Plan Review Details - Permit 23041295
Plan Review Stops For Permit 23041295
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-27 Cont ID  
Sent By cpuell Date 2023-04-27 Time 07:11 Rev Time 0.00
Received By cpuell Date 2023-04-27 Time 07:11 Sent To  
Notes
2023-04-27 07:17:53ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-06-20 Cont ID  
Sent By cseifer Date 2023-06-20 Time 07:44 Rev Time 0.00
Received By cseifer Date 2023-06-20 Time 07:41 Sent To  
Notes
2023-06-20 07:44:141) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 INCLUDE CITY UNDERGROUND UTILITIY PIPE SIZE, PIPE
 MATERIAL AND DESCRIPTION ON THE SITE PLAN. CONTACT
 JANICE TARBILL, [email protected] FOR AS-BUILT
 INFORMATION. INCLUDE AS-BUILT INFORMATION IN YOUR
 SUBMITTAL.
 2 PROVIDE PROFILE FOR PROPOSED UNDERGROUND ELECTRICAL
 ROUTE, SHOWING ALL CROSSING DATA FOR OTHER UTILITIES.
 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE
 REQUIRED PER CITY STANDARDS.
  
 REVIEWED BY:
 CHLOE SEIFER
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By amcgrego Date 2023-07-14 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-06-22 Cont ID  
Sent By lmarchan Date 2023-06-22 Time 08:36 Rev Time 0.00
Received By lmarchan Date 2023-04-26 Time 10:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2023-05-23 Cont ID  
Sent By avolcy Date 2023-05-23 Time 09:52 Rev Time 0.00
Received By avolcy Date 2023-05-23 Time 09:52 Sent To  
Notes
2023-05-23 09:53:25INSUFFICIENT
  
 1) ACACIA ROAD AND CURRIE CRESCENT AT THE LOCATION OF
 THE PROPOSED POLE IS CURRENTLY UNDER RECONSTRUCTION/HAS
 RECENTLY BEEN RECONSTRUCTED WHICH MAY REQUIRE THAT THE
 POLE AND UNDERGROUND ELECTRIC TO THE POLE BE RELOCATED.
 THE WORK INCLUDES BOTH ABOVE AND BELOW GROUND
 INFRASTRUCTURE, TO INCLUDE THE REMOVAL OF SOME OF THE
 UTILITY POLES. PLEASE CONTACT LINDA QUINONES, SENIOR
 ENGINEERING PROJECT COORDINATOR, AT 561-494-1085 FOR A
 COPY OF THE LATEST PLANS. THE ENGINEERING PLANS AND
 SURVEY NEED TO BE UPDATED ACCORDINGLY TO SHOW ACCURATE
 PLANS BASED ON THE RECONSTRUCTION OF THE ACACIA ROAD
 AND CURRIE CRESCENT RIGHTS-OF-WAY.
  
 2) BASED ON THE FINAL RECONSTRUCTION PLANS, THE POLE
 WILL NEED TO BE LOCATED TO ALIGN WITH THE EXISTING AND
 PROPOSED TREES AND POLES IN THE RIGHT-OF-WAY.
  
 3) ALL UNDERGROUND UTILITIES AND FEATURES NEED TO BE
 PROVIDED ON THE SURVEY. THE PROVIDED SURVEY
 SPECIFICALLY STATES THAT NO UNDERGROUND UTILITY LOCATES
 WERE DONE, WHICH DOES NOT COMPLY WITH THE CITY CODE
 REQUIREMENTS.
  
 4) THE CROSS SECTION SHOWS THAT THERE IS A CLEAR ZONE
 OF 2.5 FEET, WHICH DOES NOT COMPLY WITH THE ADA MINIMUM
 REQUIREMENT OF 36 INCHES.
  
 5) PROVIDE ELEVATION DETAILING THE HEIGHT, AND DIAMETER
 OF THE PROPOSED POLE. THE POLE COLOR AT THIS LOCATION
 SHALL BE RAL/RAYCAP 7042 TRAFFIC GREY A OR EQUIVALENT.
 THIS SHALL BE SPECIFICALLY STATED ON THE PLANS.
  
