Plan Review Details - Permit 23041466
Plan Review Stops For Permit 23041466
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-07-03 Cont ID  
Sent By rmcdouga Date 2023-07-03 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2023-06-30 Time 10:19 Sent To  
Notes
2023-06-30 11:01:24PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS.MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
 OPENINGS LESS THAN 5 FEET FROM THE GENERATOR EXHAUST
 ARE NOT ALLOWED. FOR OPENINGS THAT ARE BETWEEN 5 FEET
 TO 10 FEET FROM THE PROPOSED GENERATOR EXHAUST
 LOCATION, STATE ON THE PLANS THAT A CO DETECTOR WILL BE
 INSTALLED INSIDE THE BUILDING, EITHER ON THE CEILING OR
 5 FEET ABOVE THE FLOOR, NEXT TO EACH OPENING THAT IS
 BETWEEN 5 FEET TO 10 FEET FROM THE PROPOSED GENERATOR
 EXHAUST LOCATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2023-05-23 Time 12:59 Sent To  
Notes
2023-05-23 13:19:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-02 Cont ID  
Sent By jcooley Date 2023-05-02 Time 16:50 Rev Time 0.00
Received By jcooley Date 2023-05-02 Time 16:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2023-05-05 Cont ID  
Sent By rwbrown Date 2023-05-05 Time 10:38 Rev Time 0.00
Received By rwbrown Date 2023-05-05 Time 10:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-19 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-03 Cont ID  
Sent By rmcdouga Date 2023-07-03 Time 16:24 Rev Time 0.00
Received By rmcdouga Date 2023-06-21 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 13:06 Rev Time 0.00
Received By rmcdouga Date 2023-04-28 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2023-05-22 Cont ID  
Sent By hmoser Date 2023-05-22 Time 09:22 Rev Time 0.00
Received By hmoser Date 2023-05-22 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-05-05 Cont ID  
Sent By rwbrown Date 2023-05-05 Time 10:38 Rev Time 0.00
Received By rwbrown Date 2023-05-05 Time 10:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-23 Cont ID  
Sent By rmcdouga Date 2023-05-23 Time 13:03 Rev Time 0.00
Received By rmcdouga Date 2023-05-23 Time 12:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-16 Cont ID  
Sent By vbroglia Date 2023-05-16 Time 13:44 Rev Time 0.00
Received By vbroglia Date 2023-05-16 Time 13:44 Sent To  
Notes
***NONE***