2023-04-05 09:41:01 | 1ST GAS REVIEW |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2017 WPB AMEND - 105.1/107.3 - THERE ISN'T A |
| CORRESPONDING GENERATOR PERMIT. WHEN THE GENERATOR |
| PERMIT IS APPLIED FOR, I CAN COMPLY THIS COMMENT. THE |
| PLACEMENT OF THE GAS LINE IS RELATIVE TO THE SEPARATION |
| DISTANCES REQUIRED AND REVIEWED IN THE GENERATOR PERMIT |
| REVIEWS. |
| |
| 2. 2017 WPB AMEND 107.3.5.3 (13) - PROVIDE A FLOOR PLAN |
| THAT OVERLAYS THE GAS ROUTING WITH RESPECT TO THE FLOOR |
| PLAN. SHOW LOCATIONS OF THE FIXTURES WITHIN THE FLOOR |
| PLAN. |
| |
| 3. 2017 WPB AMEND 107.3.5.3 (13) - INCLUDE ROOM SIZING |
| AND COMBUSTION AIR CALCS FOR THE FIREPLACE AND RANGE. |
| |
| 4. 2017 WPB AMEND 107.3.5.3 (13) - ON THE FLOOR PLAN, |
| INCLUDE SEPARATION FROM STRUCTURE OPENINGS. GENERATORS |
| ARE 10 FEET FROM OPENINGS, POOL HEATERS ARE 4 FEET FROM |
| OPENINGS. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |