Plan Review Stops For Permit 23041231 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-07-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-06 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-06 |
Time |
10:45 |
Sent To |
|
|
Notes |
2023-07-06 10:46:15 | GUARD RAILS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-28 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-28 |
Time |
09:15 |
Sent To |
|
|
Notes |
2023-06-28 09:16:15 | GUARD RAILS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
14:04 |
Sent To |
|
|
Notes |
2023-06-08 14:06:59 | GUARD RAILS | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
amcgrego |
Date |
2023-07-05 |
Time |
09:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-29 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-29 |
Time |
08:09 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-06-27 |
Time |
08:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-06-16 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-06-16 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-05-18 |
Time |
12:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
F |
Date |
2023-07-06 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-06 |
Time |
10:46 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-06 |
Time |
10:46 |
Sent To |
|
|
Notes |
2023-07-06 10:51:09 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-28 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-28 |
Time |
09:16 |
Sent To |
|
|
Notes |
2023-06-28 09:16:44 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
14:07 |
Sent To |
|
|
Notes |
2023-06-08 14:07:51 | SIGNATURE REVIEW | | | | CORRECTIONS NEEDED - | | | | 1) GUARD RAIL DETAIL DRAWING SD2.0 NEEDS TO BE SIGNED | | BY THE ENGINEER (ALAYM AGUILAR P.E.) - SIGNED AND | | SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2023-06-28 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-06-28 |
Time |
16:44 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2023-06-28 |
Time |
16:44 |
Sent To |
|
|
Notes |
2023-06-28 16:50:03 | FAILED | | | | 1) THE GUARDRAIL SPEC PAGES SHOW A TWO-FOOT HIGH CHAIN | | LINK FENCE AND AN FDOT GUARDRAIL. THE SITE PLAN ONLY | | MENTIONS THE FDOT GUARDRAIL. WHERE IS THE CHAIN LINK | | FENCE PROPOSED? | | | | 2) CHAIN LINK FENCES SHALL BE VYNAL COATED. THE PLANS | | SHALL CALL THIS OUT. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2023-06-15 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-06-15 |
Time |
17:00 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2023-06-15 |
Time |
17:00 |
Sent To |
|
|
Notes |
|
|