Plan Review Details - Permit 23030984
Plan Review Stops For Permit 23030984
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-06-08 Cont ID  
Sent By rmcphers Date 2023-06-08 Time 08:11 Rev Time 0.00
Received By rmcphers Date 2023-06-08 Time 08:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-05-02 Cont ID  
Sent By rmcphers Date 2023-05-02 Time 11:24 Rev Time 0.00
Received By rmcphers Date 2023-05-02 Time 11:24 Sent To  
Notes
2023-05-02 11:25:53DUMPSTER ENCLOSURE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SAY "NOT FOR CONSTRUCTION" CANNOT HAVE THAT
 STATEMENT ON THE DRAWINGS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2023-06-13 Cont ID  
Sent By lquinone Date 2023-06-13 Time 15:02 Rev Time 0.00
Received By lquinone Date 2023-06-13 Time 15:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2023-05-04 Cont ID  
Sent By lquinone Date 2023-05-04 Time 15:16 Rev Time 0.00
Received By lquinone Date 2023-05-04 Time 15:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-06-08 Cont ID  
Sent By pleduc Date 2023-06-08 Time   Rev Time 0.00
Received By pleduc Date 2023-06-08 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-04-13 Cont ID  
Sent By pleduc Date 2023-04-13 Time   Rev Time 0.00
Received By pleduc Date 2023-04-13 Time 11:14 Sent To  
Notes
2023-04-13 11:16:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF COVERING OVER EXISTING FIRE
 LINE THAT WILL ALLOW A VEHICLE TO PASS OVER.
  
 PER NFPA 24
  
 10.4.4 PIPE UNDER DRIVEWAYS SHALL BE BURIED AT A
 MINIMUM
 DEPTH OF 3 FT (0.9 M).
  
 THERE IS NO INDICATION OF HOW DEEP THE PIPE IS.
  
 PLEASE INDICATE DIMENSIONS IN COMPLIANCE WITH THE CODE
 OR CORRECT.
  
  
  
 2) THERE ARE INDICATIONS OF THE LOCATION OF THE
 DUMPSTER IN CLOSE PROXIMITY OF THE DDCV WHERE IS MAY
 BECOME DAMAGED FROM OPENING THE GATE OR BY A VEHILCE IN
 THE PROCESS OF TRASH COLLECTION.
  
 PER NFPA 24
  
 6.5 BACKFLOW PREVENTION ASSEMBLIES.
  
 6.5.2 WHERE BACKFLOW PREVENTION ASSEMBLIES ARE USED,
 THEY
 SHALL BE PROTECTED AGAINST MECHANICAL DAMAGE WHERE
 NEEDED.
  
 PLEASE PROVIDE BOLLARDS OF SIMILARE PROTECTION
 EQUIPMENT.
  
  
  
 3 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-06-22 Cont ID  
Sent By lmarchan Date 2023-06-22 Time 08:32 Rev Time 0.00
Received By lmarchan Date 2023-06-07 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-05-23 Cont ID  
Sent By aoliver Date 2023-05-23 Time 07:25 Rev Time 0.00
Received By aoliver Date 2023-04-12 Time 11:57 Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 2023-06-21 Cont ID  
Sent By jbjoseph Date 2023-06-21 Time 10:24 Rev Time 0.00
Received By jbjoseph Date 2023-06-21 Time 10:24 Sent To  
Notes
2023-06-21 10:25:36FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, GC-7.
  
 BRUCELY A. JOSEPH
 PW PROGRAM MANAGER
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 2023-05-22 Cont ID  
Sent By jbjoseph Date 2023-05-22 Time 14:27 Rev Time 0.00
Received By jbjoseph Date   Time   Sent To  
Notes
2023-05-22 14:28:091. SCOPE OF SITE WORK IS UNCLEAR.
 2. DUMPSTER ENCLOSURE APPEARS TO BE IN CLOSE PROXIMITY
 TO THE DDCV ASSEMBLY. PLEASE SHOW ALL DIMENSIONS TO
 ENSURE THAT THERE NO ENCROACHMENTS.
 FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, GC-7.
 3. FURTHER COMMENTS MAY BE FORTHCOMING
  
 BRUCELY A. JOSEPH
 PUBLIC WORKS PROGRAM MANAGER
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-06-08 Cont ID  
Sent By rmcphers Date 2023-06-08 Time 08:12 Rev Time 0.00
Received By rmcphers Date 2023-06-08 Time 08:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-05-02 Cont ID  
Sent By rmcphers Date 2023-05-02 Time 11:33 Rev Time 0.00
Received By rmcphers Date 2023-05-02 Time 11:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-06-14 Cont ID  
Sent By vbroglia Date 2023-06-14 Time 09:43 Rev Time 0.00
Received By vbroglia Date 2023-06-14 Time 09:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-05-18 Cont ID  
Sent By VBroglia Date 2023-05-18 Time 17:04 Rev Time 0.00
Received By vbroglia Date 2023-05-18 Time 17:04 Sent To  
Notes
2023-05-18 17:05:54FAILED FOR THE FOLLOWING REASON(S):
  
 1. SCOPE OF WORK IS UNCLEAR, PLEASE CALL OUT ON THE
 PLANS WHAT "SITE WORK" IS BEING PROPOSED BESIDES THE
 DUMPSTER ENCLOSURE
  
 **** REVIEWD BY ****
 VALENTINA BROGLIA
 PLANNER
 [email protected]
  
  