Plan Review Stops For Permit 23030984 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
08:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-02 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-02 |
Time |
11:24 |
Sent To |
|
|
Notes |
2023-05-02 11:25:53 | DUMPSTER ENCLOSURE | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) DRAWINGS SAY "NOT FOR CONSTRUCTION" CANNOT HAVE THAT | | STATEMENT ON THE DRAWINGS. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2023-06-13 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-06-13 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-06-13 |
Time |
15:02 |
Sent To |
|
|
Notes |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2023-05-04 |
|
|
Cont ID |
|
Sent By |
lquinone |
Date |
2023-05-04 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
lquinone |
Date |
2023-05-04 |
Time |
15:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-06-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-06-08 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2023-04-13 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-04-13 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-04-13 |
Time |
11:14 |
Sent To |
|
|
Notes |
2023-04-13 11:16:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF COVERING OVER EXISTING FIRE | | LINE THAT WILL ALLOW A VEHICLE TO PASS OVER. | | | | PER NFPA 24 | | | | 10.4.4 PIPE UNDER DRIVEWAYS SHALL BE BURIED AT A | | MINIMUM | | DEPTH OF 3 FT (0.9 M). | | | | THERE IS NO INDICATION OF HOW DEEP THE PIPE IS. | | | | PLEASE INDICATE DIMENSIONS IN COMPLIANCE WITH THE CODE | | OR CORRECT. | | | | | | | | 2) THERE ARE INDICATIONS OF THE LOCATION OF THE | | DUMPSTER IN CLOSE PROXIMITY OF THE DDCV WHERE IS MAY | | BECOME DAMAGED FROM OPENING THE GATE OR BY A VEHILCE IN | | THE PROCESS OF TRASH COLLECTION. | | | | PER NFPA 24 | | | | 6.5 BACKFLOW PREVENTION ASSEMBLIES. | | | | 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED, | | THEY | | SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE | | NEEDED. | | | | PLEASE PROVIDE BOLLARDS OF SIMILARE PROTECTION | | EQUIPMENT. | | | | | | | | 3 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-06-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-06-22 |
Time |
08:32 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-06-07 |
Time |
09:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-05-23 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-05-23 |
Time |
07:25 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-04-12 |
Time |
11:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
PW |
PUBLIC WORKS |
Rev No |
2 |
Status |
P |
Date |
2023-06-21 |
|
|
Cont ID |
|
Sent By |
jbjoseph |
Date |
2023-06-21 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
jbjoseph |
Date |
2023-06-21 |
Time |
10:24 |
Sent To |
|
|
Notes |
2023-06-21 10:25:36 | FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE | | ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY | | OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE | | ENCLOSURE STANDARD, GC-7. | | | | BRUCELY A. JOSEPH | | PW PROGRAM MANAGER | | [email protected] |
|
|
Review Stop |
PW |
PUBLIC WORKS |
Rev No |
1 |
Status |
F |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
jbjoseph |
Date |
2023-05-22 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
jbjoseph |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-05-22 14:28:09 | 1. SCOPE OF SITE WORK IS UNCLEAR. | | 2. DUMPSTER ENCLOSURE APPEARS TO BE IN CLOSE PROXIMITY | | TO THE DDCV ASSEMBLY. PLEASE SHOW ALL DIMENSIONS TO | | ENSURE THAT THERE NO ENCROACHMENTS. | | FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE | | ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY | | OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE | | ENCLOSURE STANDARD, GC-7. | | 3. FURTHER COMMENTS MAY BE FORTHCOMING | | | | BRUCELY A. JOSEPH | | PUBLIC WORKS PROGRAM MANAGER | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-06-08 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-06-08 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-06-08 |
Time |
08:12 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-02 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-02 |
Time |
11:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2023-06-14 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-06-14 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-06-14 |
Time |
09:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-05-18 |
|
|
Cont ID |
|
Sent By |
VBroglia |
Date |
2023-05-18 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-05-18 |
Time |
17:04 |
Sent To |
|
|
Notes |
2023-05-18 17:05:54 | FAILED FOR THE FOLLOWING REASON(S): | | | | 1. SCOPE OF WORK IS UNCLEAR, PLEASE CALL OUT ON THE | | PLANS WHAT "SITE WORK" IS BEING PROPOSED BESIDES THE | | DUMPSTER ENCLOSURE | | | | **** REVIEWD BY **** | | VALENTINA BROGLIA | | PLANNER | | [email protected] | | | | |
|
|