Plan Review Stops For Permit 23040251 |
Review Stop |
AD |
ADDRESSING |
Rev No |
3 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-03 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-03 |
Time |
14:17 |
Sent To |
|
|
Notes |
2023-05-03 14:18:47 | SPOKE WITH MIGUEL VERRATTI 407-529-6582 WHO THE CITY | | HAS BEEN WORKING WITH ON ALL THE ADDRESSES ON THIS | | SITE. TENANT SPACES HAVE YET TO BE ESTABLISHED, BUT | | WILL BE PROVIDED BEFORE THE CO. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-02 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-02 |
Time |
16:00 |
Sent To |
|
|
Notes |
2023-05-02 16:01:51 | PER THE RESPONCE TO COMMENTS, THE GC SHOULD BE UPDATING | | THE APPLICATION WITH THE CORRECT ADDRESS OF 2737 S | | DIXIE HWY. PLEASE HAVE OWNERS REPRESENTIVES CONTACT | | [email protected] OR CALL 561-805-6659 TO DISCUSS | | THE SUITE ADDRESS. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-04-10 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-04-10 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-04-10 |
Time |
11:19 |
Sent To |
|
|
Notes |
2023-04-10 11:21:35 | INCORRECT ADDRESS LISTED ON THE PLANS AND APPLICATION | | FORM, THE CORRECT ADDRESS FOR THE PRESS IS 2737 S DIXIE | | HWY, SUITE NUMBERS NEED TO BE ASSIGNED FOR THE THRID | | FLOOR, PLEASE PROVIDE A FLOOR PLAN SHOWING EVERY SUITE | | ON THAT FLOOR. PLEASE EMAIL TO [email protected] | | FOR FURTHER QUESTIONS YOU CAN ALSO CALL 561-805-6659 |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
P |
Date |
2023-04-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-04-11 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-04-11 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-05-09 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-05-09 |
Time |
13:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2023-04-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-04-12 |
Time |
08:23 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-04-11 |
Time |
15:06 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-05-15 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-05-15 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-05-15 |
Time |
14:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-04-17 |
Time |
13:59 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-04-17 |
Time |
13:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-03 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-03 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-04-10 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2023-04-10 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-04-10 10:26:23 | FIRE PROVISO COMMENTS: | | | | (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL | | PHASES OF DEMOLITION AND CONSTRUCTION. | | | | (2) ANY WORK PERFORMED ON LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) SHALL ONLY BE CONDUCTED BY | | PROPERLY LICENSED AND QUALIFIED CONTRACTORS UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | (3) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL BE PROTECTED FROM PHYSICAL | | DAMAGE, INCLUDING PAINTING, DURING ALL PHASES OF | | DEMOLITION AND CONSTRUCTION. | | | | (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | FIRE WATCH. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-05-16 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-05-16 |
Time |
08:19 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-05-02 |
Time |
09:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-04-19 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-04-07 |
Time |
14:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-05-09 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-05-09 |
Time |
08:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-04-19 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-04-19 |
Time |
10:41 |
Sent To |
|
|
Notes |
2023-04-19 10:42:14 | MECHANICAL DEMO ONLY. ME |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-05-03 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-05-03 |
Time |
15:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-04-11 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-04-11 |
Time |
06:06 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-04-11 |
Time |
06:06 |
Sent To |
|
|
Notes |
2023-04-11 06:08:13 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FPC 607.1.2/419.5 - PLEASE ADD A DETAIL AND | | SHOW COMPLIANCE FOR THE LIMITING DEVICE REQUIRED FOR | | PUBLIC HANDWASHING FACILITIES AND TEMPERED WATER. THE | | DEVICE SHOULD CONFORM TO ASSE 1070. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2023-05-09 |
Time |
14:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2023-05-09 |
Time |
14:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-04-19 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-04-19 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-04-19 |
Time |
10:45 |
Sent To |
|
|
Notes |
|
|