Plan Review Details - Permit 23030722
Plan Review Stops For Permit 23030722 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2023-05-22 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-05-22 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-05-17 |
Time |
16:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2023-04-04 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-04-04 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-03-31 |
Time |
08:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-03-17 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-03-17 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-03-14 |
Time |
10:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2023-05-18 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-05-18 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-05-18 |
Time |
08:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2023-04-03 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-04-03 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-04-03 |
Time |
07:07 |
Sent To |
|
|
Notes |
2023-04-03 07:14:34 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 23030722 | | 4/3/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENT #1 FROM THE 1ST | | REVIEW COPIED BELOW WAS NOT ADDRESSED. THE DEVICE SHALL | | BE LEAD-FREE. | | | | 1) AN RPZ (REDUCED PRESSURE PRINCIPLE ASSEMBLY) IS | | REQUIRED FOR THE POTABLE WATER SERVICE HOWEVER A SPEC | | SHEET FOR A DOUBLE CHECK BACKFLOW HAS BEEN SUBMITTED. | | PLEASE NOTE POTABLE WATER SERVICE BF PREVENTERS SHALL | | MEET THE REQUIREMENTS OF NSF/ANSI/CAN 61 (0.25% MAX | | WEIGHTED AVERAGE LEAD CONTENT). SUBMIT A SPEC SHEET FOR | | A DEVICE THAT MEETS COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2023-03-15 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2023-03-15 |
Time |
16:51 |
Sent To |
|
|
Notes |
2023-03-15 17:13:12 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 23030722 | | 3/15/23 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) AN RPZ (REDUCED PRESSURE PRINCIPLE ASSEMBLY) IS | | REQUIRED FOR THE POTABLE WATER SERVICE HOWEVER A SPEC | | SHEET FOR A DOUBLE CHECK BACKFLOW HAS BEEN SUBMITTED. | | PLEASE NOTE POTABLE WATER SERVICE BF PREVENTERS SHALL | | MEET THE REQUIREMENTS OF NSF/ANSI/CAN 61 (0.25% MAX | | WEIGHTED AVERAGE LEAD CONTENT). SUBMIT A SPEC SHEET FOR | | A DEVICE THAT MEETS COMPLIANCE. | | 2) PROVIDE A A BASIC SITE PLAN SHOWING THE LOCATION OF | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
3 |
Status |
P |
Date |
2023-05-19 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-05-19 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-05-19 |
Time |
11:10 |
Sent To |
|
|
Notes |
2023-05-19 11:11:01 | APPROVED BY DALTON GRIFFITHS |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
2 |
Status |
F |
Date |
2023-04-04 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2023-04-04 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2023-04-04 |
Time |
10:30 |
Sent To |
|
|
Notes |
2023-04-04 10:31:15 | PER RJENKINS - NEED PICTURE SPECS SHOWING 0.25% LEAD | | FREE |
|
|
Review Stop |
PU |
PUBLIC UTILITIES |
Rev No |
1 |
Status |
F |
Date |
2023-03-17 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-03-17 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-03-17 |
Time |
10:47 |
Sent To |
|
|
Notes |
2023-03-17 10:47:43 | FAILED BY RONALD JENKINS - NO LEAD FREE |
|
|
|