2023-04-05 13:50:26 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| REVISION# 23031810 |
| 201 SUMMA ST |
| |
| 1-PROVIDE PRODUCT APPROVAL FOR: |
| |
| (A)ROOF TILE HIP & RIDGE METAL SUPPORT. |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER STATES " EAST COAST METALS |
| RIDGE ADDED TO PRODUCT APPROVAL INDEX: FL5374-R6". |
| PRODUCT APPROVAL WAS NOT SUBMITTED. NEED TO SUBMIT. |
| |
| (B)STRUCTURAL MULLIONS THAT MEETS DESIGN PRESSURES FOR |
| WINDOW "J". |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER STATES " MULLION |
| HIGHLIGHTED PAGE 12 OF MULLION NOA". |
| PAGE 9 OF 25 OF MULLION NOA SPECIFIES 1"X3.125"X.5" |
| ALUMINUM TUBE MULLION. |
| THIS MULLION SIZE DOESN'T MEET THE DESIGN PRESSURES |
| CALCULATED BY THE ARCHITECT OF RECORD. REVISE MULLION |
| SIZE AS REQUIRED. |
| |
| (C)EXTERIOR OUTSWING DOOR ON NEW UNDER STAIR STORAGE. |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER STATES "REFER TO PRODUCT |
| INDEX NOA 20-0406.03". |
| THIS NOA 20-0406.03 IS FOR MULLIONS. REVISE AS REQUIRED |
| AND PROVIDE PRODUCT APPROVAL. |
| |
| (D)EXTERIOR SOLID OUTSWING DOOR ON NEW PRIVACY WALL |
| NEXT TO THE NEW STAIRWAY. |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER STATES "THIS IS A GARDEN |
| GATE. WILL BE ENGINEERED- SHOP DRAWING TO BE |
| SUBMITTED." |
| NOTE: OK. SUBMIT ENGINEERING REVIEWED BY ARCHITECT |
| PRIOR TO INSTALLATION. |
| |
| (E)ENTRY DOOR WITH SIDELITES AS SHOWN ON PLANS. |
| RESPONSE: |
| ARCHITECT'S RESPONSE LETTER STATES "SEE PRODUCT INDEX." |
| PRODUCT APPROVAL LISTED IN THE INDEX WAS NOT SUBMITTED. |
| NEED TO SUBMIT. |
| |
| 2-DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS. |
| |
| 3- REVISED ENERGY CALCULATIONS HAVE A COPY OF THE |
| ENGINEER'S DIGITAL SIGNATURE. NEED ORIGINAL |
| SEAL/SIGNATURE WHEN SUBMITTED FOR PUBLIC RECORDS. |
| ELECTRONIC SUBMITTALS NEED VERIFIABLE DIGITAL |
| SIGNATURE. |
| |
| ENGINEERS |
| 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND |
| SEALING ELECTRONICALLY TRANSMITTED PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| |
| |
| NEW COMMENTS BASED ON REVISED ROOF PRODUCT APPROVALS |
| |
| 3- WINDSOR ROOF TILE NOA LISTED ON PRODUCT APPROVAL |
| INDEX(21-0201.05) AND NOA SUBMITTED(22-0201.05)DON'T |
| MATCH. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 4- NEW ROOF TILE NOA SUBMITTED: CLEARLY IDENTIFY |
| ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| WITH THE REQUIRED UPLIFT MOMENT FOR TILE. SEC R301.2.1 |
| FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH FOAM ADHESIVE COMMENT BELOW. |
| |
| 5- ROOF TILE ADHESIVE NOA SUBMITTED: CLEARLY IDENTIFY |
| ADHESIVE PADDY SIZE TO BE USED AS REQUIRED BY CITY |
| POLICY FOR ALL ROOFING PERMITS TO VERIFY THE REQUIRED |
| UPLIFT MOMENT FOR TILE. SEC R301.2.1 FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH ROOF TILE COMMENT ABOVE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |