Plan Review Details - Permit 23031203
Plan Review Stops For Permit 23031203
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2023-07-26 Cont ID  
Sent By rmcphers Date 2023-07-26 Time 10:11 Rev Time 0.00
Received By rmcphers Date 2023-07-26 Time 10:11 Sent To  
Notes
2023-07-26 10:18:15INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-9.4 SHOWS A UL X630 THE PRODUCT SHOULD BE
 CARBOLINE CO. - YOU WILL NEED TO REVISE DRAWING A-9.4
 TO SHOW THE REQUIRED FIRE RATED PRODUCT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-06-07 Cont ID  
Sent By rmcphers Date 2023-06-07 Time 13:58 Rev Time 0.00
Received By rmcphers Date 2023-06-07 Time 13:47 Sent To  
Notes
2023-06-07 13:58:02INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-9.4 SHOWS A UL X630 TO BE USED FOR THE
 COLUMNS - PLEASE PROVIDE THIS UL FIRE RESISTANT
 ASSEMBLY SHOWING THE REQUIRED PAINT THICKNESS FOR THE
 FIRE RATINGS FBC WPB 107.2.1.2
  
 2) THE DRAWINGS PROVIDED SHOWING THE MIL THICKNESS
 NEEDS TO SHOW THE PAINT THICKNESS IN INCHES AS PER THE
 UL X630
  
 3) DRAWING A-1.2.0 - SHOWS THE COLUMNS TO HAVE A 2 HR
 FIRE RATING - THE DRAWINGS SHOWING THE MILS THICKNESS
 WILL NEED TO SHOW THE THICKNESS IN INCHES AND MEET A 2
 HR FIRE RATING.
  
 4) PRODUCT DATA SHEET PROVIDED FOR "CONTEGO" IS NOT THE
 PRODUCT IN THE UL X630
  
 5) ICC REPORT ESR-5314 DOES NOT INCLUDE A 2 HR FIRE
 RATING FOR AN HSS COLUMN.
  
 6) YOU WILL NEED TO REVISE DRAWING A-9.4 TO SHOW THE UL
 DESIGN NUMBER OR ICC REPORT TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-05-25 Cont ID  
Sent By rmcphers Date 2023-05-25 Time 12:33 Rev Time 0.00
Received By rmcphers Date 2023-05-25 Time 12:33 Sent To  
Notes
2023-05-25 13:02:08INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-9.4 SHOWS A UL X630 TO BE USED FOR THE
 COLUMNS - PLEASE PROVIDE THIS UL FIRE RESISTANT
 ASSEMBLY SHOWING THE REQUIRED PAINT THICKNESS FOR THE
 FIRE RATINGS FBC WPB 107.2.1.2
  
 2) THE DRAWINGS PROVIDED SHOWING THE MIL THICKNESS
 NEEDS TO SHOW THE PAINT THICKNESS IN INCHES AS PER THE
 UL X630
  
 3) DRAWING A-1.2.0 - SHOWS THE COLUMNS TO HAVE A 2 HR
 FIRE RATING - THE DRAWINGS SHOWING THE MILS THICKNESS
 WILL NEED TO SHOW THE THICKNESS IN INCHES AND MEET A 2
 HR FIRE RATING.
  
 4) PRODUCT DATA SHEET PROVIDED FOR "CONTEGO" IS NOT THE
 PRODUCT IN THE UL X630

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 17:10 Rev Time 0.00
Received By rmcphers Date 2023-04-24 Time 17:07 Sent To  
Notes
2023-04-24 17:10:45INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE UL TEST REPORTS FOR THIS PRODUCT
 SHOWING THE REQUIRED PAINT THICKNESS FOR THE FIRE
 RATINGS FBC WPB 107.2.1.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-07 Cont ID  
Sent By rmcphers Date 2023-04-07 Time 09:09 Rev Time 0.00
Received By rmcphers Date 2023-04-07 Time 09:09 Sent To  
Notes
2023-04-07 09:12:16INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 THIS IS NOT REQUIRED FOR PLAN REVIEW THIS IS A FIELD
 INSPECTION ITEM.
  
 FOR A PLAN REVIEW THE FOLLOWING ITEMS ARE REQUIRED.
  
 1) PROVIDE A SIGNED AND SEALED DRAWING FROM THE
 ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH
 COLUMN AND THE INTUMESCENT PAINT THICKNESS.
  
 2) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS.
  
 3) DRAWINGS NEED TO BE SIGNED BY THE DESIGNER - FBC WPB
 107.2.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 10:53 Sent To  
Notes
2023-03-21 11:14:26INTUMESCENT PAINT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE BUILDING DESIGNER OF RECORD HAS MARKED THE
 SUBMITTAL AS "MAKE CORRECTIONS" - YOU WILL NEED TO MAKE
 THE CORRECTIONS AND SUBMIT A PACKAGE THAT IS MARKED "NO
 EXCEPTION TAKEN". "ARCHITECT NEEDS TO VERIFY THE
 THICKNESS MEETS THE REQUIRED FIRE RATING"
  
 2) PROVIDE A SIGNED AND SEALED DRAWING FROM THE
 ARCHITECT THAT SHOWS THE HOURLY FIRE RATING FOR EACH
 COLUMN AND THE INTUMESCENT PAINT THICKNESS.
  
 3) PROVIDE THE INTUMESCENT PAINT MANUFACTURE DETAILS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2023-07-25 Cont ID  
Sent By pleduc Date 2023-07-25 Time   Rev Time 0.00
Received By pleduc Date 2023-07-25 Time 10:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-23 Cont ID  
Sent By pleduc Date 2023-05-23 Time   Rev Time 0.00
Received By pleduc Date 2023-05-23 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By pleduc Date 2023-04-07 Time   Rev Time 0.00
Received By pleduc Date 2023-04-07 Time 09:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-21 Cont ID  
Sent By pleduc Date 2023-03-21 Time   Rev Time 0.00
Received By pleduc Date 2023-03-21 Time 11:53 Sent To  
Notes
2023-03-21 12:00:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION ON THE SHOP DRAWINGS WITH A
 CHECK MARK "MAKE CORRECTIOND NOTED", HOWEVER, IT IS
 UNCLEAR IF THE SUBMITTED PLANS HAVE THOSE CORRECTIONS.
  
 FOR THE OFFICIAL RECORD, PLEASE INDICATE THAT THOSE
 CORRECTIONS HAVE BEEN INCORPORATED OR SUBMIT PLANS
 SHOWING THOSE CORREECTIONS IN A CLOUD CALLOUT.
  
  
 2) THE SHOP DRAWINGS INDICATE AN ADDRESS OF 840 N
 DIXIE; HOWEVER, THE PERMIT APPLICATION ADDRESS
 INDICATES 740 N DIXIE.
  
 FOR THE OFFICIAL RECORD, PLEASE INDICATE WHICH ADDRESS
 IS CORRECT AND MAKE APPLICABLE CHANGES.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-07-26 Cont ID  
Sent By rmcphers Date 2023-07-26 Time 10:20 Rev Time 0.00
Received By rmcphers Date 2023-07-24 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-07 Cont ID  
Sent By rmcphers Date 2023-06-07 Time 13:58 Rev Time 0.00
Received By rmcphers Date 2023-06-05 Time 08:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-05-25 Cont ID  
Sent By rmcphers Date 2023-05-25 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2023-05-22 Time 16:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-24 Cont ID  
Sent By rmcphers Date 2023-04-24 Time 17:10 Rev Time 0.00
Received By rmcphers Date 2023-04-19 Time 17:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-07 Cont ID  
Sent By aoliver Date 2023-04-07 Time 16:28 Rev Time 0.00
Received By aoliver Date 2023-04-06 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-21 Cont ID  
Sent By lmarchan Date 2023-03-21 Time 12:30 Rev Time 0.00
Received By lmarchan Date 2023-03-20 Time 10:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-26 Cont ID  
Sent By rmcphers Date 2023-07-26 Time 10:20 Rev Time 0.00
Received By rmcphers Date 2023-07-26 Time 10:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-07 Cont ID  
Sent By rmcphers Date 2023-04-07 Time 09:16 Rev Time 0.00
Received By rmcphers Date 2023-04-07 Time 09:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-21 Cont ID  
Sent By rmcphers Date 2023-03-21 Time 11:14 Rev Time 0.00
Received By rmcphers Date 2023-03-21 Time 11:14 Sent To  
Notes
***NONE***