2023-03-02 11:06:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF A PROPOSED NEW STORAGE |
| ROOM WITH 2-HOUR RATED WALLS; HOWEVER, THERE IS NO |
| INDICATION OF A FIRE RATED DOOR ASSEMBLY TO THIS ROOM. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE PROVIDE A RATED DOOR ASSEMBLY EQUAL TO PROPOSED |
| RATED WALLS. |
| |
| |
| 2) THERE IS NO INDICATION OF WHAT IS BEING PROPOSED TO |
| STORE WITHIN THIS STORAGE ROOM |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE PROVIDE DETAILS ON THE PROPOSED STORAGE |
| MATERIALS/COMMODITY/HAZARD CLASSIFICATIONS. |
| |
| |
| 3) THERE IS NO INDICATION OF THE RACKS/SHELVING TYPE, |
| LOCATION AND HEIGHT BEING USED IF ANY. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| PLEASE PROVIDE DETAILS OF THE RACKS/SHELVING TYPE, |
| LOCATION AND HEIGHT. |
| |
| |
| 4) THERE IS NO INDICATIONS OF EXISTING FIRE SPRINKLER |
| PROTECTION. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS |
| EXISTING FIRE SPRINKLER PROTECTION. |
| |
| |
| 5) THERE IS NO INDICATIONS OF EXISTING FIRE ALARM |
| PROTECTION. |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| FOR THE OFFICIAL RECORD PLEASE INDICATE IF THERE IS |
| EXISTING FIRE ALARM PROTECTION AND THE LOCATION OF ANY |
| DEVICES WITHIN THIS ROOM. |
| |
| |
| 6) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND |
| EQUIPMENT. |
| |
| DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM |
| DEVICES/EQUIPMENT. |
| |
| THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| DEMO AND CONSTRUCTION. |
| |
| PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT AS TO WHAT |
| SYSTEM MAYBE EXISTING. |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |