2023-04-04 07:50:35 | 1ST PLUMBING REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE SPEC SHEET |
| FOR THE BACKFLOW DEVICE TO BE INSTALLED. IT NEEDS TO |
| INDICATE IT IS LEAD FREE AND USC APPROVED. BE SURE TO |
| HIGHLIGHT THE MAKE, MODEL, AND SIZE OF THE DEVICE. |
| |
| 2. 2017 WPB AMEND - 107.3.5 -THE SITE PLAN IS |
| UNREADABLE. |
| |
| 3. 2017 WPB AMEND 105.1 - THE TEST REPORT TO CERTIFY A |
| BACKFLOW IS NOT REQUIRED FOR PLAN REVIEW. THE BACKFLOW |
| CANNOT BE TESTED BEFORE THE PERMIT IS ISSUED. A PERMIT |
| IS REQUIRED TO INSTALL THE BACKFLOW. IF AN EMERGENCY |
| REPAIR IS NEEDED, PER 105.2.1 YOU CAN CONTACT THE |
| BUILDING DEPARTMENT AT [email protected] AND COPY ME AT |
| [email protected] AND NOTIFY US OF THE EMERGENCY REPAIR |
| BEFORE THE WORK BEGINS. THEN, WITHIN 24 HOURS OR ONE |
| BUSINESS DAY, YOU NEED TO SUBMIT THE APPLICATION FOR |
| THE WORK PERFORMED. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |