Plan Review Details - Permit 23021417
Plan Review Stops For Permit 23021417
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-03-13 Cont ID  
Sent By cpuell Date 2023-03-13 Time 09:05 Rev Time 0.00
Received By cpuell Date 2023-03-13 Time 09:05 Sent To  
Notes
2023-03-13 09:09:26APPLICATION LIST SPACES 3 4 AND 5, HOWEVER THOSE ARE
 NOT THE CORRECT SUITE ADDRESSES FOR THAT BUILDING, IS
 THE INTENT TO MERGE THOSE SUITE SPACES, IF SO SINGULAR
 SUITE ADDRESS WOULD NEED TO BE ASSIGNED. PLEASE CONTACT
 [email protected] OR CALL 561-805-659 TO DISCUSS
 ADDRESSING ISSUES.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By jwitmer Date 2023-03-29 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2023-03-29 Time 06:46 Sent To  
Notes
2023-03-29 14:11:53COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By jwitmer Date 2023-03-29 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2023-03-29 Time 06:46 Sent To  
Notes
2023-03-29 06:47:08WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 23021417
 ADD: 242PARK PL.
 CONT: MDI GENERAL CONTRACTORS
 TEL: 561-346-6916
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MARCH 29TH/2023
 ACTION: DENIED
  
 1) SITE ADDRESS ONLY REQUIRES ADDRESSING TO ASSIGN
 TENANT SUITE/ UNIT NUMBERS.
 2020 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 2) DISCREPANCY IN PLANS. THE COVER SHEET LIST A
 MERCANTILE OCCUPANCY, 5882 SQ. FT/ 60 SQ. FT/ OCC= 98
 OCCUPANTS WHEREAS THE 1.1A LIFE SAFETY SHEET LIST
 OFFICE SPACE @ 100 SQ. FT= 59 OCCUPANTS. NOTE FOR
 BUSINESS OCCUPANCY PLEASE USE THE OCCUPANT LOAD FACTOR
 OF 150 SQ. FT./ OCCUPANT 2020 FBC BUILDING TABLE
 1004.5. WHICH IS IT MERCANTILE OR BUSINESS OCCUPANCY?
  
 3) BOTH THE A1.1A AND LIFE SAFETY FLOOR PLAN SHOW
 COMMON LOBBY JUST OUTSIDE OF THE LEFT OR REAR WALL,
 PLEASE CORRECT THIS IS AN EXIT ACCESS CORRIDOR, DOES
 NOT NEED TO BE RATED. CLARIFY TERMINOLOGY. 2020 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1. CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4) THE LIFE SAFETY PLAN NOR A1.1A BOTTOM LEFT CORNER OF
 THE TENANT SPACE THE ROOM LEADING TO THE EXIT, IS NOT
 LABELED THE USE, IT APPEARS TO BE MORE OF A STORAGE
 AREA? YOU CAN NOT HAVE EXITING THROUGH A STORAGE ROOM.
 2010 FBC-BUILDING SECTION 1016.2.5 EGRESS SHALL NOT
 PASSTHROUGH STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES.
  
 5) LIFE SAFETY PLAN. ON THE RIGHT SIDE OF THE TENANT
 SPACE TO THE COMMON LOBBY THE EGRESS DOORS ARE IN
 SWINGING DOORS. THE BASE BUILDING PERMIT 21051228,
 REVISION 22090701 SHOWS THESE DOORS OUT SWINGING INTO
 THE COMMON AREA, THEY WERE THE ASSIGNED MEANS OF EGRESS
 DOORS FOR THIS SIDE OF THE TENANT SPACE. 2020
 FBC-BUILDING CODE SECTION 1010.1.2.1 DIRECTION OF
 SWING.
  
 6) THE LIFE SAFETY PLAN NOR A1.1A UPPER MIDDLE LEFT
 CORNER OF THE TENANT SPACE THE ROOM LABELED DESIGN
 STUDIO SHOW THE EXIT LIGHT TO THE EXIT ACCESS CORRIDOR,
 BUT THERE IS NO DIRECTIONAL LIGHT LEADING THE OCCUPANTS
 TO THE DESIGN STUDIO. EXIT DIRECTIONAL LIGHTS REQUIRED.
 1013.1 WHERE REQUIRED. 2020FBC-BUILDING CODE.
  
 7) THE LIFE SAFETY PLAN NOR A1.1A THE DOORS LEADING
 INTO THE DESIGN STUDIO, SHOULD SWING IN THE DIRECTION
 OF EGRESS TRAVEL WHEN THE OCCUPANT LOADS ARE 50 OR
 MORE, SEE 1010.1.2.1 DIRECTION OF SWING.
  
