2023-03-20 10:35:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION ON THE APPLICATION OF |
| "FLOORING REPLACEMENT", BUT NO SPEC SHEET NOR A PRODUCT |
| NAME FOR THE ACTUAL PROPOSED VINYL FLOORING. |
| |
| FLOORING IS MANUFACTURED AROUND THE WORLD BUT NOT ALL |
| ARE TESTED AND MEETING LISTED AND NFPA STANDARDS. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE FLOORING |
| TYPE AND NAME AND THE PRODUCT SPEC SHEETS INDICATING |
| THE FIRE BEHAVIOR RATING. |
| |
| IF THE PROPOSED FLOORING IS PORCELAIN/CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, PRODUCT SPEC SHEETS |
| WOULD NOT BE REQUIRED. |
| |
| PRODUCT SPEC SHEETS ARE REQUIRED FOR LVT, VINYL |
| FLOORING, WOOD/VINYL LAMINATES, ETC. |
| |
| |
| |
| 2) THERE ARE INDICATIONS ON THE FLOOR PLAN SHEET OF |
| BLUE & PINK OUTLINES ALONG THE WALL AROUND THE KITCHEN. |
| |
| THERE ARE NO INDICATIONS OF WHAT THESE LINES REPRESENT. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PLEASE PROVIDE DETAILS OF THESE COLOR LINES REPRESENT. |
| |
| |
| |
| 3) THERE ARE INDICATIONS ON THE FLOOR PLAN SHEET OF |
| NUMERIC INDICATORS OF 1 THRU 4. |
| |
| THERE ARE NO INDICATIONS OF WHAT THESE NUMBERS |
| REPRESENT. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS |
| |
| PLEASE PROVIDE DETAILS OF THESE NUMBERS REPRESENT. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |