Plan Review Stops For Permit 23040838 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-31 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-31 |
Time |
14:07 |
Sent To |
|
|
Notes |
2023-05-31 14:08:29 | BUILDINGS READDRESSES, THE APPROPRIATE BUILDING TO BE | | DEMOLISHED IS NOW SHOWN ON THE SURVEY |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-05-04 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-04 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-04 |
Time |
10:08 |
Sent To |
|
|
Notes |
2023-05-04 11:38:36 | THE BUILDING THAT IS BEING DESCRIBED AS A SHED, IS A | | HABITABLE BUILDING NOT A SHED, THERE IS A SHED ON THE | | NORTH EAST CORNER OF THE PROPERTY BUT THAT IS NOT THE | | BUILDING IDENTIFIED IN THE SURVEY. THE EAST AND WEST | | BUILDINGS SHOULD HAVE THEIR OWN UNIQUE ADDRESS. PLEASE | | HAVE OWNER CONTACT [email protected] OR CALL | | 561-805-6659 TO DISCUSS ADDRESSING ISSUES. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
3 |
Status |
P |
Date |
2023-07-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-03 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-03 |
Time |
07:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
2 |
Status |
F |
Date |
2023-06-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-06-05 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-06-05 |
Time |
13:54 |
Sent To |
|
|
Notes |
2023-06-05 14:03:38 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW DENIED: | | | | PLEASE SIGN THE LETTER THAT WAS SUBMITTED AND THEN | | RE-SUBMIT. |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
F |
Date |
2023-05-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-04 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-04 |
Time |
06:37 |
Sent To |
|
|
Notes |
2023-05-04 06:44:01 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | ASBESTOS REVIEW DENIED: | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC | | ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION | | -RENOVATION.HTML | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-18 |
Time |
06:34 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-18 |
Time |
06:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-07-03 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-03 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-03 |
Time |
07:09 |
Sent To |
|
|
Notes |
2023-07-03 07:25:23 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | 2ND BUILDING REVIEW DENIED: | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | DEPARTMENT, REQUEST FOR METER PULL, ON | | THEIR FORM "DEMOLITION APPLICATION" | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-06-05 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-06-05 |
Time |
14:04 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-06-05 |
Time |
13:54 |
Sent To |
|
|
Notes |
2023-06-05 14:07:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | 2ND BUILDING REVIEW DENIED: | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | NOTE: ALL ITEMS ON THIS LIST MAY NOT APPLY TO THIS | | DEMOLITION PERMIT APPLICATION. PLEASE PROVIDE A | | RESPONSE SHEET WITH A RESPONSE PER EACH ITEM INCLUDING | | AN EXPLANATION AS TO WHY ANY OF THE ITEMS MAY NOT | | APPLY. | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) | | RELEASE OF SERVICE CONFIRMATION | | | | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) | | RELEASE OF SERVICE CONFIRMATION | | | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | DEPARTMENT, REQUEST FOR METER PULL, ON | | THEIR FORM "DEMOLITION APPLICATION" | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. | | | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703. | | | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-04 |
Time |
06:44 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-04 |
Time |
06:36 |
Sent To |
|
|
Notes |
2023-05-04 06:46:33 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A | | DEMO PERMIT PER FLORIDA BUILDING | | CODE, BUILDING 3303: | | | | NOTE: ALL ITEMS ON THIS LIST MAY NOT APPLY TO THIS | | DEMOLITION PERMIT APPLICATION. PLEASE PROVIDE A | | RESPONSE SHEET WITH A RESPONSE PER EACH ITEM INCLUDING | | AN EXPLANATION AS TO WHY ANY OF THE ITEMS MAY NOT | | APPLY. | | | | 1. UTILITY RELEASE - FLORIDA POWER & LIGHT (ELECTRIC) | | RELEASE OF SERVICE CONFIRMATION | | 2. UTILITY RELEASE - FLORIDA PUBLIC UTILITIES (GAS) | | RELEASE OF SERVICE CONFIRMATION | | 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER | | DEPARTMENT, REQUEST FOR METER PULL, ON | | THEIR FORM "DEMOLITION APPLICATION" | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | WATERDOWN METHOD: | | IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED | | INFPRMATION OF THE WATER TRUCK SUCH AS: THE | | GALLON CAPACITY OF THE WATER TANK AND A LETTER | | INCLUDING A STATEMENT THAT THE WATER | | USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY | | AND WILL BE ON-SITE AT ALL TIMES | | DURING DEMOLITION. | | IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, | | THEN A PARTIAL RELEASE WILL BE NOTED | | ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS | | SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE | | SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE | | BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY | | THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE | | COMPLETED "DEMOLITION APPLICATION" FORM TO | | 561-822-2183. | | 