2023-05-16 |
Time |
14:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-06-07 |
Time |
05:38 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-06-07 |
Time |
05:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-05-09 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-05-09 |
Time |
08:31 |
Sent To |
|
|
Notes |
2023-05-09 08:35:43 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMENDS 107.3.5.1.3 - PLEASE SUBMIT THE | | REQUIRED RISER/ISOMETRIC FOR THE DRAIN/WASTE/VENT | | SYSTEM. MAKE SURE TO INCLUDE KEY TAGS AT EACH FIXTURE | | FOR IDENTIFICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-21 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-21 |
Time |
15:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-07 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-07 |
Time |
10:19 |
Sent To |
|
|
Notes |
2023-06-07 10:20:13 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-1.03 DOES NOT SHOW AS DIGITALLY SIGNED IN | | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX | | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED | | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-05-17 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-17 |
Time |
16:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-17 |
Time |
16:10 |
Sent To |
|
|
Notes |
|
|