2023-06-01 14:57:54 | ROOF OVER BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #23040249 |
| 3114 45TH ST |
| |
| NOTE: |
| LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| THE FLORIDA BUILDING CODE. |
| |
| 1- PROVIDE ENGINEERING ANALYSIS SHOWING THAT EXISTING |
| STRUCTURE IS ADEQUATE TO RECEIVE THE ADDITIONAL ROOF |
| RUGGER RETROFIT FRAMING SYSTEM. |
| SEC. 706.2 FBC-EXISTING BUILDING. SEC. 107.2.1.2 CITY |
| AMENDMENTS. |
| |
| 2- ENGINEER OF RECORD FOR THE SITE SPECIFIC |
| INSTALLATION OF THE ROOF RUGGER RETROFIT FRAMING SYSTEM |
| TO REVISE PLANS AND CALCULATIONS. THE ULTIMATE WIND |
| SPEED ADOPTED BY THE CITY OF WEST PALM BEACH IS 170MPH |
| NOT 168 MPH. SEC. 120 CITY AMENDMENTS. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE HIGH AND LOW EAVE TRIMS SHOWN ON |
| PLANS. SPECIFY ALL FASTENERS. SEC. 1609.1 FBC-BUILDING. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR NEW ROOF PANELS. |
| NOTE: CLEARLY IDENTIFY PANEL FASTENING FOR ALL ROOF |
| ZONES. |
| |
| 5- ENGINEER OF RECORD FOR THE SITE SPECIFIC |
| INSTALLATION OF THE ROOF RUGGER RETROFIT FRAMING SYSTEM |
| TO REVIEW AND APPROVE IN WRITING (NOT SIGNING AND |
| SEALING) ABOVE PRODUCT APPROVAL AS REQUIRED BY SEC. |
| 107.3.4.1 CITY AMENDMENTS. |
| NOTE: CLEARLY IDENTIFY PANEL FASTENING FOR AL ROOF |
| ZONES. |
| |
| 6- DRAWINGS S1, S2 AND S3 AND CORRESPONDING |
| CALCUALTIONS: |
| ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE |
| REQUIREMENTS OF FBPE. . THE TEXT BOX LANGUAGE MUST BE |
| IDENTICAL TO THE SAMPLES PUBLISHED BY FBPE. SEE FBPE.OR |
| G/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCUMENTS/... |
| AND REVISE AS REQUIRED. |
| |
| SEC. 61G15-23.004 F.A.C. . PROCEDURES FOR DIGITALLY |
| SIGNING AND SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |