Plan Review Details - Permit 23030516
Plan Review Stops For Permit 23030516
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-03-13 Cont ID  
Sent By cpuell Date 2023-03-13 Time 07:54 Rev Time 0.00
Received By cpuell Date 2023-03-13 Time 07:54 Sent To  
Notes
2023-03-13 07:54:45ADDRESS APPROPRIATE FOR PROJECT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-04-10 Time   Rev Time 0.00
Received By amcgrego Date 2023-04-07 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-13 Cont ID  
Sent By cpuell Date 2023-03-13 Time 07:54 Rev Time 0.00
Received By cpuell Date 2023-03-08 Time 15:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-10 Cont ID  
Sent By ccole Date 2023-04-10 Time 08:44 Rev Time 0.00
Received By ccole Date 2023-04-10 Time 07:47 Sent To  
Notes
2023-04-10 08:55:082ND REVIEW FBC-2020 PLUMBING
 PERMIT-23030516
 4/10/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. IMPORTANT NOTE. THE
 FOLLOWING REVIEW IS FOR PLUMBING ONLY. A SEPARATE
 TENANT BUILD-OUT PERMIT FOR THE COMMERCIAL KITCHEN
 AND/OR NEW RESTAURANT IS REQUIRED.
  
 1) THE NEW PLUMBING DRAWINGS ARE NOT IN COMPLIANCE WITH
 THE FOLLOWING FPC-2020 CODE SECTIONS.
  
 A) SEC. 910.1 & 1003.3.5: AS NOTED IN THE 1ST REVIEW, A
 TRAP AND VENT ARE REQUIRED FOR THE 3-COMPARTMENT SINK.
 MANUFACTURER???S INSTALL GUIDELINES FOR THE SCHIER GB-1
 SHOW SINK TRAP AND VENT UPSTREAM OF THE INTERCEPTOR.
 B) SEC. 918.8: AN AAV SHALL NOT BE USED TO VENT THE
 GREASE TRAP.
 C) SEC. 904.1: THE BUILDING DRAIN REQUIRES NOT LESS
 THAN ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS.
 D) SEC. 608.3: A BACKFLOW PREVENTER IS REQUIRED FOR THE
 WATER SUPPLY LINE TO THE ICE MAKER.
 E) SEC. 801.2: AN INDIRECT WASTE RECEPTOR IS REQUIRED
 TO RECEIVE THE DRAINAGE FROM THE ICE MAKER.
  
 2) PLEASE NOTE OTHER LICENSING AGENCIES SUCH AS THE PB
 DEPARTMENT OF HEALTH, DBPR FOOD AND BEVERAGE LICENSING
 DEPT. OR DEPT. OF AGRICULTURE MAY REQUIRE A FLOOR DRAIN
 IN THE KITCHEN FOR SANITARY PURPOSES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By ccole Date 2023-03-09 Time 16:07 Rev Time 0.00
Received By ccole Date 2023-03-09 Time 14:43 Sent To  
Notes
2023-03-09 16:08:041ST REVIEW FBC-2020 PLUMBING
 PERMIT-23030516
 3/9/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR THE
 GREASE INTERCEPTOR AND DUE TO A CHANGE IN PROCESS THE
 PERMIT APPLICATION SHALL BE SUBMITTED PRIOR TO THE MAIN
 PLUMBING PLAN REVIEW APPROVAL. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS. THE
 COMMENTS BELOW WILL APPLY TO BOTH THE MAIN PLUMBING
 PERMIT AND THE SEPARATE GREASE INTERCEPTOR PERMIT.
  
 2) SUBMIT A MANUFACTURER'S SPECIFICATION SHEET FOR THE
 IRONWALLS INTERCEPTOR THAT INDICATES THE UNIT MEETS
 EITHER THE ASME AND/OR PDI DESIGN AND TESTING STANDARD
 FOR HYDROMECHANICAL GREASE INTERCEPTORS AS REQUIRED BY
 SEC. 1003.3.5; OR THE IAPMO/ANSI Z1001 STANDARD FOR
 GRAVITY GREASE INTERCEPTORS AS REQUIRED BY SEC.
 1003.3.7 FBC P. I WAS UNABLE TO LOCATE TESTING STANDARD
 INFORMATION ONLINE FOR THE UNIT.
  
