Plan Review Stops For Permit 23030657 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
F |
Date |
2023-07-14 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-07-14 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-07-14 |
Time |
11:18 |
Sent To |
|
|
Notes |
2023-07-14 11:18:23 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-09 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-05-09 |
Time |
09:14 |
Sent To |
|
|
Notes |
2023-05-09 09:16:22 | THE NORTH BUILDING 2ND FLOOR HAS A HALF ADDRESS WHICH | | WILL NEED TO BE READDRESSED, THE DOWNSTAIRS FLOOR | | APPEARS TO BE DIVIDED INTO TWO SPACES, PLEASE PROVIDE A | | FLOOR PLAN FOR THE NORTH BUILDING GROUND FLOOR TO SEE | | IF ADDITIONAL ADDRESSES NEED TO BE ASSIGNED. PLEASE | | HAVE OWNER CONTACT [email protected] OR CALL | | 561-805-6659 TO DISCUSS ADDRESSING ISSUES |
|
|
Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
Rev No |
1 |
Status |
N |
Date |
2023-04-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-04-27 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-04-27 |
Time |
11:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-07-18 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-07-18 |
Time |
10:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-04-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-04-27 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-04-27 |
Time |
11:22 |
Sent To |
|
|
Notes |
2023-04-27 11:25:21 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT:23030657 | | | | REVIEWED: 4.27.2023 | | | | FLORIDA BUILDING CODE,7TH EDITION (2020) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC BUILDING | | FBC EXISTING BUILDING | | | | COMMENTS: | | | | AS PER SECTION 107.2.1 | | SHEET A-1 | | PROVIDE FBC PRODUCT APPROVAL FOR NEW IMPOACT WINDOW "A" | | DESIGN PRESSURE ANS WIND LOADS, SAME FOR NEW DOOR "1" | | IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT | | HESITATE TO CONTACT ME | | | | LOUIS BOND, AIA | | BUILDING PLANS EXAMINER II | | DEVELOPMENT SERVICES DEPT. | | BUILDING DIVISION | | 401 CLEMATIS STREET | | WEST PALM BEACH, FLORIDA 33401 | | PH: 561-805-6729 | | FX: 561-805-6676 | | EMAIL: [email protected] | | | | | | NOTES: | | PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-07-24 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-07-24 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-07-24 |
Time |
11:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2023-05-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-05-08 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-05-08 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
N |
Date |
2023-04-26 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-04-26 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-04-26 |
Time |
14:30 |
Sent To |
|
|
Notes |
2023-04-26 14:33:38 | A SINGLE APT DWELLING IS NOT REQUIRED TO HAVE A LIFE | | SAFETY REVIEW BY FIRE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
amcgrego |
Date |
2023-07-12 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2023-05-09 |
Time |
09:16 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2023-04-20 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2023-04-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-04-27 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-04-27 |
Time |
11:15 |
Sent To |
|
|
Notes |
2023-04-27 11:15:41 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2023-07-22 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-07-22 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-05-03 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-05-03 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-05-03 |
Time |
09:29 |
Sent To |
|
|
Notes |
2023-05-03 09:29:28 | 1ST REVIEW FMC | | PERMIT: 23030657 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. | | FEC R101.5.1.1.1 | | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS | | FOR THIS PROJECT. FEC R403.7.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-07-17 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-07-17 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-07-17 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-04-21 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-04-21 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-04-21 |
Time |
09:47 |
Sent To |
|
|
Notes |
2023-04-21 09:51:28 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2020 FRC P2705.1 #5 -- ACCORDING TO THE SCALE, IT | | APPEARS THAT YOUR SHOWER IS ALMOST 36". WITH THE | | DIMENSIONS OF THE BATHROOM, IT APPEARS YOU MAY NOT HAVE | | THE MINIMUM 30" FOR THE LAV AND 30" FOR THE WATER | | CLOSET. PLEASE SHOW THE FIXTURE SPACING TO MEET THIS | | CODE SECTION. | | | | 2. 2020 FRC P3108.2.1 - THE WATER CLOSET AND SHOWER ARE | | BOTH UPSTREAM OF THE VENTED FIXTURE'S CONNECTION TO THE | | HORIZONTALLY WET VENTED BRANCH. ONLY ONE FIXTURE IS | | ALLOWED TO BE UPSTREAM OF THE VENTED FIXTURE'S | | CONNECTION. PLEASE RECONFIGURE. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-07-18 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-07-18 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-04-27 |
|
|
Cont ID |
|
Sent By |
lbond |
Date |
2023-04-27 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
lbond |
Date |
2023-04-27 |
Time |
11:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-05-09 |
|
|
Cont ID |
|
Sent By |
vbroglia |
Date |
2023-04-25 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
vbroglia |
Date |
2023-04-25 |
Time |
14:13 |
Sent To |
|
|
Notes |
2023-05-09 09:17:16 | FAILED FOR THE FOLLOWING REASONS: | | | | 1. PLEASE PROVIDE A SURVEY DATED WITHIN THE LAST TWO | | YEARS | | | | 2. SITE PLAN MUST SHOW THE EXSISTING BUILDING FLOOR | | PLAN AND PROPOSED BUILDING FLOOR PLAN | | | | PER STAFF'S RESEARCH THERE ARE MUTIPLE UNITES ON THE | | PROPERTY AND PLANS DO NOT SHOW THE ENTIRE BUILDING FOOT | | PRINT | | | | VALENTINA BROGLIA | | [email protected] | | | | |
|
|