Plan Review Details - Permit 23041370
Plan Review Stops For Permit 23041370
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 12:11 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 12:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By lbond Date 2023-06-27 Time 08:55 Rev Time 0.00
Received By lbond Date 2023-06-27 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-06-12 Cont ID  
Sent By lbond Date 2023-06-12 Time 12:13 Rev Time 0.00
Received By lbond Date 2023-06-12 Time 12:13 Sent To  
Notes
2023-06-12 12:17:12COMPLY TO FIRE COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-29 Cont ID  
Sent By jleahy Date 2023-06-29 Time 14:23 Rev Time 0.00
Received By jleahy Date 2023-06-29 Time 13:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-06-02 Cont ID  
Sent By jleahy Date 2023-06-02 Time 12:36 Rev Time 0.00
Received By jleahy Date 2023-06-02 Time 12:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-28 Cont ID  
Sent By pleduc Date 2023-06-28 Time   Rev Time 0.00
Received By pleduc Date 2023-06-28 Time 09:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-05-30 Cont ID  
Sent By pleduc Date 2023-05-30 Time   Rev Time 0.00
Received By pleduc Date 2023-05-30 Time 11:57 Sent To  
Notes
2023-05-30 12:11:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS "NEW VINYL FLOORS THROUGHOUT",
 BUT NO INDICATIONS OF A MANUFACTURER'S SPECIFICATION
 SHEET NOR A PRODUCT NAME FOR THE PROPOSED VINYL
 FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE VINYL
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS AN INDICATION OF BATHROOM WORK THAT MAY
 EFFECT FIRE RATED TENANT/CORRIDOR SEPARATION WALLS.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARD
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 IF AN APPLICABLE RATED WALL, PLEASE PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-07-07 Cont ID  
Sent By hmoser Date 2023-07-07 Time 10:51 Rev Time 0.00
Received By hmoser Date 2023-06-26 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-13 Cont ID  
Sent By hmoser Date 2023-06-13 Time 16:50 Rev Time 0.00
Received By hmoser Date 2023-05-26 Time 16:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-07-07 Cont ID  
Sent By hmoser Date 2023-07-07 Time 10:50 Rev Time 0.00
Received By hmoser Date 2023-07-07 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-06-13 Cont ID  
Sent By hmoser Date 2023-06-13 Time 16:47 Rev Time 0.00
Received By hmoser Date 2023-06-13 Time 16:47 Sent To  
Notes
2023-06-13 16:50:17PLAN DENIED
 1) PROVIDE A EQUIPMENT SCHEDULE FOR THE NEW
 AIR CONDITIONING EQUIPMENT ON THE PLAN.
 SECTION 107 FBC 2020

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By ccole Date 2023-06-27 Time 09:51 Rev Time 0.00
Received By ccole Date 2023-06-27 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-05-30 Cont ID  
Sent By rwbrown Date 2023-05-30 Time 10:52 Rev Time 0.00
Received By rwbrown Date 2023-05-30 Time 10:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By lbond Date 2023-06-27 Time 08:55 Rev Time 0.00
Received By lbond Date 2023-06-27 Time 08:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-02 Cont ID  
Sent By jleahy Date 2023-06-02 Time 12:36 Rev Time 0.00
Received By jleahy Date 2023-06-02 Time 12:33 Sent To  
Notes
***NONE***