Plan Review Details - Permit 23030286
Plan Review Stops For Permit 23030286 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2023-03-20 |
|
|
Cont ID |
|
Sent By |
rperdomo |
Date |
2023-03-20 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
rperdomo |
Date |
2023-03-20 |
Time |
12:16 |
Sent To |
|
|
Notes |
2023-03-20 15:12:17 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW | | | | 1. PROVIDE LOAD CALCULATION AND LOAD SHADDING IN | | ACCORDANCE WITH NEC 220, 700 | | | | END OF COMMENTS | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | RUBEN PEREZ PERDOMO, P.E. | | ELECTRICAL PLANS EXAMINER | | 561-805-6738 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2023-03-08 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2023-03-08 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2023-03-08 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2023-04-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-04-14 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-03-07 |
Time |
12:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
Sent By |
medwards |
Date |
2023-03-15 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
medwards |
Date |
2023-03-15 |
Time |
11:23 |
Sent To |
|
|
Notes |
2023-03-15 11:29:18 | THIS PROJECT WILL NEED A SEPARATE FUEL PIPING PERMIT | | AND A MECHANICAL REVEW. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|
|
Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
Rev No |
1 |
Status |
F |
Date |
2023-04-13 |
|
|
Cont ID |
|
Sent By |
rgathrig |
Date |
2023-04-13 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
rgathrig |
Date |
2023-04-13 |
Time |
10:05 |
Sent To |
|
|
Notes |
2023-04-13 10:07:23 | PERMIT APPLICATION IS MARKED AS PRIVATE PROVIDER | | INSPECTIONS ONLY. NO NOTICE TO BUILDING OFFICIAL | | SUBMITTED | | NOR ANY OF THE OTHER REQUIRED PP DOCUMENTS. | | PLEASE PROVIDE | | | | RICHARD GATHRIGHT | | 561 805 6679 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2023-04-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2023-04-14 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2023-04-14 |
Time |
10:04 |
Sent To |
|
|
Notes |
2023-04-14 10:05:44 | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | AND SEALED BY THE ENGINEER OF RECORD |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2023-04-11 |
|
|
Cont ID |
|
Sent By |
ESchneid |
Date |
2023-04-11 |
Time |
15:59 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2023-04-11 |
Time |
15:59 |
Sent To |
|
|
Notes |
2023-04-11 15:59:30 | FAILED | | | | 1) RESOLUTION NO. 13-19 REQUIRES THAT THE FULL HEIGHT | | OF THE GENERATOR IS SCREENED. THE GENERATOR SHOP | | DRAWINGS SHOW THE GENERATOR, PLUS PAD, AT 12.3 FEET | | ABOVE THE LEVEL OF THE GENERATOR PIT. PROVIDE A CROSS | | SECTION DRAWING VERIFYING THAT THE SIX-FOOT-HIGH FENCE | | AND EIGHT-FOOT-HIGH HEDGE SHOWN ON THE APPROVED PLANS | | SCREEN THE FULL HEIGHT OF THE GENERATOR. | | | | CONTACT ERIC SCHNEIDER @ 561-822-1446 | | [email protected] | | |
|
|
|