Plan Review Stops For Permit 23031203 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2023-07-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-26 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-26 |
Time |
10:11 |
Sent To |
|
|
Notes |
2023-07-26 10:18:15 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-9.4 SHOWS A UL X630 THE PRODUCT SHOULD BE | | CARBOLINE CO. - YOU WILL NEED TO REVISE DRAWING A-9.4 | | TO SHOW THE REQUIRED FIRE RATED PRODUCT. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-07 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-07 |
Time |
13:47 |
Sent To |
|
|
Notes |
2023-06-07 13:58:02 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-9.4 SHOWS A UL X630 TO BE USED FOR THE | | COLUMNS - PLEASE PROVIDE THIS UL FIRE RESISTANT | | ASSEMBLY SHOWING THE REQUIRED PAINT THICKNESS FOR THE | | FIRE RATINGS FBC WPB 107.2.1.2 | | | | 2) THE DRAWINGS PROVIDED SHOWING THE MIL THICKNESS | | NEEDS TO SHOW THE PAINT THICKNESS IN INCHES AS PER THE | | UL X630 | | | | 3) DRAWING A-1.2.0 - SHOWS THE COLUMNS TO HAVE A 2 HR | | FIRE RATING - THE DRAWINGS SHOWING THE MILS THICKNESS | | WILL NEED TO SHOW THE THICKNESS IN INCHES AND MEET A 2 | | HR FIRE RATING. | | | | 4) PRODUCT DATA SHEET PROVIDED FOR "CONTEGO" IS NOT THE | | PRODUCT IN THE UL X630 | | | | 5) ICC REPORT ESR-5314 DOES NOT INCLUDE A 2 HR FIRE | | RATING FOR AN HSS COLUMN. | | | | 6) YOU WILL NEED TO REVISE DRAWING A-9.4 TO SHOW THE UL | | DESIGN NUMBER OR ICC REPORT TO BE USED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-25 |
Time |
12:33 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-25 |
Time |
12:33 |
Sent To |
|
|
Notes |
2023-05-25 13:02:08 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWING A-9.4 SHOWS A UL X630 TO BE USED FOR THE | | COLUMNS - PLEASE PROVIDE THIS UL FIRE RESISTANT | | ASSEMBLY SHOWING THE REQUIRED PAINT THICKNESS FOR THE | | FIRE RATINGS FBC WPB 107.2.1.2 | | | | 2) THE DRAWINGS PROVIDED SHOWING THE MIL THICKNESS | | NEEDS TO SHOW THE PAINT THICKNESS IN INCHES AS PER THE | | UL X630 | | | | 3) DRAWING A-1.2.0 - SHOWS THE COLUMNS TO HAVE A 2 HR | | FIRE RATING - THE DRAWINGS SHOWING THE MILS THICKNESS | | WILL NEED TO SHOW THE THICKNESS IN INCHES AND MEET A 2 | | HR FIRE RATING. | | | | 4) PRODUCT DATA SHEET PROVIDED FOR "CONTEGO" IS NOT THE | | PRODUCT IN THE UL X630 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2023-04-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-24 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-24 |
Time |
17:07 |
Sent To |
|
|
Notes |
2023-04-24 17:10:45 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE THE UL TEST REPORTS FOR THIS PRODUCT | | SHOWING THE REQUIRED PAINT THICKNESS FOR THE FIRE | | RATINGS FBC WPB 107.2.1.2 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2023-04-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-07 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-07 |
Time |
09:09 |
Sent To |
|
|
Notes |
2023-04-07 09:12:16 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | THIS IS NOT REQUIRED FOR PLAN REVIEW THIS IS A FIELD | | INSPECTION ITEM. | | | | FOR A PLAN REVIEW THE FOLLOWING ITEMS ARE REQUIRED. | | | | 1) PROVIDE A SIGNED AND SEALED DRAWING FROM THE | | ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH | | COLUMN AND THE INTUMESCENT PAINT THICKNESS. | | | | 2) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS. | | | | 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER - FBC WPB | | 107.2.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-03-21 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-03-21 |
Time |
10:53 |
Sent To |
|
|
Notes |
2023-03-21 11:14:26 | INTUMESCENT PAINT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) THE BUILDING DESIGNER OF RECORD HAS MARKED THE | | SUBMITTAL AS "MAKE CORRECTIONS" - YOU WILL NEED TO MAKE | | THE CORRECTIONS AND SUBMIT A PACKAGE THAT IS MARKED "NO | | EXCEPTION TAKEN". "ARCHITECT NEEDS TO VERIFY THE | | THICKNESS MEETS THE REQUIRED FIRE RATING" | | | | 2) PROVIDE A SIGNED AND SEALED DRAWING FROM THE | | ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH | | COLUMN AND THE INTUMESCENT PAINT THICKNESS. | | | | 3) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2023-07-25 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-07-25 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-07-25 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2023-05-23 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-05-23 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-05-23 |
Time |
13:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-04-07 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-04-07 |
Time |
09:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-03-21 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-03-21 |
Time |
11:53 |
Sent To |
|
|
Notes |
2023-03-21 12:00:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION ON THE SHOP DRAWINGS WITH A | | CHECK MARK "MAKE CORRECTIOND NOTED", HOWEVER, IT IS | | UNCLEAR IF THE SUBMITTED PLANS HAVE THOSE CORRECTIONS. | | | | FOR THE OFFICIAL RECORD, PLEASE INDICATE THAT THOSE | | CORRECTIONS HAVE BEEN INCORPORATED OR SUBMIT PLANS | | SHOWING THOSE CORREECTIONS IN A CLOUD CALLOUT. | | | | | | 2) THE SHOP DRAWINGS INDICATE AN ADDRESS OF 840 N | | DIXIE; HOWEVER, THE PERMIT APPLICATION ADDRESS | | INDICATES 740 N DIXIE. | | | | FOR THE OFFICIAL RECORD, PLEASE INDICATE WHICH ADDRESS | | IS CORRECT AND MAKE APPLICABLE CHANGES. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2023-07-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-26 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-24 |
Time |
16:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2023-06-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-07 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-05 |
Time |
08:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2023-05-25 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-25 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-22 |
Time |
16:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-04-24 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-24 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-19 |
Time |
17:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-04-07 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-04-07 |
Time |
16:28 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-04-06 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-03-21 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-03-20 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2023-07-26 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-26 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-26 |
Time |
10:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-04-07 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-04-07 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-04-07 |
Time |
09:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
N |
Date |
2023-03-21 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-03-21 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-03-21 |
Time |
11:14 |
Sent To |
|
|
Notes |
|
|