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT | | APPLICATION TO BUILDING DIVISION); | | SCHEDULE A FINAL PLUMBING #703. | | 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST | | CONTROL COMPANY STATING THAT | | DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED | | FOR RODENTS. | | 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART | | MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS | | IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR | | THE FORM TO [email protected]. | | 7. PROVIDE A SITE PLAN OR SURVEY SHOWING LOCATION OF | | THE STRUCTURE(S) TO BE DEMOLISHED, | | FBC 107. | | 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN. | | 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | RENOVATION.HTML |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-05-31 |
Time |
20:01 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-05-31 |
Time |
20:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2023-05-08 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-05-08 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-05-08 |
Time |
11:02 |
Sent To |
|
|
Notes |
2023-05-08 11:02:46 | PLEASE PROVIDE STORMWATER POLLUTION PREVENTION PLAN | | SHOWN ON COPY OF PROPERTY SURVEY - SILT FENCE AROUND | | PROPERTY TO PREVENT DEBRIS RUNOFF; PROTECT ROADWAY FROM | | TRACKING OF DIRT FROM TRUCKS HAULING DEBRIS; PROTECT | | ANY STORM DRAIN INLETS IN VICINITY USING BEST | | MANAGEMENT PRACTICES (FILTER FABRIC, ETC.) | | | | THERE ARE WATER AND SEWER LINES IN THE VICINITY OF THIS | | PROJECT. PER CHAPTER 556 OF THE FLORIDA STATE STATUTES, | | YOU MUST CALL 811 FOR UTILITY LOCATES AT LEAST TWO FULL | | BUSINESS DAYS IN ADVANCE OF ANY CONSTRUCTION OR | | DEMOLITION WORK. INFORMATION CAN BE FOUND HERE: | | HTTP://WWW.SUNSHINE811.COM/ | | | | PROVIDE ALL REQUIRED ASSOCIATED DOCUMENTS AS REQUIRED | | BY BUILDING DEPT. - STORMWATER POLLUTION PREVENTION | | PLAN, AND UTILITY SIGNOFFS - WATER/SEWER, PEST, FPL, | | FPU, ASBESTOS ETC. | | | | TO RESUBMIT, YOU MUST FIRST WAIT TILL ALL THE PLAN | | REVIEWS ARE COMPLETE. EVEN IF YOU FAILED ONE TRADE AND | | WANT TO ADDRESS THE COMMENTS IMMEDIATELY, YOU MUST WAIT | | FOR ALL OTHER TRADES TO REVIEW YOUR PLAN. RESUBMITTING | | BEFORE PLAN REVIEW IS COMPLETE WILL DELAY YOUR PLAN | | REVIEW TIME. | | | | ONCE ALL PLAN REVIEWS ARE COMPLETE, IF YOU DONT | | UNDERSTAND THE FAILED PLAN REVIEW COMMENTS, AS A BEST | | PRACTICE YOU SHOULD CALL OR EMAIL YOUR PLAN REVIEWER TO | | DISCUSS. EVERY PLAN REVIEWER INCLUDES THEIR NAME, PHONE | | AND EMAIL ADDRESS IN THE COMMENTS. TO VIEW YOUR PLAN | | REVIEW COMMENTS ONLINE, GO TO THE DEVELOPMENT SERVICES | | WEBSITE AT HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-S | | ERVICES/PERMITS AND SEE WHERE CAN I FIND MY PLAN REVIEW | | COMMENTS ONLINE? FOR INSTRUCTIONS. | | | | FOR QUESTIONS ABOUT HOW TO RESUBMIT, SEE INFO ON | | WEBSITE OR EMAIL [email protected] AND A BUILDING DIVISION | | TEAM MEMBER WILL HELP YOU. | | | | THANKS, | | LINDA M. QUINONES-CINTRON, PROJECT COORDINATOR, | | ENGINEERING SERVICES DEPARTMENT (561) 494-1085 | | [email protected] | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
2 |
Status |
P |
Date |
2023-06-22 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-06-22 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-06-22 |
Time |
09:27 |
Sent To |
|
|
Notes |
2023-06-22 09:28:13 | PASSED, DEMOLITION PERMITTED *ONLY* OF NON-HISTORIC | | SHED STRUCTURE. | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | [email protected] | | 561.822.1428 | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
F |
Date |
2023-05-24 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-05-24 |
Time |
09:02 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-05-24 |
Time |
09:02 |
Sent To |
|
|
Notes |
2023-05-24 09:02:53 | **FAILED SO APPLICANT CAN RESUBMIT** |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-07-18 |
Time |
06:34 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-07-13 |
Time |
16:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-07-05 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-07-05 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-06-30 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-23 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-06-23 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-05-26 |
Time |
15:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-05-25 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-05-03 |
Time |
13:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2023-05-04 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-04 |
Time |
06:41 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-04 |
Time |
06:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-06-22 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-06-22 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-06-22 |
Time |
09:28 |
Sent To |
|
|
Notes |
2023-06-22 09:28:36 | PASSED, DEMOLITION PERMITTED *ONLY* OF NON-HISTORIC | | SHED STRUCTURE. | | | | ANNE HAMILTON | | HISTORIC PRESERVATION PLANNER | | [email protected] | | 561.822.1428 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-05-24 |
|
|
Cont ID |
|
Sent By |
amhamilt |
Date |
2023-05-24 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
amhamilt |
Date |
2023-05-24 |
Time |
09:02 |
Sent To |
|
|
Notes |
2023-05-24 09:03:25 | **FAILED SO APPLICANT CAN RESUBMIT** |
|
|