Plan Review Details - Permit 23040880
Plan Review Stops For Permit 23040880
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-04-27 Cont ID  
Sent By cpuell Date 2023-04-27 Time 08:04 Rev Time 0.00
Received By cpuell Date 2023-04-27 Time 08:04 Sent To  
Notes
2023-04-27 08:05:09ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By pvalenti Date 2023-04-20 Time 16:01 Rev Time 0.00
Received By pvalenti Date 2023-04-20 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By pvalenti Date 2023-06-27 Time 09:51 Rev Time 0.00
Received By pvalenti Date 2023-06-27 Time 09:51 Sent To  
Notes
2023-06-27 09:55:55PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED AS ELECTRICAL CONTRACTOR WILL
 BE ON-SITE AND THE DEMO REQUIREMENTS WILL BE APPROVED
 THROUGH MASTER PERMIT #22111270.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By pvalenti Date 2023-04-20 Time 16:38 Rev Time 0.00
Received By pvalenti Date 2023-04-20 Time 15:57 Sent To  
Notes
2023-04-20 16:45:11PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC)
 RELEASE OF SERVICE CONFIRMATION
 OR PROVIDE ELECTRICAL PERMIT WITH CONFIRMATION FROM
 ELECTRICAL CONTRACTOR STATING THAT THE ELECTRICAL
 SUPPLY HAS BEEN SAFELY DISCONNECTED.
 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS)
 RELEASE OF SERVICE CONFIRMATION
 3. WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART
 MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-06-27 Cont ID  
Sent By jleahy Date 2023-06-27 Time 11:04 Rev Time 0.00
Received By jleahy Date 2023-06-27 Time 11:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-20 Cont ID  
Sent By rperdomo Date 2023-04-20 Time 09:07 Rev Time 0.00
Received By rperdomo Date 2023-04-20 Time 08:18 Sent To  
Notes
2023-04-20 09:06:38FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL
 PERMIT APPLICATION FOR APPROVAL. THIS IS A BUILDING
 DEPARTMENT POLICY TO ENSURE ELECTRICAL SAFETY DURING
 DEMOLITION.
  
 END OF COMMENTS
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER/ INSPECTOR
 561-805-6738
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By pleduc Date 2023-04-20 Time   Rev Time 0.00
Received By pleduc Date 2023-04-20 Time 10:59 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2023-04-28 Cont ID  
Sent By amhamilt Date 2023-04-28 Time 09:39 Rev Time 0.00
Received By amhamilt Date 2023-04-28 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-04 Cont ID  
Sent By aoliver Date 2023-05-04 Time 08:12 Rev Time 0.00
Received By aoliver Date 2023-04-19 Time 10:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-20 Cont ID  
Sent By pvalenti Date 2023-04-20 Time 16:21 Rev Time 0.00
Received By pvalenti Date 2023-04-20 Time 15:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2023-05-03 Cont ID  
Sent By CKimmerl Date 2023-05-03 Time 10:14 Rev Time 0.00
Received By ckimmerl Date 2023-05-03 Time 10:14 Sent To  
Notes
***NONE***