Plan Review Details - Permit 23020635
Plan Review Stops For Permit 23020635
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2023-02-27 Cont ID  
Sent By cpuell Date 2023-02-27 Time 11:32 Rev Time 0.00
Received By cpuell Date 2023-02-27 Time 11:32 Sent To  
Notes
2023-02-27 11:39:40ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2023-02-28 Cont ID  
Sent By pvalenti Date 2023-02-28 Time 15:32 Rev Time 0.00
Received By pvalenti Date 2023-02-28 Time 15:17 Sent To  
Notes
2023-02-28 15:34:15PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-
 QUALITY/ASBESTOS-DEMOLITION-RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2023-02-28 Cont ID  
Sent By pvalenti Date 2023-02-28 Time 15:39 Rev Time 0.00
Received By pvalenti Date 2023-02-28 Time 15:17 Sent To  
Notes
2023-02-28 16:04:23PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED, MORE INFORMATION IS REQUIRED:
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING
 CODE, BUILDING 3303:
  
 1. ELECTRIC: CONSIDERING THAT THIS IS FOR A PARTIAL
 DEMO, PROVIDE AN ELECTRIC PERMIT FOR DISCONNECTING THE
 ELECTRIC FROM AREAS TO BE DEMOLISHED.
  
 2. UTILITY RELEASE - GAS: PROVIDE A FLORIDA PUBLIC
 UTILITIES (GAS) RELEASE IF GAS IS TO BE
 REMOVED/DISCONNECTED FROM STRUCTURE. CONSIDERING THIS
 IS A PARTIAL DEMO, IF THERE IS NO GAS AT AREAS TO BE
 DEMOLISHED, PLEASE PROVIDE CONFIRMATION.
  
 3. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, REQUEST FOR METER PULL, ON
 THEIR FORM "DEMOLITION APPLICATION"
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
 THIS IS APPLICABLE IF SECTION OF DEMOLITION INVOLVES
 REMOVAL OF FOOTINGS, PLEASE CONFIRM.
  
 WATERDOWN METHOD:
 IF A WATER TRUCK IS DESIRED, PROVIDE DETAILED
 INFPRMATION OF THE WATER TRUCK SUCH AS: THE
 GALLON CAPACITY OF THE WATER TANK AND A LETTER
 INCLUDING A STATEMENT THAT THE WATER
 USED WILL BE POTABLE AND FROM AN OFF-SITE LOCATION ONLY
 AND WILL BE ON-SITE AT ALL TIMES
 DURING DEMOLITION.
 IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED
 ON THEIR FORM. IF THE BACKFLOW PREVENTER DEVICE IS
 SELECTED, A PLUMBING PERMIT IS REQUIRED. BEFORE
 SCHEDULING THE 703(PLUMBING FINAL INSPECTION), THE
 BACKFLOW DEVICE NEEDS TO BE TESTED AND CERTIFIED BY
 THE CITY???S UTILITIES DEPT, 561-822-2244. FAX THE
 COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183.
  
 4. SEWER LATERAL CAPPING PERMIT IS REQUIRED (SUBMIT
 APPLICATION TO BUILDING DIVISION);
 SCHEDULE A FINAL PLUMBING #703.
 PLEASE CONFIRM IF SEWER LATERAL IS TO BE
 REMOVED/CAPPED.
  
 5. EXTERMINATION LETTER - LETTER FROM A LICENSED PEST
 CONTROL COMPANY STATING THAT
 DEMOLITION ADDRESS HAS BEEN INSPECTED AND/OR TREATED
 FOR RODENTS.
  
 6. COMPLETE THE DEMO DEBRIS FORM: HTTP://WPB.ORG/DEPART
 MENTS/DEVELOPMENT-SERVICES/FORMS/BUILDING-PERMIT-FORMS
 IF THE FORM IS NOT AVAILABLE ONLINE, SEND A REQUEST FOR
 THE FORM TO [email protected].
  
 7. PROVIDE A SITE PLAN OR SURVEY SPECIFICALLY SHOWING
 LOCATION OF THE AREAS OF STRUCTURE TO BE DEMOLISHED,
 FBC 107.
  
 8. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 9. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING
 ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 10. PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2023-03-06 Cont ID  
Sent By rrossano Date 2023-03-06 Time   Rev Time  
Received By rrossano Date 2023-03-06 Time   Sent To  
Notes
2023-03-06 09:13:41ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By amhamilt Date 2023-03-03 Time 11:13 Rev Time 0.00
Received By amhamilt Date 2023-03-03 Time 11:13 Sent To  
Notes
2023-03-03 11:14:49THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PROPERTY IS IN A HISTORIC DISTRICT, ANY DEMOLITION OR
 ALTERATIONS REQUIRES APPROVAL BY HISTORIC PRESERVATION
 BOARD. FULL DEMOLITION WOULD REQUIRE SIMULTANEOUS NEW
 CONSTRUCTION PLANS. PLEASE REACH OUT FOR COA FORM AND
 TO DISCUSS PROPOSED DEMOLITION FURTHER AS SITE
 PLAN/DESCRIPTION IS UNCLEAR.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-03-07 Cont ID  
Sent By aoliver Date 2023-03-07 Time 08:59 Rev Time 0.00
Received By aoliver Date 2023-02-27 Time 10:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2023-02-28 Cont ID  
Sent By pvalenti Date 2023-02-28 Time 15:34 Rev Time 0.00
Received By pvalenti Date 2023-02-28 Time 15:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2023-03-03 Cont ID  
Sent By amhamilt Date 2023-03-03 Time 11:12 Rev Time 0.00
Received By amhamilt Date 2023-03-03 Time 11:12 Sent To  
Notes
2023-03-03 11:13:26THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 SEE HISTORIC COMMENT. PROPERTY IS IN A HISTORIC
 DISTRICT.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  