Plan Review Details - Permit 23041326
Plan Review Stops For Permit 23041326
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 15:37 Rev Time 0.00
Received By pvalenti Date 2023-05-12 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 14:15 Rev Time 0.00
Received By pvalenti Date 2023-05-12 Time 13:39 Sent To  
Notes
2023-05-12 14:48:09PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVAL PENDING APPROVAL OF SIGNATURE
 REVIEW.
  
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: THE FASTENER SPACING LETTER BY DR,. ERNEST A.
 KUONEN, PE 022920 DOES NOT HAVE A 3RD PARTY VERIFIABLE
 DIGITAL SIGNATURE.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A
 VALID DIGITAL SIGNATURE. A SCAN OF A WET SEAL AND
 SIGNATURE OR DIGITAL SIGNATURE IS NOT CONSIDERED A
 VALID DIGITAL SIGNATURE.
 ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR
 ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH
 61G1-16 AND 61G15, F.A.C.
  
 2. SUBMIT LETTER WITH A VALID DIGITAL SIGNATURE.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5), CHPT. 471, F.S. & 61G15 AND CHPT.
 481, F.S. & 61G1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-27 Cont ID  
Sent By jbrooks Date 2023-04-27 Time 09:28 Rev Time 0.00
Received By jbrooks Date 2023-04-27 Time 08:01 Sent To  
Notes
2023-04-27 09:29:29JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA
 REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR
 DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA
 STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA
 STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE.
 ENGINEER???S LETTER NOT PROPERLY SEALED.
 2. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL16730-R41
 IS NOT APPROVED FOR USE OUTSIDE HVHZ. CITY OF WEST PALM
 BEACH IS NOT LOCATED IN A HVHZ. PROVIDE A COMPLETE SET
 OF 2020 CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE
 PROPOSED FLAT ROOF SYSTEM TO BE USED. INCLUDE COVER
 PAGE, EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS
 FOR SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R34
 HAS BEEN REVISED TO FL5259-R38. PLEASE PROVIDE A
 COMPLETE SET TO INCLUDE COVER PAGE(S); IT COVERS
 MULTIPLE PRODUCT TYPES; ROOF COVER OPTIONS; ALLOWABLE
 UNDERLAYMENT/TILE-ADHESIVE COMBINATIONS, ALLOWABLE
 SUBSTRATES & ATTACHMENT LIMITATIONS. SELECT OPTIONS
 FROM EACH CATEGORY TO BE USED; SELECT FROM TABLE 4A
 DIRECT-TO-DECK UNDERLAYMENT IN TILE ROOF APPLICATIONS
 OR TABLE 4B 2-PLY UNDERLAYMENT SYSTEMS IN TILE ROOF
 APPLICATIONS. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS.
 4. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING. REVIEW STAMP WITH INITIALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By amhamilt Date 2023-05-12 Time 13:21 Rev Time 0.00
Received By amhamilt Date 2023-05-12 Time 13:21 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By amhamilt Date 2023-05-02 Time 16:49 Rev Time 0.00
Received By amhamilt Date 2023-05-02 Time 16:49 Sent To  
Notes
2023-05-02 16:49:54THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 APPROVED PLANS HAVE BARREL TILE PRODUCT, HOWEVER, S
 TILE WAS SUBMITTED. PLEASE REVISE TO THE APPROVED
 BARREL TILE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amhamilt Date 2023-05-01 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 15:37 Rev Time 0.00
Received By pvalenti Date 2023-05-12 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 14:57 Rev Time 0.00
Received By pvalenti Date 2023-05-10 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-03 Cont ID  
Sent By aoliver Date 2023-05-03 Time 09:30 Rev Time 0.00
Received By aoliver Date 2023-04-26 Time 08:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 15:37 Rev Time 0.00
Received By pvalenti Date 2023-05-12 Time 15:37 Sent To  
Notes
2023-05-12 15:44:01PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW APPROVED BY SUBMITTAL OF ENGINEER'S
 ORIGINAL HAND SIGNED/SEALED LETTER FOR ROOF ZONE
 FASTENER SPACING. THIS LETTER HAS BEEN ROUTED TO THE
 STORAGE BIN.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-05-12 Cont ID  
Sent By pvalenti Date 2023-05-12 Time 14:49 Rev Time 0.00
Received By pvalenti Date 2023-05-12 Time 13:39 Sent To  
Notes
2023-05-12 14:57:09SIGNATURE REVIEW DENIED:
  
 THE LETTER FOR THE FASTENER SPACING BY DR. ERNEST A.
 KUONEN, PE 022920 DOES NOT HAVE A 3RD PARTY VERIFIABLE
 DIGITAL SIGNATURE/SEAL.
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) LETTER:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-27 Cont ID  
Sent By jbrooks Date 2023-04-27 Time 09:28 Rev Time 0.00
Received By jbrooks Date 2023-04-27 Time 09:28 Sent To  
Notes
2023-04-27 09:28:34JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 SUBMITTED SIGNED AND SEALED ENHANCED NAILING
 CALCULATIONS IS A COPY OF A WET SIGNATURE. PLEASE
 UPLOAD A VALID ELECTRONICALLY SIGNED PLAN/DOCUMENT TO
 PROJECTDOX
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 PLEASE UPLOAD A VALID ELECTRONICALLY SIGNED
 PLAN/DOCUMENT TO PROJECTDOX
 PAPER PLANS/DOCUMENTS FOR SIGNATURE REVIEW WILL NO
 LONGER BE ACCEPTED BY THE CITY OF WEST PALM BEACH
 BUILDING DEPRTMENT.
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  