Plan Review Details - Permit 23031888
Plan Review Stops For Permit 23031888
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-04 Cont ID  
Sent By jleahy Date 2023-05-04 Time 11:34 Rev Time 0.00
Received By jleahy Date 2023-05-04 Time 11:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By jleahy Date 2023-04-10 Time 10:46 Rev Time 0.00
Received By jleahy Date 2023-04-06 Time 18:05 Sent To  
Notes
2023-04-10 10:48:36FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN.CITY OF WPB
 AMENDMENT 107.2.1, FS 471, 481
  
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM ???LEGAL??? OR ITS
 EQUIVALENT BE USED A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-04-26 Cont ID  
Sent By pleduc Date 2023-04-26 Time   Rev Time 0.00
Received By pleduc Date 2023-04-26 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-13 Cont ID  
Sent By pleduc Date 2023-04-13 Time   Rev Time 0.00
Received By pleduc Date 2023-04-13 Time 10:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-04-03 Cont ID  
Sent By pleduc Date 2023-04-03 Time   Rev Time 0.00
Received By pleduc Date 2023-04-03 Time 12:32 Sent To  
Notes
2023-04-03 12:39:40FIRE PROVISO:
  
 ALL ACCESS CONTROL SHALL COMPLY WITH REQUIREMENTS OF
 NFPA 101, CH 7, MEANS OF EGRESS.
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
  
 7.2.1.6* SPECIAL LOCKING ARRANGEMENTS.
 7.2.1.6.1 DELAYED-EGRESS ELECTRICAL LOCKING SYSTEMS.
 7.2.1.6.1.1 APPROVED, DELAYED-EGRESS ELECTRICAL LOCKING
 SYSTEMS SHALL
 BE PERMITTED TO BE INSTALLED ON DOOR ASSEMBLIES SERVING
 LOW- AND
 ORDINARY-
 HAZARD CONTENTS IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.6 OR AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 9.7, AND WHERE PERMITTED IN
 CHAPTERS 11
 THROUGH 43, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE DELAY OF THE DELAYED-EGRESS ELECTRICAL LOCKING
 SYSTEM SHALL
 DEACTIVATE ALLOWING UNOBSTRUCTED EGRESS UPON ACTUATION
 OF ONE OF
 THE FOLLOWING:
 (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7
 (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED,
 SUPERVISED
 AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH
 SECTION 9.6
 (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED,
 SUPERVISED
 AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE WITH
 SECTION 9.6
 (2) THE DELAY OF THE DELAYED-EGRESS ELECTRICAL LOCKING
 SYSTEM SHALL
 DEACTIVATE ALLOWING UNOBSTRUCTED EGRESS UPON LOSS OF
 POWER CONTROLLING
 THE LOCK OR LOCKING MECHANISM.
 (3)* AN IRREVERSIBLE PROCESS SHALL RELEASE THE
 ELECTRICAL LOCK IN THE
 DIRECTION OF EGRESS WITHIN 15 SECONDS, OR 30 SECONDS
 WHERE
 APPROVED BY THE AUTHORITY HAVING JURISDICTION, UPON
 APPLICATION OF
 A FORCE TO THE RELEASE DEVICE REQUIRED IN 7.2.1.5.10
 UNDER ALL OF THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR
 MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE
 SIGNAL IN THE VICINITY OF THE DOOR OPENING.
 (D) ONCE THE ELECTRICAL LOCK HAS BEEN RELEASED BY THE
 APPLICATION
 OF FORCE TO THE RELEASING DEVICE, REARMING THE DELAY
 ELECTRONICS
 SHALL BE BY MANUAL MEANS ONLY.
 (4)* A READILY VISIBLE, DURABLE SIGN THAT CONFORMS TO
 THE VISUAL CHARACTERS
 REQUIREMENTS OF ICC/ANSI A117.1, ACCESSIBLE AND USABLE
 BUILDINGS
 AND FACILITIES, SHALL BE LOCATED ON THE DOOR LEAF
 ADJACENT TO THE
 RELEASE DEVICE IN THE DIRECTION OF EGRESS, AND SHALL
 READ AS FOLLOWS:
 (A) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED
 IN 15 SECONDS, FOR DOORS THAT SWING IN THE DIRECTION OF
 EGRESS TRAVEL
 (B) PULL UNTIL ALARM SOUNDS, DOOR CAN BE OPENED
 IN 15 SECONDS, FOR DOORS THAT SWING AGAINST THE
 DIRECTION
 OF EGRESS TRAVEL
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-04 Cont ID  
Sent By jleahy Date 2023-05-04 Time 11:34 Rev Time 0.00
Received By jleahy Date 2023-04-20 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By lmarchan Date 2023-04-14 Time 13:06 Rev Time 0.00
Received By lmarchan Date 2023-04-12 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By jleahy Date 2023-04-10 Time 10:49 Rev Time 0.00
Received By jleahy Date 2023-03-31 Time 13:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-05-04 Cont ID  
Sent By jleahy Date 2023-05-04 Time 11:34 Rev Time 0.00
Received By jleahy Date 2023-05-04 Time 11:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-04-10 Cont ID  
Sent By jleahy Date 2023-04-10 Time 10:45 Rev Time 0.00
Received By jleahy Date 2023-04-10 Time 10:43 Sent To  
Notes
2023-04-10 10:48:56FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN.CITY OF WPB
 AMENDMENT 107.2.1, FS 471, 481
  
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM ???LEGAL??? OR ITS
 EQUIVALENT BE USED A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN