Plan Review Stops For Permit 23030502 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2023-07-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-05 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-05 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-05-02 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-05-02 |
Time |
11:38 |
Sent To |
|
|
Notes |
2023-05-02 11:45:04 | TRAILER | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE A SITE PLAN SHOWING THE TRAILER | | LOCATION AND SET BACKS FROM PROPERTY LINES AND EXISTING | | BUILDINGS. | | | | 2) PLEASE STATE ON THE SITE PLAN WHAT THE TRAILER WILL | | BE USED FOR - (FOR CONSTRUCTION PURPOSES?) | | | | 3) THERE MAY BE ADDITIONAL COMMENTS BASED ON THE USE OF | | THE TRAILER. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2023-07-10 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-07-10 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-07-10 |
Time |
09:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-04-26 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-04-26 |
Time |
14:57 |
Sent To |
|
|
Notes |
2023-04-26 15:12:24 | ELECTRIC REVIEW FAILED | | | | 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM INCLUDING | | ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND | | OVERCURRENT PROTECTION SIZES. NEC 215.5 | | | | 215.5 DIAGRAMS OF FEEDERS. | | IF REQUIRED BY THE AUTHORITY HAVING JURISDICTION, A | | DIAGRAM SHOWING FEEDER DETAILS SHALL BE PROVIDED PRIOR | | TO THE INSTALLATION OF THE FEEDERS. SUCH A DIAGRAM | | SHALL SHOW THE AREA IN SQUARE FEET OF THE BUILDING OR | | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL | | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE | | DEMAND FACTORS USED, THE CALCULATED LOAD AFTER APPLYING | | DEMAND FACTORS, AND THE SIZE AND TYPE OF CONDUCTORS TO | | BE USED. | | | | 2) PLEASE PROVIDE A SITE PLAN LOCATING ALL ELECTRICAL | | EQUIPMENT. FBC 107.2 | | | | FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2023-07-03 |
|
|
Cont ID |
|
Sent By |
clfranci |
Date |
2023-07-03 |
Time |
|
Rev Time |
0.00 |
Received By |
clfranci |
Date |
2023-07-03 |
Time |
|
Sent To |
|
|
Notes |
2023-07-03 11:03:30 | PRIOR COMMENTS WERE NOT ALL ADDRESSED. | | | | 1. WHERE IS THE FIRE DEPARMENT ACCESS PROVIDED? | | | | 2. WHERE ARE THE ACCESS TO WATER SUPPLY FOR THE FIRE | | DEPARTMENT IN CASE OF AN EMERGENCY? | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2023-04-17 |
|
|
Cont ID |
|
Sent By |
cwalker |
Date |
2023-04-17 |
Time |
|
Rev Time |
|
Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2023-04-17 10:30:21 | PROVIDE A SITE PLAN FOR THE PROPOSED MOBILE STRUCTURE | | TO INCLUDE LOCATION ON THE PROPERTY, FIRE DEPARTMENT | | ACCESS, WATER SUPPLY, DISTANCE TO OTHER STRUCTURES, | | ETC. TO ALLOW FOR AN ADEQUATE PLAN REVIEW. NFPA 1, 1.14 | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
amcgrego |
Date |
2023-06-30 |
Time |
09:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
aoliver |
Date |
2023-06-01 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
aoliver |
Date |
2023-04-14 |
Time |
16:28 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2023-07-18 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2023-07-18 |
Time |
12:00 |
Rev Time |
0.00 |
Received By |
jbaker |
Date |
2023-07-18 |
Time |
12:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-04-26 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-04-26 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-04-26 |
Time |
16:38 |
Sent To |
|
|
Notes |
2023-04-26 16:39:00 | 1ST REVIEW FMC | | PERMIT: 23030502 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE CHANGE THE PERMIT APPLICATION TO REFLECT WHAT | | THE USE OF THIS TRAILER WILL BE AT THIS ADDRESS. | | | | 2) PROVIDE THE THIRD PARTY STAMP ON THE DOCUMENTS FOR | | THIS TRAILER. | | | | 3) IT APPEARS THE DIGITAL SIGNATURE OF THE DRAWINGS ARE | | COPIES OF THE ORIGINAL DIGITAL SIGNATURE. PLEASE SUBMIT | | THE ORIGINAL DIGITALLY SIGNED DOCUMENTS. FS 471/481 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2023-07-01 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-07-01 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-07-01 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2023-04-19 |
|
|
Cont ID |
|
Sent By |
rwbrown |
Date |
2023-04-19 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
rwbrown |
Date |
2023-04-19 |
Time |
10:40 |
Sent To |
|
|
Notes |
2023-04-19 10:43:43 | 1ST PLUMBING REVIEW | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMEND - 105.1/107.3 -- THE BACKFLOW DEVICE | | AT THE UTILITY CONNECTION IS REQUIRED TO CONNECT THE | | TRAILER TO POTABLE WATER. WHEN YOU HAVE APPLIED FOR THE | | BACKFLOW, YOU CAN NOTIFY ME AND I CAN COMPLY THIS | | COMMENT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
P |
Date |
2023-07-05 |
|
|
Cont ID |
|
Sent By |
rmcphers |
Date |
2023-07-05 |
Time |
09:10 |
Rev Time |
0.00 |
Received By |
rmcphers |
Date |
2023-07-05 |
Time |
09:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2023-04-26 |
|
|
Cont ID |
|
Sent By |
mpeterso |
Date |
2023-04-26 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
mpeterso |
Date |
2023-04-26 |
Time |
15:12 |
Sent To |
|
|
Notes |
2023-04-26 15:13:09 | SIGNED AND SEALED PLANS ARE FOUND IN THE SIGNATURE | | FOLDER |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-06-01 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2023-06-01 |
Time |
14:11 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2023-06-01 |
Time |
14:11 |
Sent To |
|
|
Notes |
2023-06-01 14:13:35 | FAILED | | | | 1) PROVIDE A SITE PLAN AND SURVEY SHOWING THE LOCATION | | OF THE TRAILER AND THE SETBACKS FROM THE PROPERTY | | LINES. | | | | 2) ADDITIONAL COMMENTS MAY BE PROVIDED UPON SUBMITTAL | | OF THE SITE PLAN AND SURVEY. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] |
|
|