Plan Review Details - Permit 23021442
Plan Review Stops For Permit 23021442
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 13:51 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 13:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By lbond Date 2023-03-02 Time 11:13 Rev Time 0.00
Received By lbond Date 2023-03-02 Time 11:13 Sent To  
Notes
2023-03-02 11:15:58BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23021442
  
 REVIEWED: MARCH 2, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS REVIEW:
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 13:52 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 13:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-03-02 Cont ID  
Sent By lbond Date 2023-03-02 Time 11:12 Rev Time 0.00
Received By lbond Date 2023-03-02 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 12:23 Rev Time 0.00
Received By mpeterso Date 2023-03-15 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By pleduc Date 2023-04-17 Time   Rev Time 0.00
Received By pleduc Date 2023-04-17 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2023-03-02 Cont ID  
Sent By pleduc Date 2023-03-02 Time   Rev Time 0.00
Received By pleduc Date 2023-03-02 Time 10:53 Sent To  
Notes
2023-03-02 11:06:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A PROPOSED NEW STORAGE
 ROOM WITH 2-HOUR RATED WALLS; HOWEVER, THERE IS NO
 INDICATION OF A FIRE RATED DOOR ASSEMBLY TO THIS ROOM.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE A RATED DOOR ASSEMBLY EQUAL TO PROPOSED
 RATED WALLS.
  
  
 2) THERE IS NO INDICATION OF WHAT IS BEING PROPOSED TO
 STORE WITHIN THIS STORAGE ROOM
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE DETAILS ON THE PROPOSED STORAGE
 MATERIALS/COMMODITY/HAZARD CLASSIFICATIONS.
  
  
 3) THERE IS NO INDICATION OF THE RACKS/SHELVING TYPE,
 LOCATION AND HEIGHT BEING USED IF ANY.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE DETAILS OF THE RACKS/SHELVING TYPE,
 LOCATION AND HEIGHT.
  
  
 4) THERE IS NO INDICATIONS OF EXISTING FIRE SPRINKLER
 PROTECTION.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS
 EXISTING FIRE SPRINKLER PROTECTION.
  
  
 5) THERE IS NO INDICATIONS OF EXISTING FIRE ALARM
 PROTECTION.
  
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS
 EXISTING FIRE ALARM PROTECTION AND THE LOCATION OF ANY
 DEVICES WITHIN THIS ROOM.
  
  
 6) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AS TO WHAT
 SYSTEM MAYBE EXISTING.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 13:56 Rev Time 0.00
Received By lbond Date 2023-04-14 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-15 Cont ID  
Sent By mpeterso Date 2023-03-15 Time 12:23 Rev Time 0.00
Received By mpeterso Date 2023-03-01 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2023-03-07 Cont ID  
Sent By medwards Date 2023-03-07 Time 09:37 Rev Time 0.00
Received By medwards Date 2023-03-07 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2023-03-06 Cont ID  
Sent By ccole Date 2023-03-06 Time 10:58 Rev Time 0.00
Received By ccole Date 2023-03-06 Time 10:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-17 Cont ID  
Sent By lbond Date 2023-04-17 Time 13:56 Rev Time 0.00
Received By lbond Date 2023-04-17 Time 13:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-02 Cont ID  
Sent By ccole Date 2023-03-02 Time 07:41 Rev Time 0.00
Received By ccole Date 2023-03-02 Time 07:41 Sent To  
Notes
2023-03-02 07:44:25SIGNATURES ON PAPER PLANS APPROVED AND ROUTED TO
 STORAGE.