Plan Review Stops For Permit 23040751 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-25 |
Time |
07:54 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-25 |
Time |
06:34 |
Sent To |
|
|
Notes |
2023-05-25 08:37:28 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | 1.) FBC B 107.2.1, PLEASE INDICATE, ON-PLAN, THE | | LOCATION OF WINDOWS/DOORS TO BE INSTALLED. INCLUDE THE | | TYPE AND SIZE OF WINDOWS/DOORS TO BE INSTALLED ON THE | | PLAN. ALSO, THE ONLY NOA/PRODUCT APPROVAL SUBMITTED WAS | | FOR THE FIXED WINDOWS (22-0105.01). ARE THERE OTHER | | TYPES OF WINDOWS/DOORS THAT ARE TO BE INSTALLED? | | | | 2.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL FOR THE | | ROOF SHINGLES. | | | | 3.) FBC R 905.1.1.1, CLARIFY THE ROOFING UNDERLAYMENT | | SYSTEM TO BE USED BY INDICATING THE OPTION (2 PLIES OF | | 30# FELT OR OTHER OPTION PER FBC R 905.1.1.1) IN | | ADDITION TO THE NOTE ON DETAIL 10 FROM PLAN SHEET A-3 | | THAT INDICATES 30# FELT. | | | | 4.) FBC B 107.2.1, PLEASE OBTAIN A ROOFING SUB-PERMIT. | | | | 5.) FBC EB R502.1, PROVIDE THE ENERGY CALCULATIONS PER | | THE REQUIREMENTS OF THE FLORIDA EXISTING BUILDING CODE. | | | | 6.) FBC B 107.2.1, PLEASE CLARIFY THE DIMENSIONS | | REQUIRED FOR THE F-1 FOOTINGS. THE FOOTING SCHEDULE ON | | PLAN SHEET A-4 INDICATES THE F-1 FOOTING DEPTH AT 5", | | THE DETAIL 1/A-4 INDICATES THE DEPTH TO BE 12" BELOW | | 4"SLAB. PLEASE CLARIFY THE REQUIRED DEPTH AND CORRECT | | DETAILS TO MATCH. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-04-17 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-04-17 |
Time |
15:36 |
Sent To |
|
|
Notes |
2023-04-17 16:23:06 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PROVIDE MORE INFORMATION. PLEASE CLARIFY | | THE COMPLETE SCOPE OF WORK FOR THIS PROJECT AS IT | | APPEARS THAT NEW PLAN SHEETS WILL NEED TO INCLUDE THE | | FOLLOWING: | | | | FLOOR PLAN SHOWING THE EXISTING AREA OF CONSTRUCTION | | AND THE PROPOSED CONSTRUCTION AT THAT AREA INCLUDING | | NEW WINDOW/DOOR LOCATIONS, PLAN SHEETS SHOWING THE | | CONNECTION DETAILS FOR ALL OF THE PROPOSED NEW TRUSS TO | | THE EXISTING TRUSS AND EXISTING STRUCTURAL MEMBERS, | | PLAN SHEETS WITH DETAILS FOR NEW STRUCTURAL MEMBERS | | INCLUDING BEAMS/COLUMNS & WALLS, & LOCATION WITH | | DIMENSIONS OF NEW WINDOWS TO BE INSTALLED. | | | | THESE DETAILS AND CALCULATIONS ARE TYPICALLY PUT | | TOGETHER BY A DESIGN PROFESSIONAL AS THEY NEED TO SHOW | | THE LOAD CAPACITIES (INCLUDING UPLIFT CAPACITIES) AT | | THE CONNECTION POINTS. | | ALL SUBMITTALS BY A DESIGN PROFESSIONAL (ARCHITECT OR | | ENGINEER) WILL NEED TO BE SIGNED AND SEALED BY THAT | | DESIGN PROFESSIONAL. | | | | ALSO, FOR ENCLOSING AN EXISTING OPEN PATIO AND | | INCREASING WHAT IS CONSIDERED THE LIVING SPACE, ENERGY | | CALCULATIONS ARE REQUIRED MEANING THAT ELECTRICAL AND | | MECHANICAL PERMITS WILL BE NEEDED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-05-25 |
Time |
02:55 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-05-25 |
Time |
02:45 |
Sent To |
|
|
Notes |
2023-05-25 03:01:49 | ELECTRIC REVIEW FAILED | | | | 1)NO ELECTRICAL PLAN WAS SUBMITTED . ARCHITECT WAS MADE | | AWARE BY BUILDING PLAN REVIEWER THAT AN ELECTRICAL | | WOULD NEED TO BE SUBMITTED. ARCHITECHT ACKNOWLEDGED | | THIS AND STILL DID NOT SUBMITT APPROPRIATE DRAWINGS OR | | AN ELECTRIC SUB PERMIT APPLICATION. PLEASE SUBMIT | | APPROPRIATE PLANS AND APPLICATION. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-05 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-06-05 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2023-06-05 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-04-24 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-04-24 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-04-24 |
Time |
17:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-25 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-25 |
Time |
08:39 |
Sent To |
|
|
Notes |
2023-05-25 08:41:26 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-06-05 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-06-05 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2023-06-05 |
Time |
13:37 |
Sent To |
|
|
Notes |
2023-06-05 13:38:34 | NEED MECHANICAL PLANS PER FBC 107 | | C MONTELLO | | 561-805-6733 |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-05-25 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-05-25 |
Time |
06:34 |
Sent To |
|
|
Notes |
2023-05-25 09:04:43 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | SIGNATURE REVIEW APPROVED BY PAPER PLANS WITH ORIGINAL | | HAND SIGNATURES/SEALS BY ARCHITECT. |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
pvalenti |
Date |
2023-04-17 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
pvalenti |
Date |
2023-04-17 |
Time |
15:28 |
Sent To |
|
|
Notes |
2023-04-17 15:41:03 | PETER E VALENTI | | BUILDING PLANS EXAMINER II/INSPECTOR | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | SIGNATURE REVIEW APPROVED FOR THE PAPER SUBMITTED TRUSS | | ENGINEERING ONLY. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | RESULT IN NEW SIGNATURE PLAN REVIEW COMMENTS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-05-25 |
Time |
16:09 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-05-25 |
Time |
16:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
Sent By |
asangele |
Date |
2023-04-24 |
Time |
17:17 |
Rev Time |
0.00 |
Received By |
asangele |
Date |
2023-04-24 |
Time |
17:17 |
Sent To |
|
|
Notes |
2023-04-24 17:18:58 | FAILED | | 4/24/2023 | | | | | | PLEASE PROVIDE HEIGHT ELEVATION DRAWINGS AND A SITE | | PLANS OF THE ADDITION | | | | | | | | ALEXIS SANGELEER | | PLANNER | | [email protected] |
|
|