Plan Review Details - Permit 23030293
Plan Review Stops For Permit 23030293
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-03-29 Cont ID  
Sent By cpuell Date 2023-03-29 Time 09:39 Rev Time 0.00
Received By cpuell Date 2023-03-29 Time 09:39 Sent To  
Notes
2023-03-29 09:39:51WARRANTY DEED PROVIDED, UPDATED PARCEL.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By cpuell Date 2023-03-02 Time 06:55 Rev Time 0.00
Received By cpuell Date 2023-03-02 Time 06:55 Sent To  
Notes
2023-03-02 06:55:54PLEASE PROVIDE A WARRANTY DEED SO THAT WE CAN UPDATE
 THE OWNER INFORMATION, THE OWNER ON THE APPLICATION
 FORM DOES NOT MATCH THE OWNER INFORMATION ON THE PBC
 PROPERTY APPRAISERS, IF THIS WAS A MISTAKE PLEASE
 RESUBMIT THE APPLICATION FORM WITH THE CORRECT OWNER OR
 EMAIL DEED TO [email protected]

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2023-03-29 Cont ID  
Sent By lbond Date 2023-03-29 Time 16:04 Rev Time 0.00
Received By lbond Date 2023-03-29 Time 16:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2023-05-09 Cont ID  
Sent By lbond Date 2023-05-09 Time 08:36 Rev Time 0.00
Received By lbond Date 2023-05-09 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 09:23 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 09:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By lbond Date 2023-03-29 Time 16:13 Rev Time 0.00
Received By lbond Date 2023-03-29 Time 16:13 Sent To  
Notes
2023-03-29 16:13:58SEE SIGNATURE COMMENT.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-18 Cont ID  
Sent By rperdomo Date 2023-05-18 Time 14:11 Rev Time 0.00
Received By rperdomo Date 2023-05-18 Time 14:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-05-02 Cont ID  
Sent By rperdomo Date 2023-05-02 Time 16:04 Rev Time 0.00
Received By rperdomo Date 2023-05-02 Time 15:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-06 Cont ID  
Sent By rperdomo Date 2023-04-06 Time 10:57 Rev Time 0.00
Received By rperdomo Date 2023-04-06 Time 10:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2023-05-09 Cont ID  
Sent By pleduc Date 2023-05-09 Time   Rev Time 0.00
Received By pleduc Date 2023-05-09 Time 09:53 Sent To  
Notes
2023-05-09 09:56:42FIRE PROVISO:
  
 ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By cwalker Date 2023-04-26 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2023-04-26 09:34:09FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE,
 INCLUDING PAINTING, DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL ONLY BE CONDUCTED BY
 PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (4) (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE A FIRE WATCH.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-28 Cont ID  
Sent By cwalker Date 2023-03-28 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2023-03-28 10:22:45FIRE PROVISO COMMENTS:
  
 (1) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL REMAIN OPERATIONAL DURING ALL
 PHASES OF DEMOLITION AND CONSTRUCTION.
  
 (2) ALL EXISTING LIFE SAFETY SYSTEMS (FIRE SPRINKLER
 AND/OR FIRE ALARM) SHALL BE PROTECTED FROM DAMAGE,
 INCLUDING PAINTING, DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
  
 (3) ANY WORK PERFORMED ON ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) SHALL BE ONLY BE CONDUCTED
 BY PROPERLY LICENSED CONTRACTORS UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 (4) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE
 SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS
 HOURS IN DURATION WILL REQUIRE A FIRE WATCH.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-05-19 Cont ID  
Sent By aoliver Date 2023-05-19 Time 07:30 Rev Time 0.00
Received By aoliver Date 2023-05-08 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-05-03 Cont ID  
Sent By aoliver Date 2023-05-03 Time 09:49 Rev Time 0.00
Received By aoliver Date 2023-04-21 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-07 Cont ID  
Sent By aoliver Date 2023-04-07 Time 07:12 Rev Time 0.00
Received By aoliver Date 2023-03-24 Time 11:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2023-03-29 Cont ID  
Sent By lbond Date 2023-03-29 Time 16:12 Rev Time 0.00
Received By lbond Date 2023-03-29 Time 16:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2023-05-09 Cont ID  
Sent By medwards Date 2023-05-09 Time 15:22 Rev Time 0.00
Received By medwards Date 2023-05-09 Time 15:22 Sent To  
Notes
2023-05-09 15:22:38NO MECHANICAL WORK SHOWN IN SCOPE OF WORK. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-05-02 Cont ID  
Sent By medwards Date 2023-05-02 Time 11:23 Rev Time 0.00
Received By medwards Date 2023-05-02 Time 11:20 Sent To  
Notes
2023-05-02 11:22:33SHEET D-1 STILL HAS A NOTE IN THE DINING ROOM THAT
 STATES: REMOVE AND REPLACE HVAC DUCT IN CEILINGS.
 PROVIDE THE ANSWERS TO THE ORIGINAL COMMENTS BELOW:
  
