Plan Review Details - Permit 23021308
Plan Review Stops For Permit 23021308
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2023-04-21 Cont ID  
Sent By lbond Date 2023-04-21 Time 09:55 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 09:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-03-15 Cont ID  
Sent By lbond Date 2023-03-15 Time 09:40 Rev Time 0.00
Received By lbond Date 2023-03-15 Time 09:40 Sent To  
Notes
2023-03-15 09:41:45BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23021308
  
 REVIEWED: MARCH 15, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS REVIEW:
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 23020793
  
 REVIEWED: MARCH 2, 2023
  
 FLORIDA BUILDING CODE,7TH EDITION (2020)
 FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC BUILDING
 FBC EXISTING BUILDING
  
 COMMENTS:
  
 ASBESTOS REVIEW:
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-
 QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML
  
 IF YOU HAVE ANY QUESTIONS OR CONCERNS, PLEASE DO NOT
 HESITATE TO CONTACT ME
  
 LOUIS BOND, AIA
 BUILDING PLANS EXAMINER II
 DEVELOPMENT SERVICES DEPT.
 BUILDING DIVISION
 401 CLEMATIS STREET
 WEST PALM BEACH, FLORIDA 33401
 PH: 561-805-6729
 FX: 561-805-6676
 EMAIL: [email protected]
  
  
 NOTES:
 PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-04-21 Cont ID  
Sent By lbond Date 2023-04-21 Time 10:00 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 10:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2023-03-15 Cont ID  
Sent By lbond Date 2023-03-15 Time 09:44 Rev Time 0.00
Received By lbond Date 2023-03-15 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2023-04-06 Cont ID  
Sent By mpeterso Date 2023-04-06 Time 09:37 Rev Time 0.00
Received By mpeterso Date 2023-04-06 Time 09:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2023-04-20 Cont ID  
Sent By pleduc Date 2023-04-20 Time   Rev Time 0.00
Received By pleduc Date 2023-04-20 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-03-09 Cont ID  
Sent By pleduc Date 2023-03-09 Time   Rev Time 0.00
Received By pleduc Date 2023-03-08 Time 15:04 Sent To  
Notes
2023-03-09 15:00:09FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2023-04-26 Time   Rev Time 0.00
Received By aoliver Date 2023-04-19 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-04-07 Cont ID  
Sent By lbond Date 2023-04-07 Time 09:03 Rev Time 0.00
Received By lbond Date 2023-03-07 Time 09:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-05-04 Cont ID  
Sent By aoliver Date 2023-05-04 Time 09:48 Rev Time 0.00
Received By aoliver Date 2023-04-28 Time 07:37 Sent To  
Notes
2023-05-04 09:47:29NO IMPACT FEES DUE, SEE EMAIL UPLOADED AO
2023-04-28 07:37:524/28/23 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2023-04-07 Cont ID  
Sent By lbond Date 2023-04-07 Time 09:02 Rev Time 0.00
Received By lbond Date 2023-04-07 Time 09:02 Sent To  
Notes
2023-04-07 09:03:02CHANGE OF USE
  
 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By medwards Date 2023-04-26 Time 07:46 Rev Time 0.00
Received By medwards Date 2023-04-26 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2023-03-14 Cont ID  
Sent By medwards Date 2023-03-14 Time 16:32 Rev Time 0.00
Received By medwards Date 2023-03-14 Time 16:32 Sent To  
Notes
2023-03-14 16:32:431ST REVIEW FMC
 PERMIT: 23021308
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CALCULATION WOULD NEED TO BE: 3285
 SF MEDIA CENTER: 3285/ 1000 = 3.285; 3.285 X 25 = 83
 OCCUPANTS; 83 X 10 = 830 CFM FOR PEOPLE; 3285 SF X .12
 = 394 CFM FOR THE SPACE; 830 + 394 = 1224 CFM OF
 REQUIRED OUTDOOR AIR. FMC 403.3.1.1 AND TABLE
 403.3.1.1.
  
 2) SHOW THE SMOKE DETECTOR FOR THE NEW VAV. FMC 606.2.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2023-04-26 Cont ID  
Sent By ccole Date 2023-04-26 Time 14:21 Rev Time 0.00
Received By ccole Date 2023-04-26 Time 13:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2023-04-03 Cont ID  
Sent By ccole Date 2023-04-03 Time 15:10 Rev Time 0.00
Received By ccole Date 2023-04-03 Time 13:48 Sent To  
Notes
2023-04-03 15:11:201ST REVIEW FBC-2020 PLUMBING
 PERMIT-23021308
 4/3/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1.1 & P3.1: THE URINAL FIXTURE DRAIN CANNOT
 CONNECT TO THE 3-INCH HORIZONTAL WET VENT FOR THE
 BATHROOM FIXTURES- SEC. 202 & 912.1 FBC P. RELOCATE THE
 DRAIN CONNECTION EITHER UPSTREAM OR DOWNSTREAM OF THE
 WET VENT.
  
 2) P2.1 & P3.1: THE THERMOSTAT CONTROL ON THE WATER
 HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER
 DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING DEVICE
 FOR THE PURPOSE OF HOT WATER DELIVERY. THIS CAN BE
 ACCOMPLISHED BY INSTALLING A MASTER THERMOSTATIC MIXING
 VALVE AT THE WATER HEATER. THIS WOULD BE IN ADDITION TO
 THE REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC
 HAND-WASHING- SEC. 607.1.1 FBC P.
  
 3) P2.1 & P3.1: PROVIDE A THERMAL EXPANSION CONTROL
 DEVICE AT THE WATER HEATER- SEC. 607.3 FBC P.
  
 4) P3.1: PROVIDE A PLUMBING FIXTURE SCHEDULE AND A
 EQUIPMENT SCHEDULE FOR THE WATER HEATER- SEC. 404.1 &
 502.1 FBC P.
  
 5) A4.01: PROVIDE THE FOLLOWING DETAILS IN COMPLIANCE
 WITH THE FBC ACC.
  
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SEC. 604.3.
  
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SEC. 606.2.
  
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
  
 D) CENTERLINES OF THE ACCESSIBLE WATER CLOSETS FROM THE
 SIDE WALLS- SEC. 604.2.
  
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
  
 F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- SEC. 606.3.
  
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
  
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
  
 I) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 J) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2
  
 K) CLEAR FLOOR SPACE DIMENSIONS FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2.
  
 L) KNEE AND TOE CLEARANCES FOR THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SEC. 602.2.
  
 M) SPOUT HEIGHTS- SECS. 602.4 & 602.7.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-04-04 Cont ID  
Sent By rgathrig Date 2023-04-04 Time 11:47 Rev Time 0.00
Received By rgathrig Date 2023-04-04 Time 11:46 Sent To  
Notes
2023-04-04 11:48:06PRIVATE PROVIDER INSPECTIONS ONLY
 PACIFICA ENGINEERING WESLEY FOSTER
  
 REG

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-04-21 Cont ID  
Sent By lbond Date 2023-04-21 Time 10:01 Rev Time 0.00
Received By lbond Date 2023-04-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2023-03-15 Cont ID  
Sent By lbond Date 2023-03-15 Time 09:27 Rev Time 0.00
Received By lbond Date 2023-03-15 Time 09:27 Sent To  
Notes
2023-03-15 09:43:37ALL DISCIPLINES DIGITALLY SIGNED-PASSED
2023-03-14 16:33:31MECHANICAL DIGITAL SIGNATURES APPROVED ME