 3) PROVIDE GREASE WASTE SIZING CALCULATIONS IN
 ACCORDANCE WITH SECS.1003.3.5 FBC P FOR HYDROMECHANICAL
 TYPES OR 1003.3.7 FOR GRAVITY TYPES.
  
 4) WATER ISOMETRIC DRAWING: HOT WATER SHALL BE
 DELIVERED FROM THE 3-COMPARTMENT SINK AND THE HANDSINK
 HOWEVER THE DRAWING SHOWS ONLY COLD WATER BEING
 SUPPLIED TO THE FIXTURES- SEC. 607.1 FBC P. PLEASE NOTE
 A MEANS OF LIMITING THE HOT WATER TEMPERATURE AT THE
 FIXTURES SUCH AS ASSE APPROVED MIXING VALVES SHALL BE
 PROVIDED- SEC. 607.1.1 FBC P.
  
 4) SANITARY ISOMETRIC: PLEASE CORRECT THE DRAWINGS PER
 ITEMS A, B, & C BELOW. PLEASE NOTE THAT INSTALLATION OF
 THE INTERCEPTOR AND ASSOCIATED PLUMBING PIPING SHALL BE
 IN COMPLIANCE WITH THE MANUFACTURER'S INSTALLATION
 GUIDELINES WHICH SHALL BE ONSITE FOR INSPECTION- SECS.
 1003.3.5 & 1003.3.7 FBC P.
  
 A) THE INTERCEPTOR DISCHARGE PIPE SHALL BE DIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE PIPE, NOT INDIRECTLY
 AS THE DRAWING SHOWS- SEC. 1003.3.8 FBC P.
  
 B) BASED ON OTHER MANUFACTURER'S INSTALLATION
 GUIDELINES THE TYPICAL INSTALLATION FOR AN INTERCEPTOR
 MOUNTED ON THE FLOOR, INSTEAD OF UNDER THE FLOOR, IS TO
 PROVIDE A TRAP AND VENT PIPE FOR THE 3-COMPARTMENT SINK
 AND DIRECT PIPE CONNECTIONS IN AND OUT OF THE UNIT.
 SOME MANUFACTURER'S REQUIRE A FLOW CONTROL AIR INTAKE
 PIPE AND A VENT FOR THE DISCHARGE PIPE. PLEASE CONSULT
 THE MANUFACTURER'S GUIDELINES. IF THE INTERCEPTOR IS
 INSTALLED UNDER THE FLOOR TYPICALLY AN INDIRECT WASTE
 RECEPTOR WITH TRAP AND VENT SHALL BE PROVIDED FOR THE
 3-COMPARTMENT WITH DIRECT FIXTURE DRAIN AND DISCHARGE
 PIPE CONNECTIONS. AS NOTE ABOVE MANUFACTURER'S
 GUIDELINES WILL ALSO APPLY.
  
 C) PROVIDE AN INDIVIDUAL AAV FOR THE HANDSINK FIXTURE
 DRAIN- TABLE 909.1 & SEC. 918.3 FBC P.
  
 5) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 SHALL BE ON THE DRAWINGS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-10 Cont ID  
Sent By ccole Date 2023-04-10 Time 08:55 Rev Time 0.00
Received By ccole Date 2023-04-10 Time 07:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-09 Cont ID  
Sent By ccole Date 2023-03-09 Time 16:12 Rev Time 0.00
Received By ccole Date 2023-03-09 Time 16:12 Sent To  
Notes
2023-03-09 16:13:461ST SIGNATURE REVIEW
 PERMIT-23030516
 3/9/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PRINTED NAME AND SIGNATURE OF THE CONTRACTOR
 SHALL BE ON THE DRAWINGS- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  