Plan Review Details - Permit 23030259
Plan Review Stops For Permit 23030259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-05 Cont ID  
Sent By pvalenti Date 2023-04-05 Time 10:40 Rev Time 0.00
Received By pvalenti Date 2023-04-05 Time 10:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-24 Cont ID  
Sent By pvalenti Date 2023-03-24 Time 07:24 Rev Time 0.00
Received By pvalenti Date 2023-03-24 Time 07:14 Sent To  
Notes
2023-03-24 07:33:43PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 OPENINGS #4 & 5 (12" O.C.) ANCHORING AS NOTED ON THE
 SHUTTER SCHEDULE DOES NOT MATCH THE REQUIREMENTS FROM
 THE PRODUCT APPROVAL FL 1850-R14, INSTALLATION
 INSTRUCTIONS ON SHEET 12 OF 20.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-05 Cont ID  
Sent By pvalenti Date 2023-04-05 Time 10:40 Rev Time 0.00
Received By pvalenti Date 2023-03-28 Time 09:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-24 Cont ID  
Sent By pvalenti Date 2023-03-24 Time 07:38 Rev Time 0.00
Received By pvalenti Date 2023-03-22 Time 08:56 Sent To  
Notes
***NONE***