Plan Review Details - Permit 23041113
Plan Review Stops For Permit 23041113
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-18 Cont ID  
Sent By lbond Date 2023-05-18 Time 09:14 Rev Time 0.00
Received By lbond Date 2023-05-18 Time 09:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-09 Cont ID  
Sent By lbond Date 2023-05-09 Time 10:46 Rev Time 0.00
Received By lbond Date 2023-05-09 Time 10:46 Sent To  
Notes
2023-05-09 10:54:31BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23041113
  
 REVIEWED: MAY 9 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
  
 SECTION 107.2.1 WPB
 PROVIDE FLOOR FINISH PLAN AND UNDERLAYMENT PER ROOM
 WITH CORRESPONDING SPECS TAKING INTO CONSIDERATION FIRE
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-17 Cont ID  
Sent By pleduc Date 2023-05-17 Time   Rev Time 0.00
Received By pleduc Date 2023-05-17 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-25 Cont ID  
Sent By pleduc Date 2023-04-25 Time   Rev Time 0.00
Received By pleduc Date 2023-04-25 Time 11:53 Sent To  
Notes
2023-04-25 11:57:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET NOR A PRODUCT
 NAME FOR THE ACTUAL PROPOSED WALNUT FLOORING.
  
 WALNUT FLOORING MAY BE MANUFACTURED AROUND THE WORLD
 BUT NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE WALNUT
 FLOORING NAME AND THE PRODUCT SPEC SHEETS INDICATING
 THE FIRE BEHAVIOR RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
  
 2) THERE IS NO FLOOR PLAN SUBMITTED SHOWING THE
 LOCATIONS OF THE PROPOSED FLOORING.
  
 PER NFPA 1
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOOR PLAN.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-18 Cont ID  
Sent By lbond Date 2023-05-18 Time 09:14 Rev Time 0.00
Received By lbond Date 2023-05-16 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-09 Cont ID  
Sent By lbond Date 2023-05-09 Time 10:54 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 06:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-18 Cont ID  
Sent By lbond Date 2023-05-18 Time 09:14 Rev Time 0.00
Received By lbond Date 2023-05-18 Time 09:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-05-09 Cont ID  
Sent By lbond Date 2023-05-09 Time 10:50 Rev Time 0.00
Received By lbond Date 2023-05-09 Time 10:50 Sent To  
Notes
2023-05-09 10:52:40SIGNATURE REVIEW: FAILED
 W.P.B. PERMIT: 23041113
  
 REVIEWED: MAY 5 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 1)THE PLANS SHALL BEAR THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE REMODEL.
 SECTION 107.2.1 WPB
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  