 8) LIFE SAFETY PLAN NOTE 10 NEEDS THE FOLLOWING
 NOTATION ON THE PLANS, THIS SIGN SHALL BE IN LETTERS 1
 INCH HIGH ON A CONTRASTING BACKROUND.1010.1.9.3.2.2.
  
 9) SHEET 1.0A FLOOR PLAN SHOWS A KITCHENETTE WITH
 WHEELCHAIR, IS THIS AN ACTIVE COUNTER AND SINK BASE
 CABINET AND COUNTERTOP? IF SO, PROVIDE DETAIL IN
 COMPLIANCE WITH 606 LAVATORIES AND SINKS> 2020
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2023-04-06 Cont ID  
Sent By rperdomo Date 2023-04-06 Time 15:31 Rev Time 0.00
Received By rperdomo Date 2023-04-06 Time 15:05 Sent To  
Notes
2023-04-06 15:36:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF THE PROTECTION (BREAKER) FOR
 PANEL P6. NEC 240
  
 2. SMOKE ALARMS (SMOKE DETECTION) SYSTEM AND CO (CARBON
 MONOXIDE) DETECTION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA 72, FBC 907, IRC 314, IRC 315
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 RUBEN PEREZ PERDOMO, P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6738
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-10 Cont ID  
Sent By pleduc Date 2023-03-10 Time   Rev Time 0.00
Received By pleduc Date 2023-03-10 Time 14:26 Sent To  
Notes
2023-03-10 14:51:17FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-10 Cont ID  
Sent By cthroop Date 2023-04-10 Time 11:06 Rev Time 0.00
Received By cthroop Date 2023-03-09 Time 09:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-03-29 Cont ID  
Sent By jwitmer Date 2023-03-29 Time 14:13 Rev Time 0.00
Received By jwitmer Date 2023-03-29 Time 06:46 Sent To  
Notes
2023-03-29 14:13:42IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected].
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM???S 2W01-2W14 WEST PALM BEACH, FL.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-15 Cont ID  
Sent By medwards Date 2023-03-15 Time 09:02 Rev Time 0.00
Received By medwards Date 2023-03-15 Time 09:02 Sent To  
Notes
2023-03-15 09:03:011ST REVIEW FMC
 PERMIT:
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW ON THE MECHANICAL DRAWING THE RETURN AIR PATH
 FROM THE DESIGN STUDIO TO EXISTING RTU-1 WHEN THE DOORS
 ARE CLOSED. FMC 601.6
  
 2) WHAT WAS THE PREVIOUS OCCUPANCY OF THIS SPACE? IT
 APPEARS THAT IT WAS STORAGE. IF SO PROVIDE THE REQUIRED
 CHANGE OF USE APPLICATION. IF IT IS A CHANGE OF USE
 FROM STORAGE TO MERCANTILE PROVIDE THE ENERGY
 CALCULATIONS AND MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW OCCUPANCY. THE EXISTING RTUS
 WOULD NOT HAVE BEEN SIZED ON A SHELL PERMIT AS THE USE
 OF SPACE WOULD HAVE BEEN KNOW. FEBC 301.3
  
 3) THE MECHANICAL DRAWING SPECIFIES 3 EXISTING RTUS BUT
 THE AERIAL VIEW DOES NOT SHOW RTUS ON THE ROOF OF THIS
 BUILDING. PLEASE EXPLAIN. FBC 107.3.5
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON THE
 OCCUPANCY CLASSIFICATION FROM TABLE 403.3.1.1 THAT MOST
 CLOSELY RESEMBLES EACH USE OF SPACE IN THIS NEW TENANT
 SPACE. IT APPEARS THAT THIS SPACE HAS OFFICES, A LOBBY,
 CONFERENCE ROOMS. FMC 403.3.1.1 AND TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-04 Cont ID  
Sent By rwbrown Date 2023-04-04 Time 14:26 Rev Time 0.00
Received By rwbrown Date 2023-04-04 Time 14:25 Sent To  
Notes
2023-04-04 14:36:481ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - SHOW THE REQUIRED SERVICE SINK
 AND DRINKING FOUNTAIN AS REQUIRED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-04-10 Cont ID  
Sent By cthroop Date 2023-04-10 Time 11:06 Rev Time 0.00
Received By cthroop Date 2023-04-10 Time 10:57 Sent To  
Notes
2023-03-15 09:03:49MECHANICAL DIGITAL SIGNATURES APPROVED ME