 SHEET D-1 NOTE INDICATES THE MECHANICAL SCOPE OF WORK
 IS TO REMOVE AND REPLACE HVAC DUCT IN CEILINGS OF
 DINING ROOM,KITCHEN, MASTER BEDROOM AND BATH. PROVIDE A
 DEMO PLAN OF THIS DUCT WORK ALONG WITH THE NEW DUCT
 WORK LAYOUT, INCLUDE SIZES ON THE DEMO AND NEW DUCTWORK
 LAYOUT. FBC 107.3.5. A MECHANICAL SUB-PERMIT WILL ALSO
 BE REQUIRED BEFORE WORK IS STARTED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-04-06 Cont ID  
Sent By medwards Date 2023-04-04 Time 06:12 Rev Time 0.00
Received By medwards Date 2023-04-04 Time 06:12 Sent To  
Notes
2023-04-04 06:16:25SHEET D-1 NOTE INDICATES THE MECHANICAL SCOPE OF WORK
 IS TO REMOVE AND REPLACE HVAC DUCT IN CEILINGS OF
 DINING ROOM,KITCHEN, MASTER BEDROOM AND BATH. PROVIDE A
 DEMO PLAN OF THIS DUCT WORK ALONG WITH THE NEW DUCT
 WORK LAYOUT, INCLUDE SIZES ON THE DEMO AND NEW DUCTWORK
 LAYOUT. FBC 107.3.5. A MECHANICAL SUB-PERMIT WILL ALSO
 BE REQUIRED BEFORE WORK IS STARTED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2023-05-11 Cont ID  
Sent By ccole Date 2023-05-11 Time 16:38 Rev Time 0.00
Received By ccole Date 2023-05-11 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By ccole Date 2023-04-24 Time 08:02 Rev Time 0.00
Received By ccole Date 2023-04-24 Time 07:56 Sent To  
Notes
2023-04-24 08:03:252ND REVIEW- FBC 2020 PLUMBING
 PERMIT- 23030293
 4/24/23
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. 2ND REQUEST FOR DIGITALLY
 SIGNED AND SEALED PLANS.
  
 1) THE PLUMBING FOR THE PROJECT WILL BE PASSED WHEN
 DIGITALLY SIGNED AND SEALED PLANS ARE RESUBMITTED- FL.
 STATUTE 471.025 AND SEC. 61G15-23.005 FAC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By ccole Date 2023-04-04 Time 12:05 Rev Time 0.00
Received By ccole Date 2023-04-04 Time 11:56 Sent To  
Notes
2023-04-04 12:06:221ST REVIEW- FBC 2020 PLUMBING
 PERMIT- 23030293
 4/4/23
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLUMBING FOR THE PROJECT WILL BE PASSED WHEN
 DIGITALLY SIGNED AND SEALED PLANS ARE RESUBMITTED- FL.
 STATUTE 471.025 AND SEC. 61G15-23.005 FAC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-05-26 Cont ID  
Sent By dbattles Date 2023-05-26 Time 13:46 Rev Time 0.00
Received By dbattles Date 2023-05-26 Time 13:46 Sent To  
Notes
2023-05-26 13:47:29PRIVATE PROVIDER FOR INSPECTIONS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-05-09 Cont ID  
Sent By lbond Date 2023-05-09 Time 08:36 Rev Time 0.00
Received By lbond Date 2023-05-09 Time 08:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2023-04-24 Cont ID  
Sent By lbond Date 2023-04-24 Time 09:22 Rev Time 0.00
Received By lbond Date 2023-04-24 Time 09:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By lbond Date 2023-03-29 Time 16:07 Rev Time 0.00
Received By lbond Date 2023-03-29 Time 16:07 Sent To  
Notes
2023-03-29 16:20:34BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23030293
  
 REVIEWED: MARCH 29,2023
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE PLANS SHEETS FOR THE PROJECT ARE NOT DIGITALLY
 SIGNED BY THE ARCHITECT OF RECORD AS REQUIRED BY FL.
 STATUTE AND SEC.: 61G1-16.005 FLORIDA ADMINISTRATIVE
 CODE. PLANS TRANSMITTED ELECTRONICALLY SHALL BEAR
 DIGITAL SIGNATURES AND SEALS CAPABLE OF BEING VERIFIED.
 THE PLANS SUBMITTED FOR REVIEW ARE COPIES OF A SIGNED
 AND SEALED PAPER PLANS.
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-03-23 Cont ID  
Sent By avolcy Date 2023-03-23 Time 12:30 Rev Time 0.00
Received By avolcy Date 2023-03-23 Time 12:30 Sent To  
Notes
***NONE***