Plan Review Details - Permit 23041017
Plan Review Stops For Permit 23041017
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-05-25 Cont ID  
Sent By lbond Date 2023-04-24 Time 16:22 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-05-25 Cont ID  
Sent By lbond Date 2023-05-25 Time 10:44 Rev Time 0.00
Received By lbond Date 2023-05-25 Time 10:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 16:24 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 16:24 Sent To  
Notes
2023-04-24 16:33:24BUILDING PLAN REVIEW STATUS: FAILED
  
 FLOORING SUBMITTAL
  
  
 ITEMS TO PROVIDE:
 1. FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE
 OF FLOORING FOR EACH AREA.
  
 PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL - [email protected]
 IF THE UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR
 WHICH WE HAVE TEST REPORTS ON FILE, THE FOLLOWING
 REPORTS ARE REQUIRED:
  
 2. [FBC 1207.2]AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90.
  
 3. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES
 BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A
 DWELLING
 UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS
 RATING OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 WHEN TESTED
 IN ACCORDANCE WITH ASTM E492.
  
 4. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT US:
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-05-09 Cont ID  
Sent By jleahy Date 2023-05-09 Time 15:12 Rev Time 0.00
Received By jleahy Date 2023-05-09 Time 15:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-05-24 Cont ID  
Sent By pleduc Date 2023-05-24 Time   Rev Time 0.00
Received By pleduc Date 2023-05-24 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-27 Cont ID  
Sent By pleduc Date 2023-04-27 Time   Rev Time 0.00
Received By pleduc Date 2023-04-27 Time 13:48 Sent To  
Notes
2023-04-27 13:55:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE SUBMITTED PLAN:
 "INSTALL NEW LUXURY VINYL PLANK(LVP) THROUGHOUT",
 HOWEVER, THERE IS NO INDICATION OF THE ACTUAL FLOOR
 PRODUCT NOR NAME.
  
 LVT FLOORING CAN BE MANUFACTURED AROUND THE WORLD AND
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING
 PRODUCT NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
 IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE,
 NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS
 WOULD NOT BE REQUIRED.
  
 PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL
 FLOORING, WOOD/VINYL LAMINATES, ETC.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-25 Cont ID  
Sent By lbond Date 2023-05-25 Time 10:44 Rev Time 0.00
Received By lbond Date 2023-05-23 Time 13:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-09 Cont ID  
Sent By jleahy Date 2023-05-09 Time 15:13 Rev Time 0.00
Received By jleahy Date 2023-04-21 Time 12:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2023-04-26 Cont ID  
Sent By ccole Date 2023-04-26 Time 17:02 Rev Time 0.00
Received By ccole Date 2023-04-26 Time 17:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 16:22 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 16:21 Sent To  
Notes
***NONE***