Plan Review Details - Permit 23020661
Plan Review Stops For Permit 23020661
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2023-03-15 Cont ID  
Sent By cpuell Date 2023-03-15 Time 11:02 Rev Time 0.00
Received By cpuell Date 2023-03-15 Time 11:02 Sent To  
Notes
2023-03-15 11:03:18WORK TO BE DONE ON UNITS 1 AND 2

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2023-02-18 Cont ID  
Sent By cpuell Date 2023-02-18 Time 08:10 Rev Time 0.00
Received By cpuell Date 2023-02-18 Time 08:10 Sent To  
Notes
2023-02-18 08:12:02PLANS LIST THAT THE WORK IS TO BE DONE ON UNTIS 1 AND 2
 HOWEVER THE APPLICATION FORM DOES NOT LIST THE TWO
 UNITS. PLEASE CONFIRM THAT THE WORK IS FOR UNITS 1 AND
 2, PLEASE RESPOND TO [email protected] OR CALL
 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 15:42 Rev Time 0.00
Received By jgomez Date 2023-04-24 Time 15:18 Sent To  
Notes
2023-04-24 15:43:05RESIDENTIAL(R2) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020661
 1006 10TH ST
  
 1- FLOORING SOUND INSULATION MATERIAL:
  
 ORIGINAL COMMENT:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA
 SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS
 WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST
 REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE
 USED.
  
 ORIGINAL COMMENT:
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA
 SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS
 WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST
 REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE
 USED.
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
  
  
 ORIGINAL COMMENT:
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 INFORMATION SUBMITTED NOW IS ONLY THE PRODUCT DATA
 SHEET FOR WHISPER MAT UNDERLAYMENT. THIS IS NOT WHAT IS
 WAS REQUESTED. THE REQUEST IS FOR THE UNDERLAYMENT TEST
 REPORT AS REQUIRED ABOVE FOR FLOORING INSULATION TO BE
 USED.
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION
 ( WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED
 FLOOR FINISH.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-04-05 Cont ID  
Sent By jgomez Date 2023-04-05 Time 09:12 Rev Time 0.00
Received By jgomez Date 2023-04-05 Time 08:44 Sent To  
Notes
2023-04-05 09:12:35RESIDENTIAL (R2) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020661
 1006 10TH ST
  
 1- FLOORING SOUND INSULATION MATERIAL:
  
 PREVIOUS COMMENT:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 RESPONSE:
 SPECIFICATIONS SUBMITTED ARE FOR FLASHING INFORMATION.
 THIS IS NOT WHAT IS WAS REQUESTED. THE REQUEST IS FOR
 THE FLOORING SOUND INSULATION TO BE USED NOT FOR
 FLASHING. NEED TO PROVIDE COPY OF TEST REPORT AS
 REQUIRED ABOVE FOR FLOORING INSULATION TO BE USED.
  
 PREVIOUS COMMENT:
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SPECIFICATIONS SUBMITTED ARE FOR FLASHING INFORMATION.
 THIS IS NOT WHAT IS WAS REQUESTED. THE REQUEST IS FOR
 THE FLOORING SOUND INSULATION TO BE USED NOT FOR
 FLASHING. NEED TO PROVIDE COPY OF TEST REPORT AS
 REQUIRED ABOVE FOR FLOORING INSULATION TO BE USED.
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH.
  
 PREVIOUS COMMENT:
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 RESPONSE:
 SPECIFICATIONS SUBMITTED ARE FOR FLASHING INFORMATION.
 THIS IS NOT WHAT IS WAS REQUESTED. THE REQUEST IS FOR
 THE FLOORING SOUND INSULATION TO BE USED NOT FOR
 FLASHING. NEED TO PROVIDE COPY OF TEST REPORT AS
 REQUIRED ABOVE FOR FLOORING INSULATION TO BE USED.
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-03-20 Cont ID  
Sent By jgomez Date 2023-03-20 Time 18:12 Rev Time 0.00
Received By jgomez Date 2023-03-20 Time 18:05 Sent To  
Notes
2023-03-20 18:12:36RESIDENTIAL (R2) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #23020661
 1006 10TH ST
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 1- FLOORING SOUND INSULATION MATERIAL:
 (A)PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
  
 (B)PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
  
 (C)PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR/CEILING
 CONSTRUCTION AND PROPOSED FLOOR FINISH.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2023-02-21 Cont ID  
Sent By pleduc Date 2023-02-21 Time   Rev Time 0.00
Received By pleduc Date 2023-02-21 Time 12:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-24 Cont ID  
Sent By amcgrego Date 2023-04-24 Time 08:52 Rev Time 0.00
Received By amcgrego Date 2023-04-24 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-24 Cont ID  
Sent By jgomez Date 2023-04-24 Time 15:57 Rev Time 0.00
Received By jgomez Date 2023-04-21 Time 18:59 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-05 Cont ID  
Sent By jgomez Date 2023-04-05 Time 09:12 Rev Time 0.00
Received By jgomez Date 2023-04-05 Time 08:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-20 Cont ID  
Sent By jgomez Date 2023-03-20 Time 18:13 Rev Time 0.00
Received By jgomez Date 2023-02-16 Time 08:26 Sent To I
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-03-20 Cont ID  
Sent By jgomez Date 2023-03-20 Time 18:12 Rev Time 0.00
Received By jgomez Date 2023-03-20 Time 18:09 Sent To  
Notes
2023-03-20 18:13:15NO ARCH. OR ENG'R. JG.