 6) A UTILITY POWER PLAN THAT SHOWS HOW THE UNDERGROUND
 POWER IS BEING PROVIDED TO THE POLE, INCLUDING THE
 POWER SOURCE, WAS NOT INCLUDED. THE UNDERGROUND POWER
 PATH, INCLUDING ANY BORE PITS AND HANDHOLES ARE
 REQUIRED TO BE SHOWN ON THE WIRELESS COMMUNICATION
 FACILITY ROW PERMIT APPLICATION.
  
 7) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC
 BORE FOR THE FULL LENGTH OF THE INSTALLATION. THE
 UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE
 UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER,
 SANITARY, ELECTRIC, AND CABLE) AND ANY TREE ROOT
 SYSTEMS.
  
  
 REVIEWED BY:
 GAISHA (ANNE) VOLCY
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By avolcy Date 2023-05-25 Time 08:50 Rev Time 0.00
Received By avolcy Date 2023-05-25 Time 08:50 Sent To  
Notes
2023-05-25 08:51:11INSUFFICIENT 05.23.2023
  
 1) ACACIA ROAD AND CURRIE CRESCENT AT THE LOCATION OF
 THE PROPOSED POLE IS CURRENTLY UNDER RECONSTRUCTION/HAS
 RECENTLY BEEN RECONSTRUCTED WHICH MAY REQUIRE THAT THE
 POLE AND UNDERGROUND ELECTRIC TO THE POLE BE RELOCATED.
 THE WORK INCLUDES BOTH ABOVE AND BELOW GROUND
 INFRASTRUCTURE, TO INCLUDE THE REMOVAL OF SOME OF THE
 UTILITY POLES. PLEASE CONTACT LINDA QUINONES, SENIOR
 ENGINEERING PROJECT COORDINATOR, AT 561-494-1085 FOR A
 COPY OF THE LATEST PLANS. THE ENGINEERING PLANS AND
 SURVEY NEED TO BE UPDATED ACCORDINGLY TO SHOW ACCURATE
 PLANS BASED ON THE RECONSTRUCTION OF THE ACACIA ROAD
 AND CURRIE CRESCENT RIGHTS-OF-WAY.
  
 2) BASED ON THE FINAL RECONSTRUCTION PLANS, THE POLE
 WILL NEED TO BE LOCATED TO ALIGN WITH THE EXISTING AND
 PROPOSED TREES AND POLES IN THE RIGHT-OF-WAY.
  
 3) ALL UNDERGROUND UTILITIES AND FEATURES NEED TO BE
 PROVIDED ON THE SURVEY. THE PROVIDED SURVEY
 SPECIFICALLY STATES THAT NO UNDERGROUND UTILITY LOCATES
 WERE DONE, WHICH DOES NOT COMPLY WITH THE CITY CODE
 REQUIREMENTS.
  
 4) THE CROSS SECTION SHOWS THAT THERE IS A CLEAR ZONE
 OF 2.5 FEET, WHICH DOES NOT COMPLY WITH THE ADA MINIMUM
 REQUIREMENT OF 36 INCHES.
  
 5) PROVIDE ELEVATION DETAILING THE HEIGHT, AND DIAMETER
 OF THE PROPOSED POLE. THE POLE COLOR AT THIS LOCATION
 SHALL BE RAL/RAYCAP 7042 TRAFFIC GREY A OR EQUIVALENT.
 THIS SHALL BE SPECIFICALLY STATED ON THE PLANS.
  
 6) A UTILITY POWER PLAN THAT SHOWS HOW THE UNDERGROUND
 POWER IS BEING PROVIDED TO THE POLE, INCLUDING THE
 POWER SOURCE, WAS NOT INCLUDED. THE UNDERGROUND POWER
 PATH, INCLUDING ANY BORE PITS AND HANDHOLES ARE
 REQUIRED TO BE SHOWN ON THE WIRELESS COMMUNICATION
 FACILITY ROW PERMIT APPLICATION.
  
 7) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC
 BORE FOR THE FULL LENGTH OF THE INSTALLATION. THE
 UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE
 UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER,
 SANITARY, ELECTRIC, AND CABLE) AND ANY TREE ROOT
 SYSTEMS.
  
  
 REVIEWED BY:
 GAISHA (ANNE) VOLCY
 [email protected]