Plan Review Details - Permit 23040933
Plan Review Stops For Permit 23040933
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-06-21 Cont ID  
Sent By pvalenti Date 2023-06-21 Time 16:05 Rev Time 0.00
Received By pvalenti Date 2023-06-21 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-06-14 Cont ID  
Sent By rmcphers Date 2023-06-14 Time 14:09 Rev Time 0.00
Received By rmcphers Date 2023-06-14 Time 14:09 Sent To  
Notes
2023-06-14 14:20:01ROOFING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE ENGINEERING FROM SANDRA PUERTA AR - NEEDS TO
 SHOW THE ATTACHMENT FOR ROOF WIND ZONE -1', 1, 2 AND 3
 (ALL 4 WIND ZONES).
  
 THE WIND PRESSURES FROM THE COUNTY SHOW 4 WIND ZONES -
 1',1, 2, 3
  
 THERE ARE 4 NEW ROOF ZONES. SEE FIGURE
 R301.2(7)FBC-RESIDENTIAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-06-05 Cont ID  
Sent By jgomez Date 2023-06-05 Time 15:49 Rev Time 0.00
Received By jgomez Date 2023-06-05 Time 15:32 Sent To  
Notes
2023-06-05 15:49:29RESIDENTIAL REROOF SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040933
 523 HAMPTON RD
  
 1- MISSING FLAT ROOF PRODUCT APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR FLAT ROOF AS REQUIRED BY FAC 61G20-3.001
 AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. NOTE: IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
 NOTE: NAIL ENHANCEMENT CALCULATIONS SUBMITTED ARE USING
 THE OLD CODE. DESIGN PROFESSIONAL NEEDS TO USE THE
 CURRENT 2020 CODE AND NEED TO SPECIFY THE DIMENSIONS
 FOR EACH ROOF ZONE AS REQUIRED BY FIGURE
 R301.2(7)FBC-RESIDENTIAL.
  
 RESPONSE:
 FLAT ROOF NOA 18-0919.12 WAS SUBMITTED BUT THE RAS 117
 NAIL ENHANCEMENT CALCULATIONS WERE NOT REVISED. DESIGN
 PROFESSIONAL NEEDS TO USE THE CURRENT 2020 CODE AND
 NEED TO SPECIFY THE DIMENSIONS FOR EACH NEW ROOF ZONE
 AS REQUIRED BY FIGURE R301.2(7)FBC-RESIDENTIAL. PROVIDE
 ROOF SKETCH SHOWING THE DIMENSIONS FOR EACH NEW ROOF
 ZONE..
 NOTE: THERE ARE 4 NEW ROOF ZONES. SEE FIGURE
 R301.2(7)FBC-RESIDENTIAL. ALSO, REVISE CALCULATIONS TO
 INCLUDE THE DESIGN PRESSURES FOR EACH ROOF ZONE.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 13:04 Rev Time 0.00
Received By jgomez Date 2023-05-25 Time 11:22 Sent To  
Notes
2023-05-25 13:04:58RESIDENTIAL REROOF BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23040933
 523 HAMPTON RD
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- MISSING FLAT ROOF PRODUCT APPROVAL. PROVIDE PRODUCT
 APPROVAL FOR FLAT ROOF AS REQUIRED BY FAC 61G20-3.001
 AND CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. NOTE: IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED.
 NOTE: NAIL ENHANCEMENT CALCULATIONS SUBMITTED ARE USING
 THE OLD CODE. DESIGN PROFESSIONAL NEEDS TO USE THE
 CURRENT 2020 CODE AND NEED TO SPECIFY THE DIMENSIONS
 FOR EACH ROOF ZONE AS REQUIRED BY FIGURE
 R301.2(7)FBC-RESIDENTIAL.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-21 Cont ID  
Sent By pvalenti Date 2023-06-21 Time 16:06 Rev Time 0.00
Received By pvalenti Date 2023-06-20 Time 08:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-06-14 Cont ID  
Sent By rmcphers Date 2023-06-14 Time 14:20 Rev Time 0.00
Received By rmcphers Date 2023-06-13 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-05 Cont ID  
Sent By jgomez Date 2023-06-05 Time 15:49 Rev Time 0.00
Received By jgomez Date 2023-06-02 Time 10:29 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-25 Cont ID  
Sent By jgomez Date 2023-05-25 Time 13:05 Rev Time 0.00
Received By jgomez Date 2023-05-23 Time 09:32 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-06-21 Cont ID  
Sent By pvalenti Date 2023-06-21 Time 16:05 Rev Time 0.00
Received By pvalenti Date 2023-06-21 Time 16:05 Sent To  
Notes
***NONE***